background image

SuperiorFireplaces.us.com

126861-01P

7

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space Using 

the Standard Method

Use this work sheet to determine if you have a confined or uncon-

fined space.

Space:

 Includes the room in which you will install fireplace plus any 

adjoining rooms with doorless passageways or ventilation grills between 

the rooms.
1.  Determine the volume of the space (length x width x height).
  Length x Width x Height =__________cu. ft. (volume of space)
  Example: Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling 

height) = 2,560 cu. ft. (volume of space)

  If additional ventilation to adjoining room is supplied with grills 

or openings, add the volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to determine the maximum Btu/

Hr the space can support.

   _______ (volume of space) x 20 = (Maximum Btu/Hr the space 

can support)

  Example: 2,560 cu. ft. (volume of space) x 20 = 51,200 (maximum 

Btu/Hr the space can support)

3.  Add the Btu/Hr of all fuel burning appliances in the space.
  Vent-free fireplace  ________Btu/Hr
  Gas water heater*  ________Btu/Hr
  Gas furnace 

________Btu/Hr

  Vented gas heater  ________Btu/Hr
  Gas fireplace logs  ________Btu/Hr
  Other gas appl ____Btu/Hr
 Total 

=_______Btu/Hr

  * Do not include direct-vent gas appliances. Direct-vent draws 

combustion air from the outdoors and vents to the outdoors.

 

Example:

 

  Gas water heater        40,000 Btu/Hr
  Vent-free fireplace  +  33,000 Btu/Hr
  Total 

=  73,000 Btu/Hr

4.  Compare the maximum Btu/Hr the space can support with the actual 

amount of Btu/Hr used.

   ______ Btu/Hr (maximum the space can support) 
   ______ Btu/Hr (actual amount of Btu/Hr used)
 

Example:

     51,200 Btu/Hr (maximum the space can support) 

                      73,000 Btu/Hr (actual amount of Btu/Hr used)
The space in the example is a confined space because the actual Btu/

Hr used is more than the maximum Btu/Hr the space can support. 

You must provide additional fresh air. Your options are as follows:

A.

  Rework worksheet, adding the space of an adjoining room. If the 

extra space provides an unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. See Ventilation Air 

From Inside Building.

B.

 Vent room directly to the outdoors. See Ventilation Air From 

Outdoors.

C.

  Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room 

unconfined. 

If the actual Btu/Hr used is less than the maximum Btu/Hr the 

space can support, the space is an unconfined space. You will need 

no additional fresh air ventilation.

 WARNING: If the area in which the heater may be 

operated does not meet the required volume for indoor 

combustion air, combustion and ventilation air shall 

be provided by one of the methods described in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 

International Fuel Gas Code, or applicable local codes.

VENTILATION AIR
Ventilation Air From Inside Building 

This fresh air would come from an adjoining unconfined space. When 

ventilating to an adjoining unconfined space, you must provide two 

permanent openings: one within 12" of the ceiling and one within 

12" of the floor on the wall connecting the two spaces 

(see options 

1 and 2,

 Figure 2

)

. You can also remove door into adjoining room 

(see option 3, 

Figure 2

). 

Follow the National Fuel Gas Code, ANSI 

Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of 

ventilation grills or ducts.

AIR FOR COMBUSTION AND VENTILATION 

Continued

 

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling and one 

within 12" of the floor. Connect these items directly to the outdoors or 

spaces open to the outdoors. These spaces include attics and crawl 

spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for 

Combustion and Ventilation for required size of ventilation grills or ducts. 

IMPORTANT:

 Do not provide openings for inlet or outlet air into attic 

if attic has a thermostat-controlled power vent. Heated air entering 

the attic will activate the power vent.

Figure 3 - Ventilation Air from Outdoors (Fireplace may differ 

from actual model)

Figure 2 - Ventilation Air from Inside Building (Fireplace may 

differ from actual model)

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Or

Remove

Door into
Adjoining

Room,
Option

3

Ventilation Grills 

Into Adjoining Room,

Option 2

Ventilation

Grills 

Into Adjoining 

Room,

Option 1

12"

12"

Содержание VRL4543

Страница 1: ...installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on Page 7 of this manual WARNING If the information in this manua...

Страница 2: ...trying to assemble operate or ser vicethisheater Improperuseofthisheatercancause serious injury or death from burns fire explosion electrical shock and carbon monoxide poisoning Aftermarket Completion...

Страница 3: ...bustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Fireplaces become very hot when running firepla...

Страница 4: ...off If heated the vapors from these prod ucts may create a white powder residue within burner box or on adjacent walls or furniture 10 This fireplace needs fresh air ventilation to run properly This...

Страница 5: ...a plumber or gas fitter licensed in the Commonwealth of Massachusetts The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a...

Страница 6: ...te of a structure is known the Known Air Infiltration Rate Method may be used Follow The National Fuel Gas Code ANSI Z223 1 NFPA 54 to use this method to determine if the space is confined or unconfin...

Страница 7: ...ventilation grills between rooms See Ventilation Air From Inside Building B Vent room directly to the outdoors See Ventilation Air From Outdoors C Install a lower Btu Hr fireplace if lower Btu Hr siz...

Страница 8: ...ealer where you bought fireplace for proper type fireplace WARNING This appliance is equipped for either natural gas or propane LP gas but not both Gas type is indicated on the rating plate Field conv...

Страница 9: ...16 5 2 E 14 A B C D E 1 2 3 4 5 Wall Supplied firebox hood must be used at all times Note All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf Noncombustible mat...

Страница 10: ...7 1 2 29 5 8 29 5 8 16 3 8 7 1 8 1 7 8 8 1 4 44 1 8 1 1 55 1 8 52 47 16 1 2 11 3 4 8 1 4 5 8 INSTALLATION Continued Figure 8 VRL4543 Series Dimensions Electrical Outlet Gas Line Access Gas Line Access...

Страница 11: ...e LP gas equipment shutoff valve test gauge connection sediment trap optional tee joint pipe wrench approved flexible gas line with gas connector if allowed by local codes not provided An equipment sh...

Страница 12: ...diment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into fireplace gas controls If sediment trap is not installed or is...

Страница 13: ...he gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its eq...

Страница 14: ...a guide screw the rear panel to the fireplace as shown in Figure 16 INSTALLING HOOD 1 Loosen screws at top of face opening and slide hood through screws as shown in Figure 17 2 Tighten screws securing...

Страница 15: ...ont of the fireplace unscrew 4 corner brackets from the firebox top See Figure 21 2 Remove 2 side walls and then the rear wall Discard rear wall 3 Replace 2 side walls and reinstall the corner bracket...

Страница 16: ...ner shuts OFF Figure 26 Gas Module Right Side Figure 27 Gas Module Left Side Remote Control Feature The module has a built in remote control receiver that allows the user to program the remote transmi...

Страница 17: ...supplied with the unit into the battery compart ment It is recommended that ALKALINE batteries always be used for this product Be sure the batteries are installed with the and ends facing the correct...

Страница 18: ...tory default or degrees C Press the UP and DOWN Buttons simultaneously to change between degrees F and C SET TEMP While in THERMOSTAT mode press the UP or DOWN Button to change the SET TEMP 45 90 deg...

Страница 19: ...Flame A setting number will flash in the FLAME Zone REMOTE CONTROL OPERATION Continued LIGHT ADJUSTMENT Transmits a light setting command to the control module to adjust the light output level Availa...

Страница 20: ...rt of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS This appliance requires 120V electricity for normal operation Control module should be plugged into electr...

Страница 21: ...ave heater inspected yearly by a qualified service person We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using com...

Страница 22: ...the fireplace running Some burner flame holes may become blocked by debris or rust with no flame present If so turn off fireplace and let cool Remove blockage Blocked burner flame holes will create so...

Страница 23: ...ot Main HI LO DC Motor Drive Light Module Black Black Brown Red Orange Orange To Ground Igniter Sensor PILOT BATTERY PACK WIRING DIAGRAM Black Blk White SIZE AA SIZE AA SIZE AA SIZE AA Blk Brown Yello...

Страница 24: ...ontact local propane LP gas company 3 Clean ODS pilot see Cleaning and Main tenance Page 21 or replace ODS pilot assembly 4 Replace gas regulator 1 Contact local natural or propane LP gas company 2 Cl...

Страница 25: ...cting while cooling 1 Burner orifice is clogged or damaged 2 Damaged burner REMEDY 1 Check burner for dirt and debris If found clean burner see Cleaning and Mainte nance Page 21 1 Refer to Air for Com...

Страница 26: ...LP only 3 Gas leak See Warning statement above 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement above 2 Control valve or gas co...

Страница 27: ...4 15 16 17 18 19 20 24 21 5 22 23 6 2 1 13 10 9 12 Cat No Description F1186 VRL4543ZEN F1187 VRL4543ZEP WARNING Failure to position the parts in accordance with these diagrams or failure to use only p...

Страница 28: ...tery Backup 1 20 J6205 Battery Backup 1 21 J6833 Connector 3 8 Tube x 3 8 MPT 1 22 J8033 Valve NG 1 J8040 Valve LP 1 23 J7939 Control Module Skytech AF4000MOD 1 24 J6868 Switch Rocker ON OFF Remote 1...

Страница 29: ...S VRL4543ZEN VRL4543ZEP 1 4 6 2 8 9 7 5 3 5 11 12 13 14 10 7 8 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heat...

Страница 30: ...essory part kit s can result in poor performance and safety hazards CAT NO MODEL DESCRIPTION KIT LINEAR DECORATIVE SURROUND KITS Not Shown F4216 DS BLK 43 Decorative Surround for 43 Linear Fireplace B...

Страница 31: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Страница 32: ...your local distributor for fireplace code information Printed in U S A 2013 Innovative Hearth Products P N 126861 01 Rev P 01 2020 1769 East Lawrence Street Russellville AL 35654 SuperiorFireplaces us...

Отзывы: