NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Figure 49

Thermocouple

Thermopile

Pilot

Nozzels

SIT MILLIVOLT PILOT ASSEMBLY

Igniter Rod

Hood

Proper Pilot Flame Appearance

3/8" Min.

(9 mm)

TEST ALL CONNECTIONS FOR GAS LEAKS 

(FACTORY AND FIELD):

     

WARNING

Never use an open flame to 

check for leaks.

Turn on gas supply and test for gas leaks using a 

gas leak test solution (also referred to as bubble 

leak solution).  

Note: 

Using a soapy water solution 

(50% dish soap, 50% water) is an effective leak 

test solution but it is not recommended, because 

the soap residue that is left on the pipes/fittings 

can result in corrosion over time.

A.

 Light  the  appliance  (refer  to  the  lighting 

instructions label in control compartment or 

homeowner's manual).

B.

 Brush all joints and connections with the gas 

leak test solution to check for leaks. If bubbles 

are formed, or gas odor is detected, turn the 

gas  control  knob  (off/pilot/on)  to  the  “OFF” 

position.  Either tighten or refasten the leaking 

connection, then retest as described above.

C.

 When the gas lines are tested and leak free be 

sure to rinse off the leak testing solution, 

D.

 Turn on burner then observe the individual 

tongues of flame on the burner.  Make sure 

all ports are open and producing flame evenly 

across the burner.  If any ports are blocked, or 

partially blocked, clean out the ports.

CONTROL  COMPARTMENT  ACCESS/

LOUVER PANEL INSTRUCTIONS

(

Ref. Figure 47

)

NOTE: 

 The top louvered panel and the bottom 

louvered control panel door remove and install 

the same way as follows:

The gas controls can be found behind the control 

compartment access door. 

Removing Control Compartment Door:

Open the door by  gently lifting it upward until the 

hook catches on boths sides clear the locating 

slots. Then pull door out to remove.

Figure 48

Sit and Honeywell Millivolt Gas Valve 

Showing Piezo Igniter Location (Each Unit is 

Equipped with Only One of these Gas Valves) 

Piezo

Igniter

SIT Gas Valve

Honeywell

Gas Valve

Step 7. CHECKING APPLIANCE OPERA-

TION

With the gas line installed, run initial system 

checkout  before  closing  up  the  front  of  the 

appliance. Follow the pilot lighting instructions 

provided in the Homeowner's Care and Opera-

tion Instructions. For piezo igniter location see

 

Figure 48  

(millivolt appliances only).

Note: The (pull-out) Lighting instructions label 

can  be found  in the control compartment 

(see Figure 47).

When first lighting the appliance, it will take 

a  few  minutes  for  the  line  to  purge  itself  of 

air.  Once  purging  is  complete,  the  pilot  and 

burner  will  light  and  operate  as  indicated  in 

the instruction manual. Subsequent lightings 

of the appliance will not require such purging. 

Inspect the pilot flame.

SIT  and  Honeywell  Millivolt  Appliance 

Checkout

The  pilot  flame  should  be  steady,  not  lifting 

or floating. Flame should be blue in color with 

traces of orange at the outer edge.

Figure 47

OPENING CONTROL 

COMPARTMENT DOOR

Control Valve

Lower Control 

Compartment Door

Lift the Lower Control 

Compartment Door 

up and pull out to 

remove.

Up

Out

Hook Catch

The top 3/8" (10 mm) at the pilot generator 

(thermopile) and the top 1/8" min (tip) of the 

quick drop out thermocouple should be engulfed 

in the pilot flame. The flame should project 1" (25 

mm) beyond the hood at all three ports (

Figure 

49 - SIT, Figure 50 - Honeywell

).

To light the burner; rotate the gas valve control 

knob  counterclockwise  to  the  “ON”  position 

then turn “ON” the OFF/ON switch (installed 

at 

Step 4

)

.

Observe the individual tongues of flame on 

the burner.  Make sure all ports are open and 

producing flame evenly across the burner.  If 

any ports are blocked, or partially blocked, 

clean out the ports.

