Valve Control Module
User’s Manual 13
General Tab
Device Address (MAC ID)
The VCM will have a factory set address of 63 when initially powered on. Addresses between 0 and 63 are
valid DeviceNet addresses. Do not duplicate addresses. Duplicate addresses will cause the devices at that
address to be unable to communicate with the network. As noted, new devices will be set to address 63, so it is
recommended to leave that address open to accommodate new hardware.
Assign higher priority devices a low network address as the lowest network address will be given priority during
network arbitration.
Parameter Tab
These fields can be set for each of the attached valves. Select the valve to edit and then the desired field(s).
Fig 14 Parameter Tab
Fig 13 General Tab