A-96.250.491 / 190121
AMI Deltacon DG
Maintenance
40
9
Open the flow regulating valve and adjust the sample flow.
10
After a few minutes close the manual deaeration valve.
11
Pre-rinse the new cation exchanger resin until the display shows
stable measuring values.
Operation time 1 liter Swan resin
This graphic shows the average exhaust time (flow 6 l/h) and must
be verified by the user.
Cation Conductivity.
Operational days for 1 l of cation exchange resin with an exchange
capacity of 1.8 eq/l.
Flow rate 6 l/h alkalization with ammonia. (safety margin of 15% sub
-
tracted).
0
8.8
9.0
9.2
9.4
9.6
9.8
10.0
10.2
pH
Days
100
200
300
400
500
600
700