Valve Control Module
User’s Manual 5
Specifications
Power
Voltage
24 V (dc), nominal
Current
< 310 mA (dc) at 24 V (dc)
Wattage
< 7.5 W at 24 V (dc)
Temperature
Operating (Ambient)
Minimum
23°F
(–5°C)
Maximum
122°F
(50°C)
Media
Minimum
23°F
(–5°C)
Maximum
122°F
(50°C)
Storage
Minimum
–
4°F
(–20°C)
Maximum
140°F
(60°C)
Weight
3.5 lb
(1.6 kg)
Ingress Protection
IP64
Inlet Air
Pressure
40 to 116 psig
(1.6 to 7.9 bar)
Air Quality
Filtered compressed
air, lubricated or
unlubricated, grade of
filtration 40 μm
Entity Parameters
See control drawing VCM-DN-0011-
SCHEDULE on page 6.
Supported
Communication
Baud Rates
Auto-baud function, allowing the device
to detect the speed of network traffic. It is
compatible with 125, 250, and 500 kbaud
rates.
Note: Before installing the VCM in a hazardous location, review the control drawing on page 6.
This will help ensure all electrical connections to and from the VCM comply with safety
requirements. For an electronic copy of this document, see Swagelok.com