95
C
Ch
he
ec
ckk iitte
em
m
C
Ch
he
ec
ckk m
me
etth
ho
od
d
Grounding and
equipotential connections
•
Check
whether
the
grounding
connection
is
performed properly and the grounding resistance is
less than 4Ω.
•
Check whether the equipotential connections inside
the MV Station are performed properly.
•
Check whether the equipotential connection of the oil
tray is performed properly.
Fan
•
Check the running status of the fans.
•
Check whether the fan blades have cracks.
•
Check whether the fan makes abnormal noise during
running.
Screws
Check all screws inside the MV Station.
M
Ma
aiin
ntte
en
na
an
nc
ce
e ((o
on
nc
ce
e e
evve
erryy 6
6 m
mo
on
ntth
hss tto
o a
a yye
ea
arr))
C
Ch
he
ec
ckk iitte
em
m
C
Ch
he
ec
ckk m
me
etth
ho
od
d
Safety function
•
Check the stop functions of the emergency stop
button and the LCD.
•
Simulate shutdown
•
Check the warning labels and other device symbols
for completeness and legibility, and replace them in
time if necessary.
Software maintenance
Inspect all parameter settings.
Module cleanness
•
Check the temperature and cleanness of the
radiator. If necessary, clean the radiator with a
vacuum.
•
If necessary, replace the filter.
•
Note: Check the ventilation performance of the air
inlet. Otherwise, a fault may occur in the module due
to overheat caused by poor ventilation.
System Manual