background image

SuperiorFireplaces.us.com

126861-01P

24

POSSIBLE CAUSE

1. Igniter electrode not connected to igniter 

cable

2. Igniter cable pinched or wet

3. Broken igniter cable

4. Igniter electrode positioned wrong

5. Igniter electrode broken

1. Gas supply turned off or equipment 

shutoff valve closed

2. Depleted gas supply (propane/LP only)

3. ODS/pilot is clogged

4. Gas regulator setting is not correct

1. Inlet gas pressure is too low

2. Burner orifice(s) clogged

3. Thermopile leads disconnected or 

improperly connected

4. Burner will not come on in remote posi-

tion

1. Manifold pressure is too low

2. Burner orifice(s) clogged

REMEDY 

1. Reconnect igniter cable

2. Free igniter cable if pinched by any metal 

or tubing. Keep igniter cable dry

3. Replace igniter cable

4. Replace pilot assembly

5. Replace pilot assembly

1. Turn on gas supply or open equipment 

shutoff valve

2. Contact local propane/LP gas company

3. Clean ODS/pilot 

(see Cleaning and Main-

tenance,

 Page 21

)

 or replace ODS/pilot 

assembly

4. Replace gas regulator

1. Contact local natural or propane/LP gas 

company

2. Clean burner(s) 

(see Cleaning and Main-

tenance,

 Page 21

)

 or replace burner 

orifice(s)

3. Reconnect  leads 

(see Wiring Diagram, 

Page 23

)

4. Replace battery in transmitter and re-

ceiver

1. Contact local natural or propane/LP gas 

company

2. Clean burner(s) 

(see Cleaning and Main-

tenance,

 Page 21

)

 or replace burner 

orifice(s)

OBSERVED PROBLEM

When igniter button is pressed, there is no 

spark at ODS/pilot

When igniter button is pressed, there is 

spark at ODS/pilot but no ignition

Burner does not light after ODS/pilot is lit

Delayed ignition of one or both burners

TROUBLESHOOTING

 WARNING: Turn off heater and let cool before servicing. Only a qualified service person should service 

and repair heater.

 CAUTION: Never use a wire, needle or similar object to clean ODS/pilot. This can damage ODS/pilot unit.

NOTE:

 All troubleshooting items are listed in order of operation.

Содержание VRL4543

Страница 1: ...installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ventilation section on Page 7 of this manual WARNING If the information in this manua...

Страница 2: ...trying to assemble operate or ser vicethisheater Improperuseofthisheatercancause serious injury or death from burns fire explosion electrical shock and carbon monoxide poisoning Aftermarket Completion...

Страница 3: ...bustible material other than wood flooring the appliance shall be installed on a metal or wood panel extending the full width and depth of the appliance Fireplaces become very hot when running firepla...

Страница 4: ...off If heated the vapors from these prod ucts may create a white powder residue within burner box or on adjacent walls or furniture 10 This fireplace needs fresh air ventilation to run properly This...

Страница 5: ...a plumber or gas fitter licensed in the Commonwealth of Massachusetts The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a...

Страница 6: ...te of a structure is known the Known Air Infiltration Rate Method may be used Follow The National Fuel Gas Code ANSI Z223 1 NFPA 54 to use this method to determine if the space is confined or unconfin...

Страница 7: ...ventilation grills between rooms See Ventilation Air From Inside Building B Vent room directly to the outdoors See Ventilation Air From Outdoors C Install a lower Btu Hr fireplace if lower Btu Hr siz...

Страница 8: ...ealer where you bought fireplace for proper type fireplace WARNING This appliance is equipped for either natural gas or propane LP gas but not both Gas type is indicated on the rating plate Field conv...

Страница 9: ...16 5 2 E 14 A B C D E 1 2 3 4 5 Wall Supplied firebox hood must be used at all times Note All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf Noncombustible mat...

Страница 10: ...7 1 2 29 5 8 29 5 8 16 3 8 7 1 8 1 7 8 8 1 4 44 1 8 1 1 55 1 8 52 47 16 1 2 11 3 4 8 1 4 5 8 INSTALLATION Continued Figure 8 VRL4543 Series Dimensions Electrical Outlet Gas Line Access Gas Line Access...

Страница 11: ...e LP gas equipment shutoff valve test gauge connection sediment trap optional tee joint pipe wrench approved flexible gas line with gas connector if allowed by local codes not provided An equipment sh...

Страница 12: ...diment trap where trapped matter is not likely to freeze A sediment trap traps moisture and contaminants This keeps them from going into fireplace gas controls If sediment trap is not installed or is...

Страница 13: ...he gas supply piping system during any pressure testing of that system at test pressures in excess of 1 2 psi 3 5 kPa The appliance must be isolated from the gas supply piping system by closing its eq...

Страница 14: ...a guide screw the rear panel to the fireplace as shown in Figure 16 INSTALLING HOOD 1 Loosen screws at top of face opening and slide hood through screws as shown in Figure 17 2 Tighten screws securing...

Страница 15: ...ont of the fireplace unscrew 4 corner brackets from the firebox top See Figure 21 2 Remove 2 side walls and then the rear wall Discard rear wall 3 Replace 2 side walls and reinstall the corner bracket...

Страница 16: ...ner shuts OFF Figure 26 Gas Module Right Side Figure 27 Gas Module Left Side Remote Control Feature The module has a built in remote control receiver that allows the user to program the remote transmi...

Страница 17: ...supplied with the unit into the battery compart ment It is recommended that ALKALINE batteries always be used for this product Be sure the batteries are installed with the and ends facing the correct...

Страница 18: ...tory default or degrees C Press the UP and DOWN Buttons simultaneously to change between degrees F and C SET TEMP While in THERMOSTAT mode press the UP or DOWN Button to change the SET TEMP 45 90 deg...

Страница 19: ...Flame A setting number will flash in the FLAME Zone REMOTE CONTROL OPERATION Continued LIGHT ADJUSTMENT Transmits a light setting command to the control module to adjust the light output level Availa...

Страница 20: ...rt of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS This appliance requires 120V electricity for normal operation Control module should be plugged into electr...

Страница 21: ...ave heater inspected yearly by a qualified service person We also recommend that you keep the burner tube and pilot assembly clean and free of dust and dirt To clean these parts we recommend using com...

Страница 22: ...the fireplace running Some burner flame holes may become blocked by debris or rust with no flame present If so turn off fireplace and let cool Remove blockage Blocked burner flame holes will create so...

Страница 23: ...ot Main HI LO DC Motor Drive Light Module Black Black Brown Red Orange Orange To Ground Igniter Sensor PILOT BATTERY PACK WIRING DIAGRAM Black Blk White SIZE AA SIZE AA SIZE AA SIZE AA Blk Brown Yello...

Страница 24: ...ontact local propane LP gas company 3 Clean ODS pilot see Cleaning and Main tenance Page 21 or replace ODS pilot assembly 4 Replace gas regulator 1 Contact local natural or propane LP gas company 2 Cl...

Страница 25: ...cting while cooling 1 Burner orifice is clogged or damaged 2 Damaged burner REMEDY 1 Check burner for dirt and debris If found clean burner see Cleaning and Mainte nance Page 21 1 Refer to Air for Com...

Страница 26: ...LP only 3 Gas leak See Warning statement above 1 Not enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement above 2 Control valve or gas co...

Страница 27: ...4 15 16 17 18 19 20 24 21 5 22 23 6 2 1 13 10 9 12 Cat No Description F1186 VRL4543ZEN F1187 VRL4543ZEP WARNING Failure to position the parts in accordance with these diagrams or failure to use only p...

Страница 28: ...tery Backup 1 20 J6205 Battery Backup 1 21 J6833 Connector 3 8 Tube x 3 8 MPT 1 22 J8033 Valve NG 1 J8040 Valve LP 1 23 J7939 Control Module Skytech AF4000MOD 1 24 J6868 Switch Rocker ON OFF Remote 1...

Страница 29: ...S VRL4543ZEN VRL4543ZEP 1 4 6 2 8 9 7 5 3 5 11 12 13 14 10 7 8 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this heat...

Страница 30: ...essory part kit s can result in poor performance and safety hazards CAT NO MODEL DESCRIPTION KIT LINEAR DECORATIVE SURROUND KITS Not Shown F4216 DS BLK 43 Decorative Surround for 43 Linear Fireplace B...

Страница 31: ...natural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard...

Страница 32: ...your local distributor for fireplace code information Printed in U S A 2013 Innovative Hearth Products P N 126861 01 Rev P 01 2020 1769 East Lawrence Street Russellville AL 35654 SuperiorFireplaces us...

Отзывы: