background image

SuperiorFireplaces.us.com

126628-01_J

5

FIREPLACE INSTALLATION

SELECTING LOCATION

To determine safest and most efficient location for fireplace, you 

must take into consideration the following guidelines:
1.  Location must allow for proper clearances (see Figures 1 and 2).
2.  Consider a location where fireplace will not be affected by drafts, 

air conditioning ducts, windows or doors.

3.  A location that avoids cutting of joists or roof rafters will make 

installation easier.

4.  An outside air kit is available with this fireplace (see Optional 

Outside Air Kit on page 7).

MINIMUM CLEARANCE TO COMBUSTIBLES

Back and sides of fireplace                        3/4" (19 mm) minimum*
Floor**                                                           0" (0 mm) minimum
Perpendicular wall to opening                   14" (356 mm) minimum
Top spacers                                                    0" (0 mm) minimum
Mantel clearances                                           see Mantels, page 6
Chimney outer pipe surface                          1" (26 mm) minimum

* Not required at nailing flanges

** See step 2 of Framing

 WARNING: DO NOT PACK REQUIRED AIR SPACES 

WITH INSULATION OR OTHER MATERIALS.

Minimum/Maximum Chimney Height

Minimum height of chimney, measured from base of fireplace to 

flue gas outlet of termination, is 14.5 feet for straight flue or a flue 

with one elbow set. Maximum distance between elbows is 6 feet. For 

systems with two elbow sets, minimum height is 22 feet. Maximum 

height of any system is 50 feet. This measurement includes fireplace, 

chimney sections and height of termination assembly at level of flue 

gas outlet (see Figure 20, page 12).

FRAMING

1.  Frame opening for fireplace using dimensions shown in Figures 

1 and 2.

2.  If fireplace is to be installed directly on carpeting, tile or any 

combustible material other than wood flooring, fireplace must 

be installed upon a metal or wood panel extending full width and 

depth of fireplace.

3.  Set fireplace directly in front of this opening and slide unit back 

until nailing flanges touch side framing.

4.  Check level of fireplace and shim with sheet metal if necessary.
5.  Before securing fireplace to prepared framing, ember protector 

must be placed between hearth extension (not included) and 

under bottom front edge of fireplace to protect against glowing 

embers falling through. If fireplace is to be installed on a raised 

platform, a Z-type ember protector (not included) must be fabri-

cated to fit your required platform height. Ember protector should 

extend under fireplace a minimum of 1 

1

/

2

". Ember protector 

should be made of galvanized sheet metal (28 gauge minimum) 

to prevent corrosion.

6.  Using screws or nails, secure fireplace to framing through flanges 

located on sides of fireplace.

 38 

5

/

8

(981 mm) 

 22" 

(559 mm) 

 38 

1

/

4

" (972 mm) 

Figure 1 - Framing Dimensions

 13 

3

/

4

(350 mm) 

 66 

7

/

8

" (1699 mm) 

 19 

1

/

2

"

(496 mm) 

 47 

3

/

8

"

(1204 mm) 

Maintain 

3

/

4

(19 mm)

Clearance at 

Sides and Back 

of Fireplace 

3

/

4

" (19 mm) Clearance Not

Required at nailing Flanges 

Figure 2 - Corner Installation

HEARTH EXTENSION

A hearth extension projecting a minimum of 16" in front of and a 

minimum of 8" beyond each side of fireplace opening is required to 

protect combustible floor construction in front of fireplace. Fabri-

cate a hearth extension using a material which meets the following 

specifications: a layer of noncombustible, inorganic material having 

a thermal conductivity of k = .84 BTU IN/FT

2

 HR °F (or less) at 1" 

thick. For example, if material selected has a k factor of 0.25, such 

as glass fiber, the following formula would apply:
  0.25 x 1.0" = 0.30" thickness required

 0.84
Thermal conductivity "k" of materials can be obtained from manu-

facturer or supplier of noncombustible material. If hearth extension 

is to be covered, use noncombustible material such as tile, slate, 

brick, concrete, metal, glass, marble, stone, etc. Provide a means to 

prevent hearth extension from shifting and seal gap between fireplace 

frame and hearth extension with a non-combustible material such 

as sand-cement grout (see Figure 3, page 6).

Содержание WCT2036WS

Страница 1: ...The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determine the need to obtain a permit POUR LE CANADA L autor...

Страница 2: ...tested for the fireplace system you may cause a fire hazard The IHP warranty will be voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace componen...

Страница 3: ...oseasignificanthazard IMPORTANT See appendix A page 21 for additional information regarding draft requirements smoking causes and troubleshooting WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT...

Страница 4: ...T LESS THAN 14 356 mm TO PERPENDICULAR SIDEWALL OUTSIDE AIR LEFT SIDE ONLY GAS LINE KNOCK OUT ROUND TOP TERMINATION SQUARE CHASE TOP TERMINATION AIR KIT KNOCK OUT 13 7 8 353 mm 9 1 8 232 mm 3 4 19 mm...

Страница 5: ...iling flanges touch side framing 4 Check level of fireplace and shim with sheet metal if necessary 5 Before securing fireplace to prepared framing ember protector must be placed between hearth extensi...

Страница 6: ...l Safe Zone For Projection of Combustible Materials Upper Section of Circulating Fireplace Top of Louvered Opening Fireplace Opening Note Drawing Not to Scale 8 204 mm 1 26 mm Min 12 305 mm from Perpe...

Страница 7: ...eceptacle and Ground Sheet Metal Screws Figure 7 Outside Air Kit Secure to Collars with Metal Tape Screws or Straps Min of x 20 7 mm x 508 mm in size Air Inlet Location Must Allow For Bushes or Snow V...

Страница 8: ...cal chimney pipe supported ONLY by the fireplace must not exceed 20 feet Chimney heights above 20 feet must be supported USING ELBOW OFFSETS 30E 8DM 1 To achieve desired offset you may install combina...

Страница 9: ...Elbow Offset Elbow Offset Elbow Offset Elbow 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m 6 Max 1 83 m A B C Ceiling Support Pipe 12S 8DM Ceiling Support Pipe 12S 8DM Figure 10 Cei...

Страница 10: ...A Screws OFFSET RISE CHIMNEY LENGTH A B 48 36 24 18 12 4 3 8 16 3 8 ELBOW SET ONLY 9 25 3 4 1 11 7 8 31 1 15 37 3 8 1 16 3 4 40 1 2 1 1 20 47 1 8 1 22 5 8 52 1 8 1 1 25 1 2 57 7 8 1 27 5 8 62 1 1 30...

Страница 11: ...l it is snug against open edge of flashing see Figure 16 Use SC1 for all round termina tions Apply waterproof caulk around perimeter of collar to provide a proper seal Figure 16 Storm Collar Chimney P...

Страница 12: ...shroud is to be installed contact manufacturer for specifications 24 610 mm Min 24 610 mm Min 18 458 mm Min Typ Figure 18 Multiple Chase Installation 10 3 05 m 10 3 05 m 2 0 61 m Min 2 0 61 m Min 3 0...

Страница 13: ...ment Install gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be tested for leaks after installation is completed After ensuring that gas valve is on apply soap...

Страница 14: ...h glass doors operates much differently than a fireplace with an open front A fireplace with glass doors has a limited amount of air for combustion Excessive heat within fireplace can result if too la...

Страница 15: ...used if installed in accordance with the instructions by its manufacturer A locally fabricated shroud may be used with IHP Shroud Leg Spacer Kit SLK in accor dance with instructions provided with the...

Страница 16: ...16 PARTS WOOD BURNING FIREPLACE MODELS WRT2036WS WRT2036WSI WCT2036WS WCT2036WSI MODEL CAT NO WRT2036WS F0683 WRT2036WSI F0684 WCT2036WS F0685 WCT2036WSI F0686 11 27 23 23 22 24 10 14 25 4 17 3 2 1 18...

Страница 17: ...ner 1 13 See Page 18 Right Side Brick Liner 1 14 See Page 18 Bottom Brick Liner 1 15 See Page 18 Front Bottom Brick Liner 1 16 J6937 Blower Access Plate 1 17 J6895 Refractory Retainer 2 18 Top Insulat...

Страница 18: ...to obtain any of these parts Never use substitute materials not ap proved by IHP Use of non approved parts can result in poor performance and safety hazards 1 2 4 3 6 5 ACCESSORIES REFRACTORY STAIN K...

Страница 19: ...Snap Lock F0882 18 8HT 18 Section Hi Temp Double Wall Pipe Snap Lock F0883 24 8HT 24 Section Hi Temp Double Wall Pipe Snap Lock F0884 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT...

Страница 20: ...UVERS AND SLIP SECTION F0921 ETL 8DM Square Top with Slip Section F0893 ETL 8HT Hi Temp Large Pyramid Top with Slip Section MESH SQUARE TOP TERMINATION F0922 ETO 8DM Square Top with Mesh MESH SQUARE T...

Страница 21: ...nditions inadequate chimney heights adversewindconditionsand orunusualenvironmental factors or conditions beyond our control take into account all variables within the installation and install the app...

Страница 22: ...ance The best location to install your appliance is determined by consid ering the location of windows doors and the traffic flow in the room where the appliance is located allowing space in front of...

Страница 23: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 24: ...6628 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult yo...

Отзывы: