P_1925
C02 max level ppm
1000 ppm
Min 350
Max 2000
Indicates at which carbon
dioxide content in the room the
airflow should be increased to
the highest flow.
P_1926
ppm C02 / Volt
200 ppm/volt
Min 10
Max 500
Indicates how the controller
converts the CO
2
signal to an
0-10V output signal.
Example: At 200ppm/Volt,
800ppm will product a 4V
output signal.
P_1927
Emergency func, SA mode
0
Min 0
Max 1
Indicates which blade position
the damper in the supply air
duct should have in event of
fire.
0 = Closed
1 = Open
P_1928
Emergency func, EA damper
0
Min 0
Max 1
Indicates which blade position
the damper in the extract air
duct should have in event of
fire.
0 = Closed
1 = Open
P_1929
SA1 Flow sen, 0=NP, 1=Ana, 2=MB
2
Min 0
Max 2
Indicates whether pressure
sensor in supply air duct 1 is
connected and if so of what
type.
0 = No sensor connected.
1 = Analogue sensor.
2 = ModBus.
P_1930
SA2 Flow sen, 0=NP, 1=Active
0
Min 0
Max 1
Indicates whether the pressure
sensor in supply air duct 2 is
connected.
0 = No sensor connected.
1 = Sensor connected.
P_1931
EA Flow sen, 0=NP, 1=Active
0
Min 0
Max 1
Indicates whether the pressure
sensor is connected in the
extract air duct.
0 = No sensor connected.
1 = Sensor connected.
P_1932
Reg. sequence, 0=A-W, 1=W-A
1
Min 0
Max 1
Indicates the sequence
according to which the
controller should manage air
and water.
0 = Air - Water
1 = Water - Air
P_1933
Normal flow SA1 (l/s)
20 l/s
Min 5
Max 5000
Indicates which normal flow in
supply air duct 1 should be set,
in the AUTO operating mode.
P_1934
Boost flow SA1 (l/s)
30 l/s
Min 0
Max 5000
Indicates which flow in supply
air duct 1 should be set for
BOOST.
P_1935
Boost flow SA2 (l/s)
30 l/s
Min 0
Max 5000
Indicates which flow in supply
air duct 2 that should be set for
BOOST.
P_1936
Parameter not used.
59
20210201 Swegon reserves the right to make design changes.
CONDUCTOR
W4
Содержание 20210201
Страница 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Страница 2: ......
Страница 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Страница 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Страница 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Страница 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Страница 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...