F1.4 Analog output selection Setting range
:
0 ~ 2
Meaning of selection analog output terminal AO.
1
st
of LED
:
Define meaning of analog output AO
0
:
Output freq
Analog output (AO) amplitude is direct ratio to inverter output freq. Upper setting range ( [F1.6])
of analog output is corresponding to upper freq.
1
:
Output current
Analog output (AO) amplitude is direct ratio to inverter output current. Upper setting range
([F1.6]) of analog output is corresponding to twice than inverter rated current.
2
:
Output volt
Analog output (AO) amplitude is direct ratio to inverter output volt. Upper setting range
([F1.6]) of analog output is corresponding to max output volt ([F0.13]).
F1.5 AO output lower limit Setting range
:
0.0 V ~ [F1.6]
F1.6 AO output upper limit Setting range
:
[F1.5] ~ 10.0 V
Define max and min value of analog output AO output signal shown as fig 6-7.
[F1.6]
AO
Rated current
O utput freq
Upper freq
[F1.5]
O utput current
M ax/rated volt Output volt
1
2
3
Fig 6-7 Analog output content of analog output terminal
F1.7 Input terminal 1 function selection Setting range
:
0 ~ 12
F1.8 Output terminal 2 function selection Setting range
:
0 ~ 12
F1.9 Input terminal 1 function selection Setting range
:
0 ~ 12