42
SUNFAR E300 SERIES
Data
Operation
0
Read slave state and characteristics information
1
Read slave running parameter
2
Read function code parameter
Modify inverter RAM area function code parameter, it will not save if power-off
(no storage)
3
4
Send control order
5
Modify inverter EPROM area function code parameter, it will save if power-off
6
~
F
Reserved
(
4
)
Operation order
Master gives control order to slave and it exists in all types of data frame (master sends 4th and
5th
)
shown as bellow
:
Data
Operation
Data
Operation
00H Invalid order
10H Set slave running freq
01H FWD running startup
11H
FWD running startup with running freq set
02H REV running startup
12H REV running startup with running freq set
03H Stop
13H Stop with running freq set
04H Slave FWD jog
14H FWD jog running with running freq set
05H Slave REV jog
15H REV jog running with running freq set
06H Jog running stop
16H Jog stop with running freq set
…
…
…
…
20H Slave
failure
reset
30H Reserved
21H Slave urgent stop
31H Reserved
E300 Series Mini-type Integrated Universal Inverter Manual