
ALARM – IN-CONVEYOR MOTOR - FUSE TRIPPED
Follow the instructions on the screen:
Reset the fuse inside the electrical cabinet.
Inspection of the in-conveyor is needed. Problem can be caused by food
waste material getting stuck in the in-conveyor. Clean the infeed
hopper and the in-conveyor. If necessary run the in-conveyor in reverse
and thereby loosen any material that is stuck inside the pipe leading to
the cylinder.
Problem can also be caused by a faulty inverter.
Note that this ALARM needs to be acknowledged in the ALARM list in order to turn off the Alarm
Indicator which is visible in the left hand upper corner on all screens.
Use the ALARM button to go to alarm log menu.
From this alarm screen, it is possible
to navigate to
the ‘manual run infeed’ screen
pressing the
symbol with the infeed and two
arrows on the
alarm screens.
Use the back and forward arrow
trying to loosen
the blockage in the inconveyor.
Normally if there is a blockage of the infeed, the alarm that goes off is the ‘ALARM infeed - In-conveyor has
automatically reversed 2 times but is still unable to run’ see 10.10. If there is an alarm that the fuse for the
infeed motor has tripped the settings of the function of the infeed reversing two times may need adjusting,
see above.
If the infeed hopper, propellers and in-conveyor have been cleared and the alarm comes back
contact service personnel.
Содержание BIGHANNA T120
Страница 8: ......
Страница 28: ......
Страница 32: ......
Страница 80: ...5 3 1 START UP SCHEDULE MODEL T60 RESTAURANT WASTE...
Страница 81: ......
Страница 82: ...5 3 2 START UP SCHEDULE MODEL T120 RESTAURANT WASTE...
Страница 83: ......
Страница 84: ...5 3 3 START UP SCHEDULE MODEL T240 RESTAURANT WASTE...
Страница 85: ......
Страница 86: ......
Страница 94: ......
Страница 114: ......