SuperiorFireplaces.us.com

900464-01C

10

INSTALLATION  

Continued

*  Purchase the optional equipment shutoff valve from your dealer.
**Minimum inlet pressure for purpose of input adjustment. 

Figure 12 - Gas Connection

  Pipe  Cap Tee

 Nipple    Joint

Gas Control 

3" Minimum

Sediment Trap

Equipment Shutoff Valve 

With 1/8" NPT Tap*

Approved Flexible Gas 

Hose (if allowed by 

local codes)

PROPANE/LP 

From External 

Regulator

(11" W�C�** 

to 14" W�C� 

Pressure)

NATURAL 

From Gas 

Meter

(5" W�C�** 

to 10�5" W�C� 

Pressure)

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1�  Disconnect appliance with its appliance main gas valve (control 

valve) and equipment shutoff valve from gas supply piping system� 

Pressures in excess of 1/2 psig will damage appliance regulator�

2�  Cap off open end of gas pipe where equipment shutoff valve was 

connected�

3�  Pressurize supply piping system by either opening propane/LP sup-

ply tank valve for propane/LP gas or opening main gas valve located 

on or near gas meter for natural gas or using compressed air�

4�  Check all joints of gas supply piping system� Apply noncorrosive 

leak detection fluid to all joints� Bubbles forming show a leak� 

5�  Correct all leaks at once�
6�  Reconnect appliance and equipment shutoff valve to gas supply� 

Check reconnected fittings for leaks� 

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1�  Close equipment shutoff valve (see Figure 13).
2�  Pressurize supply piping system by either opening propane/LP 

supply tank valve for propane/LP gas or opening main gas valve 

located on or near gas meter for natural gas or using compressed 

air�

3�  Check all joints from gas meter to equipment shutoff valve for 

natural gas or propane/LP supply to equipment shutoff valve 

for propane/LP (see Figure 14 or Figure 15, Page 11). Apply 

noncorrosive leak detection fluid to all joints� Bubbles forming 

show a leak� 

4�  Correct all leaks at once�

PRESSURE TESTING APPLIANCE GAS CONNECTIONS

1�  Open equipment shutoff valve (see Figure 13)
2�  Open main gas valve located on or near gas meter for natural gas 

or open propane/LP supply tank valve�

3�  Make sure control knob of appliance is in the OFF position�

4�  Check all joints from gas meter to equipment shutoff valve for 

natural gas or propane/LP supply to equipment shutoff valve for 

propane/LP (see Figure 14 or Figure 15, Page 11). Apply noncor-

rosive leak detection fluid to all joints� Bubbles forming show a leak� 

5�  Correct all leaks at once�

6�  Light appliance (see Operation, Page 15)� Check all other internal 

joints for leaks�

7�  Turn off appliance (see To Turn Off Gas to Appliance, Page 15).

Figure 13 - Equipment Shutoff Valve

Open

Closed

Equipment 

Shutoff 

Valve

 CAUTION: Avoid damage to gas control. Hold gas 

control with wrench when connecting it to gas piping 

and/or fittings.

We recommend that you install a sediment trap in supply line as 

shown in Figure 12� Locate sediment trap where it is within reach for 

cleaning� Install in piping system between fuel supply and appliance� 

Locate sediment trap where trapped matter is not likely to freeze� A 

sediment trap traps moisture and contaminants� This keeps them 

from going into appliance controls� If sediment trap is not installed 

or is installed wrong, appliance may not run properly�

CHECKING GAS CONNECTIONS

 WARNING: Test all gas piping and connections, 

internal and external to unit, for leaks after installing 

or servicing. Correct all leaks at once.

 WARNING: Never use an open flame to check for 

a leak. Apply a noncorrosive leak detection fluid to 

all joints. Bubbles forming show a leak. Correct all 

leaks at once.

 CAUTION: Make sure external regulator has been 

installed between propane/LP supply and appliance. 

See guidelines under Connecting to Gas Supply

Page 9.

PRESSURE TESTING GAS SUPPLY PIPING SYSTEM 

The appliance and its appliance main gas valve must be disconnected 

from the gas supply piping system during any pressure testing of 

that system at test pressures in excess of 1/2 psi (3�5 kPa)�
The appliance must be isolated from the gas supply piping system 

by closing its equipment shutoff valve during any pressure testing of 

the gas supply piping system at test pressures equal to or less than 

1/2 psi (3�5 kPa)�

Содержание MNF24ONE

Страница 1: ...ce in an en closed space such as a camper tent car or home DANGER FIRE OR EXPLOSION HAZARD If you smell gas Shut off gas to the appliance Extinguish any open flame If odor continues leave the area immediately After leaving the area call your gas supplier or fire department Failure to follow these instructions could result in fire or explosion which could cause property damage personal injury or de...

Страница 2: ...a qualified installer service agency or the gas supplier DANGER Carbon monoxide poisoning may lead to death WARNING This product can expose you to chemi calsincludingCarbonBlack whichisknowntotheState of California to cause cancer and Carbon Monoxide which is known to the State of California to cause birth defects or other reproductive harm For more information go to www P65Warnings ca gov WARNING...

Страница 3: ...nstallanadjustablesafety gate to keep toddlers young children and other at risk individuals out of the room and away from hot surfaces 2 Do not place propane LP supply tank s inside any structure Locate propane LP supply tank s outdoors propane LP units only 3 If you smell gas shut off gas supply do not try to light any appliance do not touch any electrical switch do not use any phone in your buil...

Страница 4: ...rorsimilarproducts turn appliance off If heated the vapors from these products may create a white powder residue within burner box or on adjacent walls and furniture 9 Do not use this appliance as a wood burning appliance Use only the logs provided with the appliance Do not burn solid fuels in this appliance 10 Do not run appliance where flammable liquids or vapors are used or stored under dusty c...

Страница 5: ... optional MAGNIFLAME EMBER BURNER KIT MFEB the depth dimension increases by 3 1 2 MINIMUM FIREPLACE CLEARANCE TO COMBUSTIBLE MATERIALS Side Wall 16 Ceiling 42 Floor 5 Front 36 LOG SIZING REQUIREMENTS Log Size Minimum Firebox Size Height Depth Front Width Rear Width LMF24GTA B LMF24MOA B 29 15 5 32 5 22 75 LMF30GTA B LMF30MOA B 29 15 5 39 26 75 LMF36GTA B LMF36MOA B 29 20 47 33 OUTDOOR ENCLOSURE RE...

Страница 6: ...t Noncombustible material must extend at least 8 up for all models If noncombustible material is less than 12 you must install the fireplace hood accessory See Figure 3 for minimum clearances If Using Mantel You must have noncombustible material s above the fireplace open ing Noncombustible materials such as slate marble tile etc must be at least 1 2 thick With sheet metal you must have noncombust...

Страница 7: ...arances between fireplace opening and mantel shelf If you do not meet the clearances listed below you will need a hood Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top of fireplace opening a hood is not required see Figure 4 Page 7 14 Min Combustible Material Noncombustible Material Figure 6 Minimum Fireplace Clearances If Installed at Floor Level Hea...

Страница 8: ... Only Installation of this gas log set as a vented indoor appliance in the Commonwealth of Massachusetts requires the damper be permanently removed or welded in the fully open position You must install the damper clamp accessory to order see Acces sories Page 22 This will ensure vented operation see Figure 8 The damper clamp will keep damper open Installation instructions are included with clamp a...

Страница 9: ...ead gas will void the manufacturer s warranty to this appliance Installation must include an equipment shutoff valve union and plugged 1 8 NPT tap Locate NPT tap within reach for test gauge hook up NPT tap must be upstream from appliance see Figure 12 Page 10 IMPORTANT Install equipment shutoff valve in an accessible location The equipment shutoff valve is for turning on or shutting off the gas to...

Страница 10: ...ted on or near gas meter for natural gas or open propane LP supply tank valve 3 Make sure control knob of appliance is in the OFF position 4 Check all joints from gas meter to equipment shutoff valve for natural gas or propane LP supply to equipment shutoff valve for propane LP see Figure 14 or Figure 15 Page 11 Apply noncor rosive leak detection fluid to all joints Bubbles forming show a leak 5 C...

Страница 11: ...F30ONE MNF30OPE LMF36GTA B LMF36MOA B WARNING Failure to position the parts in accor dance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury CAUTION Afterinstallationandperiodicallythere after check to ensure that no flame comes in contact with any log With appliance set to Hi check to see if flamescontactany...

Страница 12: ... See Figures 17 17A and 17B Figure 17A shows how the log must fit against the end of the burner Figure 17B shows how the notch in log fits against the vertical portion of the burner tube Place this log on the base assembly by inserting it from the left side as shown in Figure 17 You will need to twist the log slightly to get it to fit against the burners properly It will rest even with the back ed...

Страница 13: ...025 See Figures 18 18A and 18B The log has a rectangular stand off on the bottom that fits against the lip on the black metal base as shown in Figure 18A The bottom of this log has a slot that fits over the second bar on the grate as shown in Figure 18B Place the log on the base assembly as shown in figures Figure 18A Installing Front Left Log Side View Figure 18B Installing Front Left Log Charred...

Страница 14: ...is on the top of the middle split log The right end of this log rests behind the knot on the top of the front right log 6 Find the right split crossover log D 022 The bottom of the log has a rectangular stand off that fits in the slots on the right side of the front right log and the middle split log Place this log as shown in Figure 21 Right Split Crossover Log D 022 Right Front Log Square Peg Fi...

Страница 15: ...as supplier from a neighbor s phone Follow the gas supplier s instructions C Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS 1 STOP Read the safety information first 2 Do not attempt to light the burne...

Страница 16: ... The remote system is ready for use Pushing and holding the LEARN button for 6 seconds will result in clearing the transmitter security code from the module s memory The module will make three long beeps in succession when it has been cleared Remote Off Switch ADJ S Pilot Connection I Pilot Connection AF 4000 MOD Module Rt Side Figure 26 Gas Module Right Side AF 4000 MOD Module Lt Side AUX Connect...

Страница 17: ...ing compressed air in a can please follow the directions on the can If you don t follow directions on the can you could damage the pilot assembly 1 Shut off unit Allow unit to cool for at least thirty minutes 2 Inspect burner and primary air inlet holes on injector holder for dust and dirt see Figure 31 3 Blow air through the ports slots and holes in the burner 4 Check injector holder located at e...

Страница 18: ... Pilot I S AUX AF 5000MOD AF 4000 AF 4000B P Control Module Black Black Opti Red SWI SWI GND Black Red HI LO Main Black These wires are not used on this application CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous opera tion Verify proper operation after servicing ...

Страница 19: ...n ON button on remote control is pressed there is spark at igniter but no ignition 1 Gas supply turned off or equipment shutoff valve closed 2 Air in gas lines when installed 3 Depleted gas supply propane LP only 4 Control module not in REMOTE position 5 Gas control valve pressure setting is not correct 6 Inlet gas pressure is too low 7 Burner orifice s clogged 8 Wire disconnected from gas control...

Страница 20: ...and Main tenance Page 17 or replace burner orifice s White powder residue forming within burner box or on adjacent walls or furniture 1 When heated vapors from furniture polish wax carpet cleaners etc may turn into white powder residue 1 Turn appliance off when using furniture polish wax carpet cleaners or similar products Remote does not function 1 Battery is not installed Battery power is low 1 ...

Страница 21: ...ature is too high 1 Check to see the minimum fireplace size requirements are met Page 6 Module makes one beep every one second 1 The burner did not successfully ignite 1 Press OFF then ON buttons to re attempt ignition Refer to When on button on remote control is pressed there is spark at igniter but no ignition on Page 19 Gas odor during combustion 1 Gas leak See Warning statement at top of Page ...

Страница 22: ...uantity required 6 The installation date of the appliance If you encounter any problems or have any questions concerning the installation or application of this appliance please contact your dealer IHP 1769 East Lawrence Street Russellville AL 35654 Visit us at SuperiorFireplaces us com SERVICE HINTS When Gas Pressure Is Too Low pilot will not stay lit burners will have delayed ignition appliance ...

Страница 23: ...11 12 13 15 16 18 19 20 21 23 24 25 26 22 17 14 8 3 Cat No Model F2123 MNF24ONE F2125 MNF24OPE F2127 MNF30ONE F2129 MNF30OPE WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifi cally approved with this heater may result in property damage or personal injury ...

Страница 24: ... Tube x 3 8 NPT 1 17 J6532 Grate MF42 Stainless Steel 1 J8237 Grate MF48 Stainless Steel 1 18 J4711 Flextube Dormont 3 8 X 15 1 19 J4733 Brass Compression Cap Slv 3 8 1 20 J6127 Orifice Holder 90 Degree Elbow 1 21 J3604 Orifice 120 1 J3615 Orifice 070 1 22 J5198 Shutter Air 1 J5199 Shutter Air 1 23 J8173 Screw Blk Pan HD PH 10 24 X 3 4 2 24 J8172 Nut Hex 10 24 Blk Finish 2 25 J6548 Assembly Ignite...

Страница 25: ... CAT NO Log Id CAT NO Log Id CAT NO Log Id DESCRIPTION QTY 1 J8245 D 061 J8253 D 019 J8259 D 027 Log Front Right 1 2 J8246 D 060 J8254 D 018 J8260 D 026 Log Back Left 1 3 J8247 D 059 J8255 D 017 J8261 D 025 Log Front Left 1 4 J6519 D 020 J6519 D 020 J6519 D 020 Log Charred 1 5 J8248 D 063 J8256 D 021 J8262 D 028 Log Middle Split 1 6 J8249 D 022 J8257 D 022 J8263 D 022 Log Right Split Crossover 1 7...

Страница 26: ... 3 9 1 7 8 5 4 KEY NO CAT NO LOG ID NO CAT NO LOG ID NO CAT NO LOG ID NO DESCRIPTION QTY 1 J6696 D 061 J6516 D 019 J6527 D 027 Log Front Right 1 2 J6697 D 060 J6517 D 018 J6528 D 026 Log Back Left 1 3 J6698 D 059 J6518 D 017 J6529 D 025 Log Front Left 1 4 J6519 D 020 J6519 D 020 J6519 D 020 Log Charred 1 5 J6699 D 063 J6520 D 021 J6530 D 028 Log Middle Split 1 6 J6521 D 022 J6521 D 022 J6521 D 022...

Страница 27: ...produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product d damages repairs or inefficiency resulting from faulty installation or application of the Product This Limited Three Year Warranty covers only parts and labor as provided herein In no case shall IHP be ...

Страница 28: ...liance serial number Date appliance was Installed Type of gas appliance uses Dealer name Innovative Hearth Products IHP reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information 1769 East Lawrence Street Russellville AL 35654 P900464 01 ...

Отзывы: