23
1:Heat shrink tubing
2:OT/DT terminal
Step 2
Unscrew the screw on the side of the converter, fasten the cable with a screw driver.
Step 3
Apply silica gel or paint the grounding terminal to improve its anti-corrosion
performance.
There are two grounding terminals. Use at least one of them to ground the
converter.
-- -- E
En
nd
d
5.5
DC Cable Connection
Electric shock!
Be careful when you connect the electrical cables. Voltage that can be fatal
may exist between the positive and negative electrodes of the storage battery.
Make sure that the battery is well insulated to the ground before you connect
the storage battery to the converter.
The following requirements must be fulfilled when the battery is being con-
nected. Failing to do so may cause irreversible damage to the converter that is
not covered by the warranty.
•
Make sure that the voltage on the positive or negative electrode of the sto-
rage batter does not exceed 1,500V.
•
Make sure that the maximum input current of the storage battery does not
exceed 140A.
Step 1
Take out the DC connector from the packaging. The positive electrode connector is or-
ange and the negative electrode connector is black.
User Manual