background image

Sun Microsystems, Inc.
www.sun.com

Submit comments about this document at:

http://www.sun.com/hwdocs/feedback

Sun Fire

V890 Server

Rackmounting Guide

Part No. 817-6264-10

May 2004, Revision A

Содержание Sun Fire V890

Страница 1: ...Sun Microsystems Inc www sun com Submit comments about this document at http www sun com hwdocs feedback Sun Fire V890 Server Rackmounting Guide Part No 817 6264 10 May 2004 Revision A...

Страница 2: ...VALID Copyright 2004 Sun Microsystems Inc 4150 Network Circle Santa Clara Californie 95054 Etats Unis Tous droits r serv s Sun Microsystems Inc a les droits de propri t intellectuels relatants la tech...

Страница 3: ...tions 6 Tools Equipment and Documentation Required 8 Preparing the Server 8 Remove Components 9 Overview of Parts to Be Removed From the Chassis 9 Remove the Handle From Each Side Door 10 Remove the F...

Страница 4: ...the Server Into the Sun Rack 900 Cabinet 35 Before You Begin 36 Safety and System Performance Cautions 36 Tools Equipment and Documentation Required 37 Preparing the Server 38 Remove Components 38 Ov...

Страница 5: ...ach Side Door 67 Remove the Fenders and Lower Side Panels 69 Install the Lifting Handles 72 Attach the Cable Management Bracket to the Server 73 Preparing the Cabinet 74 Installing the Tray Assembly I...

Страница 6: ...vi Sun Fire V890 Server Rackmounting Guide May 2004 A Requirements for 19 Inch Cabinets 93 B Requirements for Sun Rack 900 Cabinets 95...

Страница 7: ...ating System software How This Book Is Organized The chapters in this book are organized as follows Chapter 1 describes the contents of the rackmounting kit Chapter 2 provides step by step instruction...

Страница 8: ...d in this document go to http www sun com service contacting Sun Welcomes Your Comments Sun is interested in improving its documentation and welcomes your comments and suggestions You can submit your...

Страница 9: ...Preface ix...

Страница 10: ...x Sun Fire V890 Server Rackmounting Guide May 2004...

Страница 11: ...the cabinet To install the server into an Electronic Industries Association EIA compliant 19 inch 48 26 cm wide cabinet see Chapter 2 To install the server into a Sun Rack 900 cabinet see Chapter 3 T...

Страница 12: ...each Sun Fire V890 server you intend to install into a cabinet Each rackmounting kit contains the following parts Tray assembly Cable management bracket for the server EIA compliant rack kit only Cabl...

Страница 13: ...ng figure shows the screws at actual size Any screws not used in the rack installation are spares Note Bar nuts are required but not included for non threaded cabinets See the cabinet instructions for...

Страница 14: ...2682 01 in the rackmounting kit The following illustration shows the additional short rear brackets Note You can install only one Sun Fire V890 server into a Sun Fire Expansion Cabinet What Next To in...

Страница 15: ...re the cabinet See Preparing the Cabinet on page 18 Install the tray assembly into the cabinet See Installing the Tray Assembly Into the Cabinet on page 18 Install the server into the tray assembly Se...

Страница 16: ...flects the cautionary measures described Unpack the rackmounting kit and verify that you have all the components and hardware described in Inventory on page 2 Gather the required tools See Tools Equip...

Страница 17: ...ed securely to the floor or equipped with a sturdy and extendable anti tip leg If there are feet beneath the cabinet to prevent it from rolling be sure the feet are fully extended downward to the floo...

Страница 18: ...service technician should complete the following tasks Power off the system and disconnect the server s power cords network cables and I O cables See the Sun Fire V890 Server Service Manual for instr...

Страница 19: ...you attempt to install it into the cabinet To reduce the weight of the server a qualified service technician should remove the following components All power supplies All CPU Memory boards All CPU fan...

Страница 20: ...The following sections provide detailed information about removing each part Remove the Handle From Each Side Door 1 Open one of the server s side doors Use the key provided with the server to unlock...

Страница 21: ...Installing the Server Into a 19 Inch Cabinet 11 2 Remove the pawl from the side door On the inside of the door remove the slot head screw from the center of the pawl Pull the pawl straight out to remo...

Страница 22: ...Remove the side door handle Remove the nine screws from the inside of the door From the outside of the door pull the handle straight out to remove it Note The lock remains in the handle 4 Repeat Steps...

Страница 23: ...you reconfigure the server as a deskside unit Remove the Fenders and Lower Side Panels 1 Remove the fender from the front of each of the lower side panels a Remove the screw from the top of the fender...

Страница 24: ...ide panel Note On the left side of the server do not remove the screw that attaches the small bracket to the side of the server Removing this screw prevents the front door from closing securely 3 Gras...

Страница 25: ...using two M4 screws to attach each handle to the lower side of the server a With the THIS SIDE UP label facing upward insert the screwdriver through one of the access holes on the outside of the hand...

Страница 26: ...the server Attach the Cable Management Bracket to the Server The cable management bracket that attaches to the back of the server provides strain relief for the cables See Managing Cables on page 31 f...

Страница 27: ...r 2 Installing the Server Into a 19 Inch Cabinet 17 2 Attach the cable management bracket to the back of the server Attach the cable management bracket using three M4 screws as shown in the following...

Страница 28: ...net See the instructions provided with the cabinet 2 Open the front and rear doors See the instructions provided with the cabinet 3 Remove if applicable the front and rear doors and the side panels of...

Страница 29: ...face of the front bracket to the inside face of the rear bracket If this measurement is longer or shorter than the cabinet s depth which you measured in Step 1 you must adjust the rear bracket on eac...

Страница 30: ...he cabinet If you are installing two Sun Fire V890 servers into the cabinet install the lower server first To determine the vertical position of the server identify which cabinet rail holes to use for...

Страница 31: ...ay Assembly to the Cabinet Using the rail holes you marked in Determine the Vertical Position of the Server in the Cabinet on page 20 attach the tray assembly to the cabinet by completing the followin...

Страница 32: ...ition of the Server in the Cabinet on page 20 Secure the front brackets using one 10 32 screw in the lower hole of each bracket Finger tighten the screws Align the upper hole of each front bracket wit...

Страница 33: ...front to back and left to right Adjust as necessary 4 Once the tray assembly is level completely tighten all of the bracket screws Tighten the eight 10 32 screws that secure the front and rear bracke...

Страница 34: ...grasp the tray handle and pull the tray toward you until it stops Caution Do not place your fingers on the tray or under the server while you are lifting the server and positioning it on the tray 3 Pl...

Страница 35: ...ert the screwdriver through one of the access holes on the outside of the handle Using the access hole makes it easier to reach the opposite screw hole on the inside of the handle to remove the screw...

Страница 36: ...26 Sun Fire V890 Server Rackmounting Guide May 2004 6 Secure the handles to the rack for safekeeping You must reattach the handles if you need to remove the server from the cabinet...

Страница 37: ...rews on each side of the server as shown in the following figure Do not tighten the screws until all screws are in place and you check the placement of the server 8 Check that the server is level and...

Страница 38: ...the server s side doors securely 4 Slide the tray assembly into the cabinet 5 Install the power supplies that you removed before you installed the server into the cabinet See the Sun Fire V890 Server...

Страница 39: ...V890 server key into the keylock on the tray handle and turn the key 90 degrees counterclockwise Locking the tray handle extends the security plates so that they cover the screw heads on each side of...

Страница 40: ...l Using the two captive screws attach each trim strip If only one screw on each trim strip aligns with a rail hole use one screw to attach each trim strip to each front rail Restoring the Cabinet 1 Re...

Страница 41: ...the following general guidelines for more information In addition some cabinets have cable management features or optional cable management accessories The following general guidelines describe techn...

Страница 42: ...et that attaches to the rear of the cabinet provides strain relief for the power cord and other server cables Releasable tie wraps provided with the rackmounting kit can be used to secure the cables S...

Страница 43: ...r cable management scheme What Next Connect the server power cords network cables and I O interface cables to the server and route the cables allowing enough slack for service access See How to Instal...

Страница 44: ...34 Sun Fire V890 Server Rackmounting Guide May 2004...

Страница 45: ...repare the server See Preparing the Server on page 38 Prepare the cabinet See Preparing the Cabinet on page 46 Install the tray assembly into the cabinet See Installing the Tray Assembly Into the Cabi...

Страница 46: ...mponents and hardware described in Inventory on page 2 Gather the required tools See Tools Equipment and Documentation Required on page 37 Safety and System Performance Cautions Adhere to the followin...

Страница 47: ...e server as low as possible in the cabinet For best stability do not install the server above equipment that weighs less than the server If you will be installing two servers in a cabinet install the...

Страница 48: ...side door handles See Remove the Handle From Each Side Door on page 40 Remove the fenders and lower side panels See Remove the Fenders and Lower Side Panels on page 42 Install the lifting handles See...