On millivolt systems, the piezo igniter, HI/LO 

flame  adjustment  knob,  and  pilot  and  main 

gas  OFF/ON  control  knob  are  located  below 

the glass panel enclosure. The gas valve for 

electronic systems is also located below the 

glass enclosure panel. See 

Figure 47.

Reinstalling Control Compartment Door:

To reinstall, insert the hook catches on each 

side of the door into the corresponding slots 

in  the  control  compartment  opening,  then 

gently  push  forward  and  slide  down  until  it 

locks in place.

Содержание SSDV-3328

Страница 1: ... Follow your gas suppliers instructions If your gas supplier cannot be reached call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING IFTHEINFORMATIONINTHISMANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLO SIONMAYRESULTCAUSINGPROPERTYDAMAGE PERSONAL INJURY OR LOSS OF LIFE POUR VOTRE SÉCURITÉ Ne pas entreposer ni utiliser...

Страница 2: ...owner s manual installation instructions and war ranty envelope is located in the control compartment 3 One vent restrictor to be applied as shown on Page 13 restrictor is taped to the envelope 4 One hood located behind the top panel 5 Onebagofdecorativevolcanicstonelocated in the control compartment 6 One bag of glowing embers located in the control compartment This appliance is only for use with...

Страница 3: ...olt models Fuel Low High Natural Gas Lo 2 2 WC 55 kPa Hi 3 5 WC 87 kPa Propane Lo 6 3 WC 1 57 kPa Hi 10 0 WC 2 49 kPa Table 4 Test gauge connections are provided on the front of the millivolt gas control valve identi fied IN for the inlet and OUT for the manifold side A 1 8 NPT Test gauge connection is provided at the inlet and outlet side of the electronic gas control valve Burner Orifice Sizes E...

Страница 4: ...ector must comply with NFPA 720 be ANSI UL 2034 listed and be IAS certified A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade and be directly in line with the horizontal termination The sign must read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BE LOW KEEP CLEAR OF ALL OBSTR...

Страница 5: ... temperatures see Figure 4 The location should also be free of electrical plumbing or other heating air conditioning ducting These direct vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelveslikethesearecommonlyusedforlocat ing television sets and decorative plants Be aware that this is a heat producing appliance Obj...

Страница 6: ...erican National StandardforManufacturedHomes NCSBCS ANSI A225 1 latest edition CAUTIONS Ensure that the cross members are not cut or weakened during installation Thestructuralinteg rity of the manufactured home floor wall andceiling roofmust be maintained Thisappliancemustbegrounded to the chassis of the manufac tured home in accordance with local codes or in the absence of local codes with the Na...

Страница 7: ...ions exceeding 2 1 2 64 mm see Figure 6 All horizontal terminations may be located as close as 6 152mm to any combustible exterior sidewall This distance may be decreased to 2 51mm if the SV4 5HT 2 or SF4 5HT 2 termination is used and the exterior sidewall is non combustible only For additional vent location restrictions refer to Figure 7 on Page 8 Termination Heights For Vents Above Flat Or Slope...

Страница 8: ... h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e l t u o t n e v r o t a l u g e r e c i v r e s o t e c n a r a e l C I m c 1 9 t e e f 3 m c 1 9 t e e f 3 r o g n i d l i u b o t t e l n i y l p p u s r i a l a c i n a h c e m n o n o t...

Страница 9: ...um side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figure 10 At 8 1 4 side wall clearance a combustible wall can project 12 Hood Mantel Depth 4 102 2 51 4 102 6 152 8 203 10 254 12 305 6 152 10 254 14 356 12 305 8 203 5 127 8 1 4 209 14 356 12 305 19 483 45 o MINIMUM CLEARANCES Inches millimeters Back 1 2 13 0 0 Spacers Sides 1 2 13...

Страница 10: ...provided and bringinelectricalservicelineforforcedair circulating blower optional equipment b ElectronicAppliances Fieldwireandinstall operating control switch Step 5 Page 25 Install blower kit optional equipment Step 6 Page 26 Make connection to gas sup ply Step 7 Page 27 Checkout appliance operation Step 8 Page 28 Install the logs decorative volcanic stone and glowing embers Step 9 Page 30 Insta...

Страница 11: ...dels only ELECTRICAL INLET 2 3 4 x 2 70 x 51 COVER PLATE with KNOCKOUT Right Side View SSDVR models have only a rear vent SSDVT models have only a top vent 6 13 16 173 2 3 4 70 33 1 8 841 30 1 8 765 27 1 2 699 17 432 19 5 8 498 10 3 4 273 33 1 8 841 Inches millimeters 1 25 1 25 Notes Due to Lennox ongoing commitment to quality all specifications ratings and dimensions are subject to change without...

Страница 12: ...ver use galvanized or plastic pipe Refer to Table 9 for proper sizing of the gas supply line if black iron pipe is being used Gas lines must be routed constructed and made of materials that are in strict accordance with local codes and regulations We recommend that a quali fied individual such as a plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance Inst...

Страница 13: ...he vent pipe is tested to be run inside an enclosing wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe WARNING Failure to reinstall and securely tighten cover plate screws could result in leakage of flue products into the living space Vent cover plate and vent seal plate must remain securely installed on unused vent col...

Страница 14: ... 5 1 3 5 2 6 2 0 3 0 0 0 3 5 4 3 5 7 8 2 0 0 0 1 0 1 5 7 3 5 2 1 3 1 1 1 0 0 3 5 3 4 5 2 6 3 0 2 1 0 0 3 5 4 5 7 3 0 0 2 0 0 2 5 6 4 5 7 8 3 0 0 0 0 1 1 5 9 4 5 2 1 4 1 0 2 0 0 3 1 5 5 2 4 1 0 0 0 1 2 5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0...

Страница 15: ...nselectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent section SV4 5LA may be used to provide the installer withanoptionininstallingintightand confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable locati...

Страница 16: ... the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnectedventsections See Figure 22 K Install the vertical termination The final step involves installation of the SV4 5CGV 1 Vertical Termination Extend the vent sections t...

Страница 17: ...ingSecureFlex useFirestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF Table A H Maximum V Minimum feet meter feet meter 2 0 610 1 0 305 4 1 219 2 0 610 6 1 829 3 0 914 8 2 438 4 1 219 V H 40 feet 12 2 meters Max H 8 feet 2 4 mete...

Страница 18: ...Flex useFirestop SpacerSF4 5HF Figure 29 Rear Vent three elbows Figure 30 Top Vent three elbows VERTICAL VENT FIGURES TABLES CONTINUED Horizontal Outside Wall Termination System Figure 31 and Figures 34 to 40 on Pages 21 to 23 and their associated Horizontal Vent Table illustrate the various horizontal venting configurations that are possible for use with theseappliances SecureVentpipeapplications...

Страница 19: ...nels of the previous section Push the vent component against the previous section until it fully engages then twist the componentclockwiserunningthedimplesdown and along the incline channels until they seat at the end of the channels This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 20 on Page 15 F Install firestop spacer at ceiling WhenusingSecureVent ...

Страница 20: ... 5HT 2 Termination J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as described in Step B Assemble the vent system topointwheretheterminusofthelastsectionis located relative to the exterior surface to which the termination is to be attached see Figures 32 33 and Table 12 on Page 21 If the terminus of the last sec...

Страница 21: ...ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 35 See Table 12 as an aid in venting component selection for a particular range of exterior wall thicknesses WARNING Under no circumstances may separate sections of concentric flexible vent pipe be joined together HORIZONTAL VENT FIGURES TABLES Figure 36 Top Vent ONE 90 DEGREE ELBOW ...

Страница 22: ...See Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES CONTINUED Table H H H1 Maximum HMaximum V Minimum feet meter feet meter feet meter 5 1 524 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 m...

Страница 23: ...t of horizontal run up to a maximum total H H1 H2 horizontal run of 20 feet Figure 40 Top Vent THREE 90 DEGREE ELBOWS Figure 39 Rear Vent THREE 90 DEGREE ELBOWS See Table 12 on Page 21 as an aid in venting component selection for aparticularrangeofexte rior wall thicknesses See Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONT...

Страница 24: ...ovideadditional security to the connection B Install the Outer Flex Pipe 1 Install the large gear clamp loosely around the outer flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the outer adapter collar to the grooves of the collar which extend approximately 1 inch from the end and to the flat surface approximately 1 3 4 ...

Страница 25: ...trical power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the control within the millivolt control circuit using the 15 feet of 2 conductor wire supplied with the unit Caution do not connect the optional wall switch to a 120V power supply 4 Alternatively theappliancemaybe...

Страница 26: ...cal codes the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code Step 6 Connecting Gas Line Make gas line connections All codes require a shut offvalvemountedinthesupplyline Figure 46 illustrates two methods for connecting the gas supply The flex line method is acceptable in the U S however Canadian requirements vary depending on locality ...

Страница 27: ... Appliance Opera tion With the gas line installed run initial system checkout before closing up the front of the appliance Follow the pilot lighting instructions provided in the Homeowner s Care and Opera tion Instructions For piezo igniter location see Figure 48 millivolt appliances only Note The pull out Lightinginstructionslabel can be found in the control compartment see Figure 47 When first l...

Страница 28: ... edge of the ember bracket 4 Insert the alignment hole of the right twig over the front log s right pin Rotate the right twig until it almost touches the front panel glass Note Propertwigplacementiscriticalinthe gapsbetweentheflamepeaksandshouldbe positioned so that at no time they impinge the flames Glowing Ember Volcanic Stone Placement Remove the replacement rockwool Glowing Embers from the pac...

Страница 29: ...Volcanic Stone Table 13 Bag of Glowing Embers rockwool Separate into Quarter Size separate Pieces WARNING DONOTattempttoinstallthelogs until the appliance installation hasbeencompleted thegasline connected and tested for leaks and the initial burner operation has been checked out Figure 53 Glowing Embers WARNING This appliance is not designed to burn wood Any attempt to do so could cause irreparab...

Страница 30: ... The glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to touch the front enclosure glass with your hands while the fireplace is in use Air Shutter Adjustment Guidelines If there is smoke or soot present first check the log set positioning to ensure that the...

Страница 31: ...See Page 6 for Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avoid injury while adjusting flame appearance Burner Air Shutter Adjustment Procedure 1 Locate adjustment rod and adjust air shutter to the standard setting as shown in Figure 56 adjustment rod is located in the lowe...

Страница 32: ...7 1 2 effective length 4 77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 Installation Accessories The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 2 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 2 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Collar 6 per box 8 H2246 SV4 5HF Firestop Spacer Hor...

Страница 33: ...SFMP 12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV4 5HRK36 Horizontal Riser Kit 36 25 H1988 CTSA 33 Chase Top Shroud Kit Arch Top 3 X 3 26 H1985 CTSO 33 Chase Top Shroud Kit Open Top 3 X 3 26 H1987 CTSO 44 Chas...

Страница 34: ...structionssuppliedwiththekit The qualified service agency performing thisinstallationassumesresponsibil ity for this conversion AVERTISSEMENT Cet équipement de conversion sera installé par une agence qualifiée de service conformément aux instruc tionsdufabricantettoutesexigences et codes applicables de l autorisés avoir la juridiction Si l information danscetteinstructionn estpassuivie exactement ...

Страница 35: ...ning it clockwise Replace the plastic protecting cap Pilot for Honeywell Millivolt Gas Valve Loosening of Hex Fitting For Orifice Strip Tab Positioning Figure 62 7 16 in Open End Wrench Hood Hood Alignment Orifice Strip Tab Take care not to contact the orifice strip tab with the hex fitting wrench distortion of the tab may render the pilot inoperative LP propane Gas Posi tion 1 16 inch hole LP and...

Страница 36: ...the kit See Table 14 for orifice sizes required for use with natural gas or propane gas Figure 65 illustrated the orifice Step 6 Electronic Appliances Honeywell Systems See Figure 63 and the instructions provided with the kit Remove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and r...

Отзывы: