1.4 Specification Data
E300 series power range
:
2S0002(B) ~2S0022(B) and 4T0007(B) ~4T0037(B).
E300 series specification data and typical functions
:
Rated volt and freq
3 PH
(
4T****
)
380V
50/60 Hz
1 PH
(
2S****
)
220V
50/60 Hz
Input
Permissible volt range
320V ~ 460V
170V ~ 270V
Volt 0
~
380V
0~220V
Freq 0~1000
Hz
Output
Overload Endurance
110% for long-term
;
150% for 1m
;
180% for 2s
Control Mode
V/F control
Analog Input 0.4% of maximum output freq
Freq setting
Resolution
Digital Input
0.1 Hz
Analog Input Within 0.4% of maximum output freq
Freq Precision
Digital Input
Within 0.1% of setting freq
Torque boost Manual set: 0.0~20.0% of rated output
Control
Characteri-
stics
V/F
control
Auto
current/volt
limit
It will check motor stator current and volt
automatically based on special arithmetic to control
within allowable range to ensure minimum failure
during acc/ dec or stable running.
Multi-speed control
Seven programmable multi-speed control, three
multi-speed control terminal
RS485 communication
(E300B series)
Standard built-in RS485 interface, RS485
communication protocol and MODBUS for choice
Analog input
Panel potentiometer setting, DC volt 0
~
10V
,
DC
current 0
~
20mA
Freq setting
Digital input
Operation panel setting
,
RS485 interface setting,
UP/DW terminal control
Relay and OC
output
One OC output and one relay output (TA, TB, TC)
as many as 9 types for choice
Output Signal
Analog output One 0~10V volt signal
Acc /dec time setting
0.1
~
600s continuous setting, S curve and linear
mode for choice
DC braking
Action freq 0~500.0 Hz, action time 0~20.0 S
Low noise running
Carrier wave freq 1.5 KHz ~ 12.0 KHz continuous
adjustment to ensure the lowest motor noise.
Typical
Function
Running function
Upper and Lower freq setting, reversal operating
restriction, RS485 communication,, freq increasing /
decreasing control etc.
Running state
Output freq, current and volt
,
motor rotate speed,
freq setting, module temperature, analog I/O
Display
Operation panel
display
Warning
Last four times failure record, output freq, current,
volt and DC volt of last fault trip for running
parameter record
Protection / warning function
Over current
,
over volt, under volt, overheating,
short circuit etc.
E300 Series Mini-type Integrated Universal Inverter Manual