D. Install Firestop / Spacers at ceilings and walls 

When Secure Flex penetrates a wall or ceiling, 

a firestop / spacer is required: use the SF4.5 VF 

firestop / spacer for ceilings and the SF4.5 HF 

firestop / spacer for walls. See the appropriate 

sections and Figures shown throughout the vent-

ing section for their installation requirements. 

VERTICAL OR HORIZONTAL VENTING USING 

SECuRE FLEX

 KITS AND COMPONENTS

Secure  Flex

  venting  kits  and  components 

may  be  used  in  any  venting  application  in 

place of rigid 

Secure Vent

 (SV4.5) direct vent 

components.  All restrictions, clearances and 

allowances that pertain to the rigid piping apply 

to the flexible venting.  

Secure Flex

 kits may 

not be modified; also, under no circumstances 

may separate sections of flex pipe be joined 

together

Using  adapter  (SV4.5RF),

  Secure  Flex

  kits 

may be added to the end of a vent run made 

up of rigid 

Secure Vent

 (SV4.5) vent sections 

provided that doing so does not violate any of 

the venting length, height, routing, horizontal 

to  vertical  ratio  requirements  or  clearance 

considerations detailed in this manual.

Secure  Flex

  kits  come  with  an  adapter  that 

can be fitted to the inclined channel end of the 

last 

Secure Vent

 (SV4.5) vent section in a rigid 

system in the exact same fashion as any other 

Secure Vent 

section.

Align  the  dimpled  end  of  the  adapter  over 

the  previously  installed  section  or  appliance 

collar, adjusting the radial alignment until the 

four locking dimples of the adapter are aligned 

with the inlets of the four incline channels of 

the  last  vent  section  or  collar.    Push  on  the 

adapter  until  it  fully  engages,  then  twist  the 

adapter clockwise running the dimples down 

and along the incline channels until they seat 

at the end of the channels.

Attach the flexible vent to the adapter as fol-

lows 

(see also 

Figure 41

)

:

A. Install the Inner Flex Pipe - 

1.

 Install the small  gear clamp loosely around 

the inner flexible vent pipe, push it back out 

of the way.

2.

 Apply a bead of 

Mill-Pac Black (700° F) high 

temperature sealant - Catalog No. 10K81

 

to the inner adapter collar, approximately 

1/2

 

inch from the end.

3.

 Pull and extend the inner flexible vent pipe. 

4.

  Slide the inner flex pipe over the adapter col-

lar. Ensure the flexible vent pipe completely 

engages the adapter collar to a distance of 1 

3/4

 

inches from the end, and that it is free  

from damage or tears. 

5

. Slide the gear clamp down and tighten it 

fully to secure the flexible vent to the adapter 

inner collar approximately 3/4 inch from the 

end of the flex.

6

.  Install 

three screws 120 degrees apart

 through 

the flexible vent pipe and into the adapter collar 

just below the gear clamp to provide additional 

security to the connection.

B. Install the Outer Flex Pipe - 

1.

 Install the large gear clamp loosely around 

the outer flexible vent pipe, push it back out 

of the way.

 

2.

 Apply a bead of 

Mill-Pac Black (700° F) high 

temperature sealant - Catalog No. 10K81)

 

to the outer adapter collar; to the grooves 

of the collar which extend approximately 1 

inch from the end and to the flat surface, 

approximately 1 3/4 inches from the end. 

3.

 Pull and extend outer flexible vent pipe. 

4.

 Slide the outer flex pipe over the adapter col-

lar. Ensure the flexible vent pipe completely 

engages the adapter collar to a distance of 

1-3/4

 

inches from the end, and that it is free 

from damage or tears. 

5

. Slide  the  gear  clamp  down  and  tighten  it 

fully to secure the flexible vent to the adapter 

outer collar approximately 3/4 inch from the 

end of the flex.

6.

 Install 

three  screws  120  degrees  apart

 

through the flexible vent pipe and into the 

adapter collar just below the gear clamp to 

provide additional security to the connec-

tion.

C. Route Flex Vent -

Ensure that the flex vent is properly routed to 

provide the required clearance. 

Do not 

allow the 

flexible vent to bend in a radius tighter than 5" 

(127 mm). Refer to 

Figure 42

. Space out the 

internal flex vent spacers evenly - approximately 

every 6 inches - and avoid kinking of inner pipe. 

Support horizontal sections of flex with metal 

straps at 2 foot (0.61 m) intervals. 

E. Attach Flex Vent to Termination -

  

Secure  Flex

  components  can  be  purchased 

separately and attached to bulk lengths of 

Se-

cure Flex

 flexible tubing cut to size at the job 

site.  Secure the flexible vent to the 

Secure Flex

 

terminations in the same manner (see

 Figure 

41) 

as it was attached to the adapter.

Note: Secure Flex vent must be attached to Se-

cure Flex terminations only. DO NOT substitute 

Secure Vent terminations or the Secure Vent 

adapter for Secure Flex components. The collars 

of Secure Flex terminations and adapters have a 

different diameter than that used with the Secure 

Vent pipe.  Additionally, Secure Flex components 

have an extended length center tube for use in 

attaching the flexible vent.

Figure 42

5” (127 mm)

Radius

Minimum

Flexible Vent 

Section

APPLY  ONLY  MIL-PAC  BLACK 

HIGH  TEMPERATURE  SEALANT 

(Cat. No. 10K81) to the outside 

surface  of  both  collars  of  the 

adapter (be especially careful to 

fill the grooves of the outer collar 

to be covered by the flexible pipe) 

and slide flexible pipe over inner 

and outer adapter collars.

1-3/4 inch (44 mm) Flexible 

Pipe and Adapter Outer Collar 

Overlap

Adapter (SV4.5RF)

Attach Adapter to Appliance 

Collar, or Secure Vent Sections

Flex Vent

Gear Clamps

Securing Screw 

- 3 Places, 120° apart 

(equally spaced) Just 

Below Gear Clamp

1 3/4  in. (44 mm) Flexible 

Pipe and Adapter Inner Collar 

Overlap

Securing  Screw  -  3  Places 

Equidistant (equally spaced) 

Just Below Gear Clamp)

Figure 41

Note:  Outer Pipe Is Pulled Away To 

Show The Detail of The Inner Pipe

Содержание SSDV-3328

Страница 1: ... Follow your gas suppliers instructions If your gas supplier cannot be reached call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING IFTHEINFORMATIONINTHISMANUAL IS NOT FOLLOWED EXACTLY A FIRE OR EXPLO SIONMAYRESULTCAUSINGPROPERTYDAMAGE PERSONAL INJURY OR LOSS OF LIFE POUR VOTRE SÉCURITÉ Ne pas entreposer ni utiliser...

Страница 2: ...owner s manual installation instructions and war ranty envelope is located in the control compartment 3 One vent restrictor to be applied as shown on Page 13 restrictor is taped to the envelope 4 One hood located behind the top panel 5 Onebagofdecorativevolcanicstonelocated in the control compartment 6 One bag of glowing embers located in the control compartment This appliance is only for use with...

Страница 3: ...olt models Fuel Low High Natural Gas Lo 2 2 WC 55 kPa Hi 3 5 WC 87 kPa Propane Lo 6 3 WC 1 57 kPa Hi 10 0 WC 2 49 kPa Table 4 Test gauge connections are provided on the front of the millivolt gas control valve identi fied IN for the inlet and OUT for the manifold side A 1 8 NPT Test gauge connection is provided at the inlet and outlet side of the electronic gas control valve Burner Orifice Sizes E...

Страница 4: ...ector must comply with NFPA 720 be ANSI UL 2034 listed and be IAS certified A metal or plastic identification plate must be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade and be directly in line with the horizontal termination The sign must read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BE LOW KEEP CLEAR OF ALL OBSTR...

Страница 5: ... temperatures see Figure 4 The location should also be free of electrical plumbing or other heating air conditioning ducting These direct vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelveslikethesearecommonlyusedforlocat ing television sets and decorative plants Be aware that this is a heat producing appliance Obj...

Страница 6: ...erican National StandardforManufacturedHomes NCSBCS ANSI A225 1 latest edition CAUTIONS Ensure that the cross members are not cut or weakened during installation Thestructuralinteg rity of the manufactured home floor wall andceiling roofmust be maintained Thisappliancemustbegrounded to the chassis of the manufac tured home in accordance with local codes or in the absence of local codes with the Na...

Страница 7: ...ions exceeding 2 1 2 64 mm see Figure 6 All horizontal terminations may be located as close as 6 152mm to any combustible exterior sidewall This distance may be decreased to 2 51mm if the SV4 5HT 2 or SF4 5HT 2 termination is used and the exterior sidewall is non combustible only For additional vent location restrictions refer to Figure 7 on Page 8 Termination Heights For Vents Above Flat Or Slope...

Страница 8: ... h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e l t u o t n e v r o t a l u g e r e c i v r e s o t e c n a r a e l C I m c 1 9 t e e f 3 m c 1 9 t e e f 3 r o g n i d l i u b o t t e l n i y l p p u s r i a l a c i n a h c e m n o n o t...

Страница 9: ...um side wall clearance a combustible wall can project to any length Protected wall shown in white Inches millimeters Figure 10 At 8 1 4 side wall clearance a combustible wall can project 12 Hood Mantel Depth 4 102 2 51 4 102 6 152 8 203 10 254 12 305 6 152 10 254 14 356 12 305 8 203 5 127 8 1 4 209 14 356 12 305 19 483 45 o MINIMUM CLEARANCES Inches millimeters Back 1 2 13 0 0 Spacers Sides 1 2 13...

Страница 10: ...provided and bringinelectricalservicelineforforcedair circulating blower optional equipment b ElectronicAppliances Fieldwireandinstall operating control switch Step 5 Page 25 Install blower kit optional equipment Step 6 Page 26 Make connection to gas sup ply Step 7 Page 27 Checkout appliance operation Step 8 Page 28 Install the logs decorative volcanic stone and glowing embers Step 9 Page 30 Insta...

Страница 11: ...dels only ELECTRICAL INLET 2 3 4 x 2 70 x 51 COVER PLATE with KNOCKOUT Right Side View SSDVR models have only a rear vent SSDVT models have only a top vent 6 13 16 173 2 3 4 70 33 1 8 841 30 1 8 765 27 1 2 699 17 432 19 5 8 498 10 3 4 273 33 1 8 841 Inches millimeters 1 25 1 25 Notes Due to Lennox ongoing commitment to quality all specifications ratings and dimensions are subject to change without...

Страница 12: ...ver use galvanized or plastic pipe Refer to Table 9 for proper sizing of the gas supply line if black iron pipe is being used Gas lines must be routed constructed and made of materials that are in strict accordance with local codes and regulations We recommend that a quali fied individual such as a plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance Inst...

Страница 13: ...he vent pipe is tested to be run inside an enclosing wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe WARNING Failure to reinstall and securely tighten cover plate screws could result in leakage of flue products into the living space Vent cover plate and vent seal plate must remain securely installed on unused vent col...

Страница 14: ... 5 1 3 5 2 6 2 0 3 0 0 0 3 5 4 3 5 7 8 2 0 0 0 1 0 1 5 7 3 5 2 1 3 1 1 1 0 0 3 5 3 4 5 2 6 3 0 2 1 0 0 3 5 4 5 7 3 0 0 2 0 0 2 5 6 4 5 7 8 3 0 0 0 0 1 1 5 9 4 5 2 1 4 1 0 2 0 0 3 1 5 5 2 4 1 0 0 0 1 2 5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0...

Страница 15: ...nselectinglengthcombinations Elbowsare available in 90 and 45 configurations Refer to Figure 22 on Page 16 for the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent section SV4 5LA may be used to provide the installer withanoptionininstallingintightand confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable locati...

Страница 16: ... the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possiblity of unlocking anyofthepreviouslyconnectedventsections See Figure 22 K Install the vertical termination The final step involves installation of the SV4 5CGV 1 Vertical Termination Extend the vent sections t...

Страница 17: ...ingSecureFlex useFirestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF Table A H Maximum V Minimum feet meter feet meter 2 0 610 1 0 305 4 1 219 2 0 610 6 1 829 3 0 914 8 2 438 4 1 219 V H 40 feet 12 2 meters Max H 8 feet 2 4 mete...

Страница 18: ...Flex useFirestop SpacerSF4 5HF Figure 29 Rear Vent three elbows Figure 30 Top Vent three elbows VERTICAL VENT FIGURES TABLES CONTINUED Horizontal Outside Wall Termination System Figure 31 and Figures 34 to 40 on Pages 21 to 23 and their associated Horizontal Vent Table illustrate the various horizontal venting configurations that are possible for use with theseappliances SecureVentpipeapplications...

Страница 19: ...nels of the previous section Push the vent component against the previous section until it fully engages then twist the componentclockwiserunningthedimplesdown and along the incline channels until they seat at the end of the channels This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 20 on Page 15 F Install firestop spacer at ceiling WhenusingSecureVent ...

Страница 20: ... 5HT 2 Termination J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as described in Step B Assemble the vent system topointwheretheterminusofthelastsectionis located relative to the exterior surface to which the termination is to be attached see Figures 32 33 and Table 12 on Page 21 If the terminus of the last sec...

Страница 21: ...ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 35 See Table 12 as an aid in venting component selection for a particular range of exterior wall thicknesses WARNING Under no circumstances may separate sections of concentric flexible vent pipe be joined together HORIZONTAL VENT FIGURES TABLES Figure 36 Top Vent ONE 90 DEGREE ELBOW ...

Страница 22: ...See Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES CONTINUED Table H H H1 Maximum HMaximum V Minimum feet meter feet meter feet meter 5 1 524 2 0 610 1 0 305 10 3 048 4 1 219 2 0 610 15 4 572 6 1 829 3 0 914 20 6 096 8 2 438 4 1 219 V H H1 40feet 12 2m Max H 8 feet 2 438 meters Max H H1 20 feet 6 096 m...

Страница 23: ...t of horizontal run up to a maximum total H H1 H2 horizontal run of 20 feet Figure 40 Top Vent THREE 90 DEGREE ELBOWS Figure 39 Rear Vent THREE 90 DEGREE ELBOWS See Table 12 on Page 21 as an aid in venting component selection for aparticularrangeofexte rior wall thicknesses See Table 12 on Page 21 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONT...

Страница 24: ...ovideadditional security to the connection B Install the Outer Flex Pipe 1 Install the large gear clamp loosely around the outer flexible vent pipe push it back out of the way 2 ApplyabeadofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the outer adapter collar to the grooves of the collar which extend approximately 1 inch from the end and to the flat surface approximately 1 3 4 ...

Страница 25: ...trical power must be connectedtoeitherofthesereceptaclesinorder to operate these blowers Install the blower kits according to the installation instructions provided with the kits 3 Wire the control within the millivolt control circuit using the 15 feet of 2 conductor wire supplied with the unit Caution do not connect the optional wall switch to a 120V power supply 4 Alternatively theappliancemaybe...

Страница 26: ...cal codes the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code Step 6 Connecting Gas Line Make gas line connections All codes require a shut offvalvemountedinthesupplyline Figure 46 illustrates two methods for connecting the gas supply The flex line method is acceptable in the U S however Canadian requirements vary depending on locality ...

Страница 27: ... Appliance Opera tion With the gas line installed run initial system checkout before closing up the front of the appliance Follow the pilot lighting instructions provided in the Homeowner s Care and Opera tion Instructions For piezo igniter location see Figure 48 millivolt appliances only Note The pull out Lightinginstructionslabel can be found in the control compartment see Figure 47 When first l...

Страница 28: ... edge of the ember bracket 4 Insert the alignment hole of the right twig over the front log s right pin Rotate the right twig until it almost touches the front panel glass Note Propertwigplacementiscriticalinthe gapsbetweentheflamepeaksandshouldbe positioned so that at no time they impinge the flames Glowing Ember Volcanic Stone Placement Remove the replacement rockwool Glowing Embers from the pac...

Страница 29: ...Volcanic Stone Table 13 Bag of Glowing Embers rockwool Separate into Quarter Size separate Pieces WARNING DONOTattempttoinstallthelogs until the appliance installation hasbeencompleted thegasline connected and tested for leaks and the initial burner operation has been checked out Figure 53 Glowing Embers WARNING This appliance is not designed to burn wood Any attempt to do so could cause irreparab...

Страница 30: ... The glass door of this appli ance must only be replaced as a complete unit as provided by themanufacturer Donotattempt to replace broken cracked or chipped glass separately WARNING Do not attempt to touch the front enclosure glass with your hands while the fireplace is in use Air Shutter Adjustment Guidelines If there is smoke or soot present first check the log set positioning to ensure that the...

Страница 31: ...See Page 6 for Cold Climate Insulation and Page 9 for Clearances Burner Air Shutter Adjustment Procedure CAUTION Theairshutterdoorandnearbyappliancesurfacesare hot Exercise caution to avoid injury while adjusting flame appearance Burner Air Shutter Adjustment Procedure 1 Locate adjustment rod and adjust air shutter to the standard setting as shown in Figure 56 adjustment rod is located in the lowe...

Страница 32: ...7 1 2 effective length 4 77L76 SV4 5E45 45 Degree Elbow 5 77L77 SV4 5E90 90 Degree Elbow 3 4 5 6 7 10 1 8 9 11 Installation Accessories The following flashings come packaged with a storm collar 6 77L78 SV4 5F Flat Roof Flashing 6 77L79 SV4 5FA 1 2 to 7 12 Adjustable Flashing 6 77L80 SV4 5FB 7 2 to 12 12 Adjustable Flashing 7 77L81 SV4 5SC6 Storm Collar 6 per box 8 H2246 SV4 5HF Firestop Spacer Hor...

Страница 33: ...SFMP 12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 24 99L02 SV4 5HRK14 Horizontal Riser Kit 14 24 99L03 SV4 5HRK36 Horizontal Riser Kit 36 25 H1988 CTSA 33 Chase Top Shroud Kit Arch Top 3 X 3 26 H1985 CTSO 33 Chase Top Shroud Kit Open Top 3 X 3 26 H1987 CTSO 44 Chas...

Страница 34: ...structionssuppliedwiththekit The qualified service agency performing thisinstallationassumesresponsibil ity for this conversion AVERTISSEMENT Cet équipement de conversion sera installé par une agence qualifiée de service conformément aux instruc tionsdufabricantettoutesexigences et codes applicables de l autorisés avoir la juridiction Si l information danscetteinstructionn estpassuivie exactement ...

Страница 35: ...ning it clockwise Replace the plastic protecting cap Pilot for Honeywell Millivolt Gas Valve Loosening of Hex Fitting For Orifice Strip Tab Positioning Figure 62 7 16 in Open End Wrench Hood Hood Alignment Orifice Strip Tab Take care not to contact the orifice strip tab with the hex fitting wrench distortion of the tab may render the pilot inoperative LP propane Gas Posi tion 1 16 inch hole LP and...

Страница 36: ...the kit See Table 14 for orifice sizes required for use with natural gas or propane gas Figure 65 illustrated the orifice Step 6 Electronic Appliances Honeywell Systems See Figure 63 and the instructions provided with the kit Remove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and r...

Отзывы: