Service Manual Ideal Air CG2 Commercial Grade Dehumidifier
Sunlight Supply, Inc.
20
11.6. Re-‐charging the refrigerant
NOTE: If refrigerant gas is lost from the machine, it may be necessary to use a
Qualified Refrigeration Technician to correct the problem. Contact
Ideal Air Support for more information.
STEP #1. Take off the front housing.
STEP #2. Find the source of the leak and repair using specific refrigerant grade solder.
STEP #3. Locate the pinch-‐off tubes (see picture below) and solder on service valves.
STEP #4. Connect a vacuum pump, and evacuate refrigerant system for 20 to 30
minutes, until 15Pa~30Pa of vacuum are obtained.
STEP #5. Charge the system with the refrigerant charge listed on the rating label
found on the side of the unit.
Step #6. Reassemble.
Gas delivery ports
Figure:
2
nd
3
nd
1