Display image
Description
P_1937
Offset flow EA (l/s)
0 l/s
Min -100
Max 100
Indicates the offset flow in the
extract air duct.
P_1938
Economy flow, % from Normal flow
50 %
Min 3
Max 100
Indicates how large portion of
the normal flow that should be
economy flow.
P_1939
Min SA1 Pressure (Pa)
0 Pa
Min 0
Max 100
Indicates what the lowest
pressure could be in supply air
duct 1, in order to ensure the
function.
P_1940
SA1 mV at 0% output
0 mV
Min 0
Max 5000
Indicates the Volt signal
transmitted to the actuator on
a 0% output signal from the
controller.
Resolution = 50 mV
P_1941
SA1 mV at 100% output
10000 mV
Min 5000
Max 10000
Indicates the Volt signal
transmitted to the actuator on
a 100% output signal from the
controller.
Resolution = 50 mV
P_1942
SA2 mV at 0% output
0 mV
Min 0
Max 5000
Indicates the Volt signal
transmitted to the actuator on
a 0% output signal from the
controller.
Resolution = 50 mV
P_1943
SA2 mV at 100% output
10000 mV
Min 5000
Max 10000
Indicates the Volt signal
transmitted to the actuator on
a 100% output signal from the
controller.
Resolution = 50 mV
P_1944
EA mV at 0% output
0 mV
Min 0
Max 5000
Indicates the Volt signal
transmitted to the actuator on
a 0% output signal from the
controller.
Resolution = 50 mV
P_1945
EA mV at 100% output
10000 mV
Min 5000
Max 10000
Indicates the Volt signal
transmitted to the actuator on
a 100% output signal from the
controller.
Resolution = 50 mV
P_1946
SA1 damper after sensor error
50 %
Min 0
Max 100
Displays start position on supply
air 1 after an error on the
sensor.
P_1947
SA2 damper after sensor error
10 %
Min 0
Max 100
Indicates the start position on
supply air 2 after an error on
the sensor.
P_1948
EA damper after sensor error
50 %
Min 0
Max 100
Indicates start position on the
extract air after an error on the
sensor.
CONDUCTOR
W4
60
Swegon reserves the right to make design changes.. 20210201
Содержание 20210201
Страница 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Страница 2: ......
Страница 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Страница 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Страница 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Страница 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Страница 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...