background image

Superiorfireplaces.US.com

900671-00_NC

7

INSTALLATION 

Continued

VENTING INSTALLATION 

Continued

Wiring Instructions

1.  Loosen strain relief by turning plastic screw counterclockwise.
2.  Remove electrical cover plate (with strain relief) from fireplace 

by removing two sheet metal screws.

3.  Slide power source wiring through strain relief opening and 

electrical cover plate and make all necessary connections.

4.  Place all wiring connections into electric housing as shown in 

Figure 6a.

5.  Secure electrical cover plate with screws previously removed.
6.  Tighten strain relief plastic screw.

Note:

 Electrical housing and cover plate have sharp edges. Wear 

protective gloves.

VENTING INSTALLATION

OUTSIDE AIR KIT 

Installation of outside air kit should be performed during rough framing 

of fireplace due to the nature of it's location. The supplied flex duct 

measures approximately 10" compressed and up to approximately 75" 

extended. Outside combustion air is accessed through mobile home 

floor using air kit model AK6F-6, included with the fireplace, or a side 

wall using optional air kit model AK6W-6 (see Accessories on page 17).

AK6F-6 Only:

 The outside air vent is installed through a ventilated 

crawl space (see Figure 7).
1.  Locate air inlet on left side of fireplace's outer surround. 

2. 

Cut out any visible insulation that may obstruct airflow.

3.  Secure collar air duct with screws provided (bend tabs in before 

installing).

4.  Secure and Seal Flex Duct to Collar with Metal Tape (Not Sup-

plied), Screws or Tie Straps (Supplied).

5. 

Extend flex duct to attach to air inlet tube. Insert flex duct into air 

inlet tube and secure it with metal tape (Not Supplied), screws or 
tie straps (Supplied). Seal any remaining gaps around air inlet tube.

4. 

Secure and seal flex duct to collar with metal tape (Not Supplied), 

screws or tie straps (Supplied).

5. 

Extend flex duct to attach 

outside air vent termination.

6.  Construct an 8" x 8" inside framing or opening on exterior wall.
7.  Install outside air vent termination in a location that would not 

eventually be obstructed by bushes, snow or other obstructions. 

Locate vent near fireplace to make flex duct installation easier.

8. 

Extend flex duct to attach air vent termination. Insert flex duct 

into air vent termination and secure it with metal tape (Not Sup-

plied), screws or tie straps (Supplied). Seal any remaining gaps 

around air vent termination.

Figure 7 - Outside Air Kit (Floor)

Figure 7a - Outside Air Kit (Wall)

Bend Tabs 

In Before 

Installing

Floor

Bend Tabs 

In Before 

Installing

Cut and Remove Any 

Insulation Blocking Airflow

Secure and Seal Flex Duct to Collars 

with Metal Tape (Not Supplied), Screws 

or Tie Straps (Supplied)

Collar Air 

Duct

Air Inlet Tube

Flex Duct Extends 

Up to 6 Feet

Cut and Remove Any 

Insulation Blocking Airflow 

(Insulated Models Only)

Outside 

Air Vent 

Termination

Air Vent Location 

Must Allow for 

Bushes, Snow and 

Other Possible 

Obstructions

Secure and Seal 

Flex Duct to Collars 

with Metal Tape (Not 

Supplied), Screws or 

Tie Straps (Supplied)

Flex Duct Extends 

Up to 6 Feet

Collar Air 

Duct

CHIMNEY PIPE

     WARNING

Label part number 900599-01 must be applied by the 

installer to all chimney pipe sections but is not required 

on sections that will be visible after the installation is 

complete. Label must wrap around the circumference 

of the pipe. See accessories, page 19 for Kit F2659.

     CAUTION

Combustion air inlet ducts shall not terminate in 

attic space.

     CAUTION

The maximum height for the air vent can not exceed 

3 feet below the flue gas outlet of the termination.

AK6W-6 Only:

 Construct an 8" x 8" framing or opening on exterior 

wall (see Figure 7a).

The supplied flex duct measures approximately 10" compressed and 

up to approximately 75" extended.

1.  Locate air inlet cover plate on left side of fireplace's outer sur-

round.

2. 

Cut out any visible insulation that may obstruct airflow.

3.  Secure collar air duct with screws provided (bend tabs in before 

installing).

Содержание MHWB36CB

Страница 1: ...ent free log heater see Accessories page 19 FOR CANADA The authority having jurisdiction such as the municipal building department fire department etc should be contacted before installation to determ...

Страница 2: ...n sibility for the following actions a Modificationofthefireplace components doors airinletsystem and damper control b Use of any component part not manufactured or approved by IHP in combination with...

Страница 3: ...efluwithheadaches dizziness or nausea If you have these signs get fresh air at once Have the appliance inspected by a qualified service technician Some people are more affected by carbon monoxide than...

Страница 4: ...S THAN 14 356 mm TO PERPENDICULAR SIDEWALL OUTSIDE AIR LEFT SIDE ONLY GAS LINE KNOCK OUT ROUND TOP TERMINATION SQUARE CHASE TOP TERMINATION AIR KIT KNOCK OUT LEFT SIDE 13 7 8 353 mm 9 1 8 232 mm 3 4 1...

