CAUTION: FIRE OR EXPLOSION HAZARD
Maintain clearance to combustible constructions as further specified in this manual. Failure
to do so could result in a serious fire hazard. Heaters should not be located in hazardous
atmospheres containing flammable vapors or combustible dusts. Signs should be provided in
storage areas specifying maximum safe stacking height.
CAUTION: MECHANICAL HAZARD
This equipment expands and contracts with each operating cycle. The gas connection,
suspension hardware and the installation itself must safely allow this movement. Failure to
do so could result in serious fire or explosion hazard.
CAUTION: FIRE OR EXPLOSION HAZARD
This heater is equipped with an automatic ignition device. Do not attempt to light the burner
by hand. Failure to comply could result in a serious fire and personal injury hazard.
CAUTION: MECHANICAL HAZARD
Do not use high pressure (above 1/2 psi) to test the gas supply system with the burners
connected. Failure to do so could result in damage to the burner and its control components
requiring replacement.
CAUTION: SERVICE LIFE RISK
Do not install equipment in atmospheres containing halogenated hydrocarbons or other
corrosive chemicals. Failure to do so may lead to premature equipment failure and
invalidation of the warranty. Additionally, it is recommended that the equipment be installed
with a slope downward and away from the burner of ¼" inch in 10' feet to allow start-up
condensate drainage.