Installing the Server Into a Rack
37
FIGURE:
Removing the CMA Flat Cable Covers
b. Apply upward pressure to the outside edge of each hinge connector until the
hinge connector comes off the hinge [frame 3].
c. Repeat
Step a
and
Step b
to remove all three cable covers.
d. One at a time, position each round cable cover horizontally over the hinges,
and align the hinge connectors with the hinges.
e. Using your thumb, apply downward pressure on each hinge connector to
snap the hinge connector into place.
f. Swing the cable covers down and press down on the cable cover handle to
lock them into the closed position.
4. Ensure that the six Velcro straps are threaded into the CMA as shown in
FIGURE: Second-Generation CMA Components on page 35
.
Note –
Ensure that the two Velcro straps located on the front slide bar are threaded
through the opening in the top of the slide bar as shown in
FIGURE:
Second-Generation CMA Components on page 35
. This prevents the Velcro straps
from interfering with the expansion and contraction of the slide bar when the server
is extended out of the rack and returned into the rack.
Содержание X3-2
Страница 1: ...Sun Server X3 2 formerly Sun Fire X4170 M3 Installation Guide Part No E22359 14 April 2014 ...
Страница 12: ...xii Sun Server X3 2 Installation Guide April 2014 ...
Страница 16: ...4 Sun Server X3 2 Installation Guide April 2014 ...
Страница 68: ...56 Sun Server X3 2 Installation Guide April 2014 ...
Страница 100: ...88 Sun Server X3 2 Installation Guide April 2014 ...
Страница 139: ...Configuring Server Drives for OS Installation 127 4 Click Virtual Drives The Virtual Drives screen appears ...
Страница 162: ...150 Sun Server X3 2 Installation Guide April 2014 ...