6.2.3.b Technical Data (PWM and 0-10V)
Technical data 0-10V:
0-10V: 2V to 10V (20% to 100%)
Designed for a load of 10K Ohm.
10V = 100% Speed
5V = 50% Speed
2V = 20% Speed
0V = Off
6.2.4 Purging Time
During this time period, the pump is running with full speed (100%) to ensure trouble-free startup. After this time has passed, the pump is set to
speed control and is set to max. speed or min speed, depending on the speed control variant „6.2.1. - Variant“ on page 27 chosen. Purging time can
not be applied with PWM or 0-10V output.
Settings range: 5 to 600 seconds / Default setting: 8 seconds
6.2.5 Sweep Time
Sweep time determines the inertia of the speed control to prevent strong fl uctuations in temperature. Sweep time is the timespan for a complete
change from minimum to maximum pump speed.
Settings range: 1 to 15 minutes / Default setting: 4 minutes
6.2.6 Max Speed
The maximum speed of the pump is specifi ed here. During the setting the pump runs at the specifi ed speed and the fl ow rate can be determined.
Settings range: 70% to 100% / Default setting: 100%
CAUTION
The indicated percentages are guide values that may vary to a greater or lesser extent depending on the system, pump and pump
stage.