No.
Sign
Range
Default
Description
Set
208
AF
0.00~21.00
20.00
Max. AO Value of Weight Signal
[mA or V]
It
’
s the AO current or v
oltage
output value of
weight signal when
‘
Weight value
≥
[209]’
.
209
AC
1~99999
10000
Max. Weight Value for AO Output
210
At
0~1
0
AO Type
0: 20EA
[Max. Output 20mA]
1: 10V
[Max. Output 10V]
211
dI
0~4
0
DI1 Signal
0:
≡
ZEro
[Zero
Fine
Adjustment
without
Power-down Protection and without Clearing Tare
Weight]
1: -ZEro
[Zero Calibration with Power-down
Protection and Clearing Tare Weight]
2:
≡tArE
[Manual Tare without Power-down
Protection]
3: -rStr
[Clear Tare Weight with Power-down
Protection]
4: CLS
[Clear the display value of Peak Value]
212
AP
1~4
1/2/3/4
[*]
Application Mode
1. HL
[Weight Limit DO Alarm Mode]
2. HH
[Weight Increment DO Output Mode]
3. LL
[Weight Decrement DO Output Mode]
4. SEC
[Weight Section DO Output Mode]
Operating Authorization: Administrator.
[*]:
‘
RAM Reset
’