Страница 5: ...stem is 50 feet This measurement includes fireplace chimney sections and height of termination assembly at level of flue gas outlet see Figure 27 page 13 FRAMING 1 Frame opening for fireplace using di...

Страница 6: ...o Combustible Material 33 12 1 4 312 mm Ref 1 1 2 39 mm Max 6 153 mm Ref 6 153 mm Min 9 229 mm Min 12 305 mm Min 3 77 mm Nom Combustible Material Safe Zone For Projection of Combustible Materials Uppe...

Страница 7: ...ach outside air vent termination 6 Construct an 8 x 8 inside framing or opening on exterior wall 7 Install outside air vent termination in a location that would not eventually be obstructed by bushes...

Страница 8: ...Install the thimble from below a finished roof and ceiling assembly Push the thimble assembly tube section first up into an already prepared opening and secure open end of the thimble base to the fini...

Страница 9: ...boveceilinglevel firestopspacermustbeinstalled on the bottom side of the ceiling If an attic is above ceiling level firestop thimble must be installed on the bottom side of ceiling joist Figure 14 Not...

Страница 10: ...64 1 2 134 3 8 1 2 1 67 1 4 139 5 8 4 VENTING INSTALLATION Continued Figure 14 Installing Thimble Outer Pipe Thimble Cathedral Ceiling 14 Min Outer Pipe Of Chimney PENETRATING ROOF To maintain a 1 cle...

Страница 11: ...etrate inner stainless FIRESTOP SPACERS 3600FS 8DM 1 Firestop spacers are required at each point where chimney penetrates a floor space Their purpose is to establish and maintain required clearance be...

Страница 12: ...3 Places Secure with Screws RLT 8DM Level of Flue Gas Outlet Caulk Collar Flashing Underlap Shingles Bottom Only Figure 23 Termination Overlap Shingles Top and Sides Flue Pipe of RLT 8DM Inside Inner...

Страница 13: ...92 m Min 3 0 92 m Min Level of Flue Gas Outlet Figure 25 10 Foot Rule CHIMNEY SUPPORT BRACKET KIT CSK 8DM If exposed portion of chimney is greater than five feet above roofline support wires are recom...

Страница 14: ...g that the gas valve is on apply soap and water solution to all connections and joints Bubbles forming show a leak Correct all leaks at once DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPERAT...

Страница 15: ...in this fireplace Always keep fire back from doors and never allow flames to contact glass OPTIONAL GAS LINE INSTALLATION Continued FINISHING FIREPLACE Combustible materials such as wallboard gypsum...

Страница 16: ...yhole slot then pull down and forward to lock it in place see Figure 34 Vent damper must be locked in the full open position before operating fireplace Figure 33 Damper Handle Location Damper Handle W...

Страница 17: ...fireplace ready You can also visit our web site at Superiorfireplaces US com CAT NO MODEL DESCRIPTION BI FOLD GLASS DOORS F0972 BDB36 36 Standard Black Finish Included F0973 BDB36B 36 Standard Brushed...

Страница 18: ...600FS 8DM 1 1 Clearance Firestop Spacer ROOF FLASHING F0909 V6F 8DM Roof Flashing 0 to 6 12 Pitch 30 Base F0910 V12F 8DM Roof Flashing 6 12 to12 12 Pitch CHIMNEY SUPPORT BRACKET KIT Support Bracket Se...

Страница 19: ...ce Hood ADJUSTABLE FIRESTOP THIMBLE Not shown F2696 LB 97008A Adjustable Firestop Thimble LABEL UL127 50PK WARNING HOT Fire Risk Insulation and combustibles must not touch pipe Consult manual for clea...

Страница 20: ...Superiorfireplaces US com 900671 00_NC 20 PARTS WOOD BURNING FIREPLACE MODEL MHWB36CB 11 27 23 23 22 24 10 14 25 4 17 3 2 1 18 5 20 28 12 7 15 9 16 30 13 29 8 26 6 19 21...

Страница 21: ...Front Bottom Brick Liner 1 16 J6937 Blower Access Plate 1 17 J6895 Refractory Retainer 2 18 Top Insulation 1 19 Insulation Retainer 1 20 J6918 Top Standoff 4 21 J6893 Chimney Starter Collar 1 22 Door...

Страница 22: ...4 36 8HT 36 Section Hi Temp Double Wall Pipe Snap Lock F0885 48 8HT 48 Section Hi Temp Double Wall Pipe Snap Lock F0886 30E 8HT 30 Degree Hi Temp Offset and Return F0887 12S 8HT Hi Temp Chimney Suppor...

Страница 23: ...be subject to normal use with approved fuels listed in the Operation Manual provided with the product This includes burning such fireplace fuels as wood and natural or propane gas Fuel products with a...

Страница 24: ...aler name P900671 00 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and produc...

Отзывы: