Conductor W4 BMS, applies to software from 1.48
Default values from parameter file
Input
register
16 bit integer register
Read only
Modbus
Name
Min/Max
Remarks
Default
3x0001
Component Name ID
0/10
ID for type of controller in Conductor and
Wise system
00003
3x0002
- 0017
Component Name
0/999
Name built of max 16 chr, exch chr (ASCII
standard)
0
3x0018
Application ID
3x0019
HW Serial No.
3x0020
SW version
3x0021
Not used
3x0022
Application state
0/9
0=Init, 1=Auto Normal, 2=Auto
Economy, 3=Manual, 4=Standby,
5=Emergency, 6=NightCool,
7=TimerFunction, 9=Holiday
3x0023
Not used
3x0024
Not used
3x0025
Time since last boot (Year)
3x0026
Time since last boot (Hours)
0/8760
After 8760h Year is updated
3x0027
Time since last boot (Minutes) 0/60
After 60min Hour is updated
3x0028
Temp sensor regulator
Cels. Scaling 1:10 (external tempsensor
connected to 19-20)
3x0029
Temp sensor RU1
Cels. Scaling 1:10
3x0030
Temp sensor RU2
Cels. Scaling 1:10
3x0031
Temp set point RU
Setpoint in regulator form parameter or
Room Unit
3x0032
Flow set point RU
Econ-Normal-Boost
3x0033
Battery level RU
Volts. Scaling 1:10
3x0034
SA2 flow pressure MB sensor
(Pa)
3x0035
SA flow pressure MB sensor
(Pa)
3x0036
EA flow pressure MB sensor
(Pa)
3x0037
Input Analog 1
0/10000
(mV)
3x0038
Input Analog 2
0/10000
(mV)
3x0039
Input Analog 3
0/10000
(mV)
3x0040
Input Analog 4
0/10000
(mV)
3x0041
Output PWM 1
0/100
(%)
3x0042
Output PWM 2
0/100
(%)
3x0043
Output PWM 3
0/100
(%)
3x0044
Output PWM 4
0/100
(%)
3x0045
Output Analog 1
0/10000
(mV)
3x0046
Output Analog 2
0/10000
(mV)
3x0047
Output Analog 3
0/10000
(mV)
3x0048
Output Analog 4
0/10000
(mV)
3x0049
PID Water Out
-100/100
(%)
3x0050
PID ChangeOver Out
-100/100
(%)
71
20210201 Swegon reserves the right to make design changes.
CONDUCTOR
W4
Содержание 20210201
Страница 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Страница 2: ......
Страница 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Страница 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Страница 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Страница 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Страница 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...