Figure 8 - Lineal Gain

Hemmed 

End

8" Stainless 

Inner Pipe

12 

3

/

8

" Galvanized 

Outer Pipe

 WARNING: The opening in collar around chimney 

at top of fireplace must not be obstructed. Never use 

blown insulation to fill chimney enclosure

.

VENTING INSTALLATION  

Continued

ASSEMBLY AND INSTALLATION OF DOUBLE WALL CHIMNEY 

SYSTEM

Each double wall chimney section consists of a galvanized outer 

pipe, a stainless steel inner flue pipe and a wire spacer. Pipe sections 

must be assembled independently as chimney is installed. When 

connecting chimney directly to fireplace, inner flue pipe section 

must be installed first with lanced side up. Outer pipe section can 

then be installed over flue pipe section with hemmed end up. Press 

down on each pipe section until lances securely engage hem on 

fireplace starter. Wire will assure proper spacing between inner 

and outer pipe sections.

Note:

 For Canada, use chimney parts designated HT.

 Opening in collar around chimney at top of 

fireplace must not be obstructed. Never use blown 

insulation to fill chimney enclosure.

Continue to assemble chimney sections as outlined, making sure 

that both inner and outer pipe sections are locked together. When 

installing double wall snap-lock chimney together, it is important to 

assure joint between chimney sections is locked. Check by pulling 

chimney upward after locking. Chimney will not come apart if properly 

locked. It is not necessary to add screws to keep chimney together 

(exception - see Figure 11, page 10).
The height of a vertical chimney pipe supported 

ONLY

 by the 

fireplace, must not exceed 20 feet. Chimney heights above 20 feet 

must be supported.

USING ELBOW OFFSETS (30E-8DM)

1.  To achieve desired offset, you may install combinations of 12", 

18", 24", 36" and 48" length of double wall pipe (see Figure 11/

offset chart, page 10).

 

Note:

 For systems with 2 elbow sets, minimum height is 22 feet. 

Maximum height for any system is 50 feet.

2.  Chimney weight above offset rests on return elbow. Straps must 

be securely nailed to rafters or joists (see Figure 10, details A and 

B, page 9).

3.  Maximum length of pipe between supports (return elbow or 12S-

8DM) is 6' of angle run. Maximum of two 6' angle run sections 

per chimney system (see Figure 9, page 9).

4.  All pipe connections between offset and return must be secured 

with two screws on outer pipe only (see Figure 11, page 10). Do 

not penetrate inner stainless.

LINEAL GAIN

CAT. NO. PART NO.

DESCRIPTION

GAIN

36"

Fireplace

37 

1

/

2

"

F0895

F0881

12-8DM

12-8HT

Pipe Section

10 

5

/

8

"

F0896

F0882

18-8DM

18-8HT

Pipe Section

16 

5

/

8

"

F0897

F0883

24-8DM

24-8HT

Pipe Section

23 

5

/

8

"

F0898

F0884

36-8DM

36-8HT

Pipe Section

34 

5

/

8

"

F0899

F0885

48-8DM

48-8HT

Pipe Section

46 

5

/

8

"

F0916

RT-8DM

Round Termination

7

/

8

"*

RTL-8DM

Round Termination

3

/

4

"*

F0918

RLT-8DM

Round Termination

1

/

2

"*

F0917

RTT-8DM

Round Termination with 

Slip Section

7

/

8

" to 

23 

1

/

8

"*

RTTL-8DM

Round Termination with 

Slip Section

1

/

2

" to  

21 

1

/

2

"*

F0919

RLTT-8DM

Round Termination with 

Slip Section

1

/

2

" to  

21 

1

/

4

"*

F0920

ET-8DM

Square Chase-Top

12"*

F0922

ETO-8DM

Square Chase-Top with 

Mesh

12"*

F0921

ETL-8DM

Square Chase-Top with 

Slip Section

7" to 15"*

F0923

ETLO-8DM

Square Chase-Top with 

Mesh & Slip Section

12" to  

25 

1

/

2

"*

* The lineal gain for the terminations is measured to the flue gas 

outlet height.

Содержание WCT2036WS

Страница 1: ...The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L autor...

Страница 2: ...tested for the fireplace system you may cause a fire hazard The IHP warranty will be voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace componen...

Страница 3: ...oseasignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT...

Страница 4: ...T LESS THAN 14 356 mm TO PERPENDICULAR SIDEWALL OUTSIDE AIR LEFT SIDE ONLY GAS LINE KNOCK OUT ROUND TOP TERMINATION SQUARE CHASE TOP TERMINATION AIR KIT KNOCK OUT 13 7 8 353 mm 9 1 8 232 mm 3 4 19 mm...

Страница 5: ...iling flanges touch side framing 4 Check level of fireplace and shim with sheet metal if necessary 5 Before securing fireplace to prepared framing ember protector must be placed between hearth extensi...

Страница 6: ...l Safe Zone For Projection of Combustible Materials Upper Section of Circulating Fireplace Top of Louvered Opening Fireplace Opening Note Drawing Not to Scale 8 204 mm 1 26 mm Min 12 305 mm from Perpe...

Страница 7: ...eceptacle and Ground Sheet Metal Screws Figure 7 Outside Air Kit Secure to Collars with Metal Tape Screws or Straps Min of x 20 7 mm x 508 mm in size Air Inlet Location Must Allow For Bushes or Snow V...

Страница 8: ...cal chimney pipe supported ONLY by the fireplace must not exceed 20 feet Chimney heights above 20 feet must be supported USING ELBOW OFFSETS 30E 8DM 1 To achieve desired offset you may install combina...

Страница 9: ...Elbow Offset Elbow Offset Elbow Offset Elbow 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m A B C Ceiling Support Pipe 12S 8DM Ceiling Support Pipe 12S 8DM Figure 10 Cei...

Страница 10: ...A Screws OFFSET RISE CHIMNEY LENGTH A B 48 36 24 18 12 4 3 8 16 3 8 ELBOW SET ONLY 9 25 3 4 1 11 7 8 31 1 15 37 3 8 1 16 3 4 40 1 2 1 1 20 47 1 8 1 22 5 8 52 1 8 1 1 25 1 2 57 7 8 1 27 5 8 62 1 1 30...

Страница 11: ...l it is snug against open edge of flashing see Figure 16 Use SC1 for all round termina tions Apply waterproof caulk around perimeter of collar to provide a proper seal Figure 16 Storm Collar Chimney P...

Страница 12: ...shroud is to be installed contact manufacturer for specifications 24 610 mm Min 24 610 mm Min 18 458 mm Min Typ Figure 18 Multiple Chase Installation 10 3 05 m 10 3 05 m 2 0 61 m Min 2 0 61 m Min 3 0...

Страница 13: ...ment Install gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be tested for leaks after installation is completed After ensuring that gas valve is on apply soap...

Страница 14: ...h glass doors operates much differently than a fireplace with an open front A fireplace with glass doors has a limited amount of air for combustion Excessive heat within fireplace can result if too la...

Страница 15: ...used if installed in accordance with the instructions by its manufacturer A locally fabricated shroud may be used with IHP Shroud Leg Spacer Kit SLK in accor dance with instructions provided with the...

Страница 16: ...16 PARTS WOOD BURNING FIREPLACE MODELS WRT2036WS WRT2036WSI WCT2036WS WCT2036WSI MODEL CAT NO WRT2036WS F0683 WRT2036WSI F0684 WCT2036WS F0685 WCT2036WSI F0686 11 27 23 23 22 24 10 14 25 4 17 3 2 1 18...

Страница 17: ...ner 1 13 See Page 18 Right Side Brick Liner 1 14 See Page 18 Bottom Brick Liner 1 15 See Page 18 Front Bottom Brick Liner 1 16 J6937 Blower Access Plate 1 17 J6895 Refractory Retainer 2 18 Top Insulat...

Страница 18: ...to obtain any of these parts Never use substitute materials not ap proved by IHP Use of non approved parts can result in poor performance and safety hazards 1 2 4 3 6 5 ACCESSORIES REFRACTORY STAIN K...

Страница 19: ...Snap Lock F0882 18 8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT...

Страница 20: ...UVERS AND SLIP SECTION F0921 ETL 8DM Square Top with Slip Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE T...

Страница 21: ...nditions inadequate chimney heights adversewindconditionsand orunusualenvironmental factors or conditions beyond our control take into account all variables within the installation and install the app...

Страница 22: ...ance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of...

Страница 23: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 24: ...6628 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Отзывы: