background image

UNITED STATES ONLY

CHIMNEY INSTALLATION

INSTRUCTIONS USING 

IHP SNAP PAK (SP)

UNITED STATES APPROVED VENTING SYS-

TEMS:

6” diameter chimney: 

Model IHP Snap-Pak, 

including:

  -  Chimney lengths

  - Elbows 

(where necessary)

  -  Associated components as per these 

    installation instructions

INSTALLATION THROUGH FLAT 

CEILING(S) 

1. Using framing lumber equal to ceiling joist 

size, frame ceiling opening as shown in 

Figure 34

 and 

Table 3

.

5.  The first chimney section through the joist area into attic is to be approximately two (2) feet. 

If the pipe sections in the attic are not enclosed, an insulation shield (SPIS) must be installed. 

Lower the insulation shield (SPIS) over the SP pipe until the SPIS flange is resting on the joist. 

Secure the SPIS in place by nailing the flange to the joist. See 

Figure 36

. If the section within 

the attic area is to be chase enclosed, the SPIS is not required.

  WARNING: Do not place any type of insulation in the required clearance spaces surrounding 

the chimney.

6.  Continue the chimney to the roof. See “Flashing Installation”and “Termination” sections.

B

A

Framing lumber of equal size to the joist should be used.

Figure 35

FEMALE END

MALE END

BUTTON LOCK

ATTACH FOR LOCK

Figure 36

INSULATION SHIELD 

(CAT. NO. SPIS)

NAIL

FIRESTOP 

(CAT. NO. SPFS)

Chimney Flue Diameter

6”

A

12-7/16”

B

12-7/16”

Table 3

If the area above the ceiling is an attic, go 

to step 5.

2. Install SNAP-PAK chimney sections start-

ing at the top of the appliance.  Leave the 

first section loose until the installation is 

complete to allow the chimney to be ro-

tated, easing the installation of any offsets 

if they are used.  Secure subsequent sec-

tions by pushing together until stop-locked 

(see Figure 35). 

3. 

If IHP Elbows are to be used because the 

chimney is to be offset, refer to “Instal-

lation of Elbows” section. 

Directly above 

the Center of the flue in the ceiling support, 

mark the ceiling. A plumb bob is normally 

used to find the center. Cut an opening in 

the ceiling using 

Figure 34

 and

 Table 3

.

4. At each ceiling penetration, a firestop 

(SPFS) is required. Insert the SPFS into the 

joist area prepared in 

Figure 34

NOTE: When the chimney extends between 

floors-which can be occupied-the chimney 

must be enclosed to prevent contact. As 

previously noted, 2” minimum clearance 

to combustibles is to be maintained at all 

times.

Figure 34

21

Содержание WRT3920

Страница 1: ...orrect replacement door The fireplace is equipped with a blower electri cal connection must be made prior to fireplace installation Important To assure proper alignment of glass door Installthisfirepl...

Страница 2: ...use with a gas log set Do not use a fireplace insert or any other product with this fireplace unless it is specified by IHP for use with this ap pliance Failure to follow these instructions will void...

Страница 3: ...nt length to be blown in front ofanopenflamewhenthewindow is opened Keep any combustible furniture materials or decorative pillows at least 48 1219 mm from the front fireplace opening WARNING Never le...

Страница 4: ...sthecatalyticcombustor Openingthe CAT bypass damper control increases the draft allowing the unit to achieve proper operating temperatures during a cold start up It also provides more draft to prevent...

Страница 5: ...d For instance a long chimney will necessitate closing the damper more To obtain the proper combustion closethedampercompletely then open it about 1 4 to 1 2 6 4mm to 13mm Two medium size pieces of wo...

Страница 6: ...It takesabout15 30minuteswiththeCATbypass opened to reach proper light off temperatures for the catalytic combustor Step 5 Set the primary control to the desired burn level The fireplace will automati...

Страница 7: ...oisture content can exceed 80 which must be reduced to less than 20 Wood properly seasoned is then capable of generating the heat the stove was designed to provide Greenwooddoesnotburneasily Attemptin...

Страница 8: ...ombustor Remove dust accumulation after chimney sweep and put the combustor back in place CATALYTIC COMBUSTOR This fireplace is designed with a catalytic com bustor which will reduce pollution emissio...

Страница 9: ...rewsandslidingthehingebracketupordown to create better seal and then retightening Catalyst Bypass linkage replacement see Figure 8B Toolsrequired 2 9 16 wrenches 2square drive bit driver Withcatalystb...

Страница 10: ...ombustorProblem Thermal Cracking ThiscombustordoesNOTexperiencethermalcracking Notap plicable Appliestohoneycombcombustorsonly CombustorProblem CombustorPeeling ThiscombustordoesNOTexperiencecombustor...

Страница 11: ...ashes are cold 24 to 48 hours after the fire is out Do not leave the ashes in the house as they give off carbon monoxide and other toxic gases Figure 10 Figure 9 WARNING DisposalofAshes Ashesshould be...

Страница 12: ...Replacement Parts Page 28 DO NOT OPERATE THE UNIT WITH CRACKED OR BROKEN GLASS Glass Cleaning The fireplace is designed to keep the glass clean under normal operating conditions If the fireplace is op...

Страница 13: ...replace is determined by considering the location of windows doors and the traffic flow in the room where the fireplace is located allowing space in front of the unit for the hearth exten sion and the...

Страница 14: ...p must cover the entire width of the fireplace The combustible floor in front of the fireplace must be covered with at least a 1 2 inch of non combustible material tile marble stone etc See Figure 15...

Страница 15: ...raphs are not to scale consult installation instructions Product designs materials dimensions specifications colorsandpricesaresubjecttochangeordiscontinu ance without notice Allframingdimensionscalcu...

Страница 16: ...replace Side Mantel Rock Board or Other Noncombustible Facing 39 990 mm Drywall 2 x 3 Min 51mm x 76mm Standoff Mantel and Facing Side View Rock Board or Other Noncombustible Facing Drywall Figure 17 F...

Страница 17: ...mbustible Facing Drywall 2 x 3 Min Rock Board or Other Spacer Figure 22 A wall on off switch must be installed to control theblower Anoptionalheatswitchandvariable speed control are available see Page...

Страница 18: ...must be non combustible below this area u NOTES Seal the top and both sides of the roof flashing with waterproof caulk ing The gap between the vent pipe and a vertical firestop shall be sealed with no...

Страница 19: ...ase of the fireplace C The fresh air must come from outside the house The air intake must not draw air from the attic basement or garage D The air intake should be installed where it is not likely to...

Страница 20: ...for every 2 000 feet 600 m above sea level 5 All chimney installations must include at least one support Re ducing the amount of chimney weight on the fireplace will help avoid the noise created when...

Страница 21: ...tions B A Framing lumber of equal size to the joist should be used Figure 35 FEMALE END MALE END BUTTON LOCK ATTACH FOR LOCK Figure 36 INSULATION SHIELD CAT NO SPIS NAIL FIRESTOP CAT NO SPFS Chimney F...

Страница 22: ...ance to combustibles AT THIS POINT TIGHTEN CLAMPS 11 Slide IHP chimney pipe into top of tee Align male and female ends Push down on pipe sec tions until locked As sections are added it will be necessa...

Страница 23: ...all the next SP chimney section through the roof See Figure 41 NOTE If your roof is already shingled be sure to slide the upper edge under the shingles to prevent leakage 3 Install a bead of caulk aro...

Страница 24: ...verse wind conditions etc may create a need for a taller chimney should smoking occur Additional support is required above the roof if the chimney height exceeds four 4 feet Select the proper support...

Страница 25: ...nts as per these installation instructions and instructions provided by the venting Manufacturer Referencetheinstallationinstructionsprovidedbyventingmanufacturer CHIMNEY CHASE AND MULTIPLE TERMINATIO...

Страница 26: ...se the size of the hole until a 30 liner elbow can be easily slipped through 4 Slide the liner down from the top of the masonry chimney until you reach the hole level 5 Slip through the hole a 30 line...

Страница 27: ...No Cast Surround Kit CSK H7303 Cast Surround Decorative Keystone CSK DK H7757 Central Forced Air Kit Accessories Central Forced Air Kit Central forced air kit including blower BISZY flex adaptor BISA...

Страница 28: ...ctory 2 pieces PR SR2829 Secondary air tubes set of three F3540 Fireplace Ashlip F3551 Fireplace Front Bottom F3550 Top Front Insulation Protector F3554 Gasket Catalyst F3552 Catalyst Replacement Cart...

Страница 29: ...and CAN ULC S629 Description Part Cat No Lengths and Misc Chimney Components 8 length 6 Dia 6DTC 08SS 12 length 6 Dia 6DTC 12SS 18 length 6 Dia 6DTC 18SS 24 length 6 Dia 6DTC 24SS 36 length 6 Dia 6DTC...

Страница 30: ...S COMPOSANTES UTILIS ES AVEC LE FOYER DOIVENT TRE HO MOLOGU ES VOIR LA LISTE DANS LE MANUEL D INSTALLATION REMPLACER LA VITRE AVEC UN VERRE C RAMIQUE DE 5mm D PAISSEUR POUR UNE UTILISATION S CURITAIRE...

Страница 31: ...____________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________...

Страница 32: ...ct d damages repairs or inefficiency resulting from faulty installation or application of the Product IHP is not responsible for inadequate system draft caused by air conditioning and heating systems...

Страница 33: ...l use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with abnormal burning cha...

Страница 34: ...8 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing p...

Отзывы: