Technical Data
CONDUCTOR RE Controller
Technical data applicable to the CONDUCTOR RE controller (W4) is specified below.
Item
Data
Designation
CONDUCTOR RE (W4)
Storage temperature
-40
°
C to +80
°
C
Operating temperature
-20
°
C to +50
°
C
Degree of protection
IP 32
Dimensions
121 x 193 x 44 mm
Supply voltage
24V AC ± 10%
Power consumption
1 VA
Control function
PI
P-band, cooling/heating increments 1 K
Periodic valve operation
1 time/48h period (fully open for 3 minutes)
Installation
Mounting holes in enclosure or onto DIN rail
Connections
Wiring terminal for 2.5 mm² multicore cable
Data communication
ModBus RTU
Wireless communication
433 MHz band radio modem with room unit
(thermostat)
Frost protection
10
°
C
Switch in temperatures
Occupancy, cooling
23 °C
Occupancy, heating
21 °C
No occupancy, cooling
24 °C
No occupancy, heating
20 °C
Inputs
Condensation sensor
Resistance
Temperature sensor
Resistance
Presence detector
No occupancy/NO/NC (optional),
default = NC for occupancy
Window contact
No occupancy/NO/NC (optional),
default = NC for closed window
Carbon dioxide sensor
2 - 10 V, or 24 V
Pressure sensor/ModBus RTU sensor 2 - 10 V / RJ12 cable
Modular contact
RJ12 6-pole for connecting up to the room
unit (thermostat)
RJ12 6-pole for connecting up to ModBus RTU
Outputs
Actuator, heating W4.2
24 V AC, (on/off) max load 72 VA = 12
actuators
Actuator, heating W4.1
24 V AC, PWM (on/off or 0 - 10 V) max load:
72 VA = 12 actuators
Actuator, cooling
24 V AC, PWM (on/off or 0 - 10 V) max load:
72 VA = 12 actuators
Supply air damper
0 - 10 V DC (low/normal/high) max load 25
VA = 5 actuators.
Extract air damper
0 - 10 V DC (low/normal/high) max load 25
VA = 5 actuators.
CONDUCTOR
W4
22
Swegon reserves the right to make design changes.. 20210201
Содержание 20210201
Страница 1: ...CONDUCTOR W4 Technical Manual sw 1 48 20210201...
Страница 2: ......
Страница 4: ...CONDUCTOR W4 4 Swegon reserves the right to make design changes 20210201...
Страница 6: ...CONDUCTOR W4 6 Swegon reserves the right to make design changes 20210201...
Страница 24: ...CONDUCTOR W4 24 Swegon reserves the right to make design changes 20210201...
Страница 36: ...CONDUCTOR W4 36 Swegon reserves the right to make design changes 20210201...
Страница 54: ...CONDUCTOR W4 54 Swegon reserves the right to make design changes 20210201...