Страница 49: ...to Be Removed From the Chassis The following figure identifies the parts that you must remove from the chassis before you can install the server into the cabinet The following sections provide detaile...

Страница 50: ...m Each Side Door 1 Open one of the server s side doors Use the key provided with the server to unlock the door 2 Remove the pawl from the side door On the inside of the door remove the slot head screw...

Страница 51: ...t 41 3 Remove the side door handle Remove the nine screws from the inside of the door From the outside of the door pull the handle straight out to remove it Note The lock remains in the handle 4 Repea...

Страница 52: ...reconfigure the server as a deskside unit Remove the Fenders and Lower Side Panels 1 Remove the fender from the front of each of the lower side panels a Remove the screw from the top of the fender b...

Страница 53: ...of the server Remove the screw located approximately 3 inches 8 cm from the front of the lower side panel Note On the left side of the server do not remove the screw that attaches the small bracket to...

Страница 54: ...r The lower side panel should disengage as you slide the panel so that you can easily remove it 4 Repeat Steps 2 and 3 for the right lower side panel 5 Place the fenders lower side panels and screws i...

Страница 55: ...de of the handle Using the access hole makes it easier to reach the screw hole on the inside of the handle b Position the screw on the inside of the handle in the hole that is opposite the access hole...

Страница 56: ...nels of the cabinet See the instructions provided with the cabinet Installing the Tray Assembly Into the Cabinet To install the tray assembly into the cabinet complete these tasks If necessary adjust...

Страница 57: ...two 10 32 screws located on the inside rear of each outer slide The screws on the inside of the outer slide and the lock nuts on the outside of the bracket secure the rear bracket to the outer slide b...

Страница 58: ...ertical space to install the server Note Each Sun Fire V890 server requires 17 rack units 29 75 inches 75 6 cm or 51 holes on the vertical rails of the cabinet The Sun Rack 900 cabinet can accommodate...

Страница 59: ...tching holes on the right and left rear vertical rails Count the holes to be sure you are using the holes that match the ones you marked in Step 1 Attach the Tray Assembly to the Cabinet Using the rai...

Страница 60: ...osition of the Server in the Cabinet on page 48 Secure the front brackets using one M6 screw in the lower hole of each bracket Finger tighten the screws Align the upper hole of each front bracket with...

Страница 61: ...ackets to the rear rails of the cabinet using four M6 screws Align the lower hole of each rear bracket with the rail hole you marked in Determine the Vertical Position of the Server in the Cabinet on...

Страница 62: ...the cabinet is stabilized so that the cabinet cannot move or tip forward when the tray is extended and the server is placed on the tray Stabilize the cabinet by implementing the stabilizing features...

Страница 63: ...ts 2 Extend the tray all the way forward Standing in front of the cabinet grasp the tray handle and pull the tray toward you until it stops Caution Do not place your fingers on the tray or under the s...

Страница 64: ...nting Guide May 2004 4 Adjust the server on the tray until the four holes on each side of the server align with the four holes in the tray assembly Tray Align the four screw holes on the tray with the...

Страница 65: ...ing the access hole makes it easier to reach the opposite screw hole on the inside of the handle to remove the screw See the following figure b Remove the two M4 screws that attach each handle to the...

Страница 66: ...server to the tray assembly using the eight M4 screws you removed in Step 5 Use four M4 screws on each side of the server as shown in the following figure Do not tighten the screws until all screws a...

Страница 67: ...stalled the server into the cabinet See the Sun Fire V890 Server Service Manual for installation instructions 2 If you removed the server s side doors replace them Caution Avoid keeping the server s d...

Страница 68: ...nt rails of the cabinet Use one or two M6 screws to attach the tray handle to each front rail If each of the two screw holes on each side of the handle aligns with a rail hole use two M6 screws to att...

Страница 69: ...uctions provided with the cabinet 2 If you removed the side panels from the cabinet do not replace them until you connect and route the server cables Caution To prevent the cabinet from tipping forwar...

Страница 70: ...60 Sun Fire V880 Server Rackmounting Guide May 2004...

Страница 71: ...re You Begin on page 62 Prepare the server See Preparing the Server on page 64 Prepare the cabinet See Preparing the Cabinet on page 74 Install the tray assembly into the cabinet See Installing the Tr...

Страница 72: ...quired tools See Tools Equipment and Documentation Required on page 63 Safety and System Performance Cautions Adhere to the following cautions when installing a Sun Fire V890 server into a cabinet For...

Страница 73: ...rver as low as possible in the cabinet For best stability do not install the server above equipment that weighs less than the server If you will be installing two servers in a cabinet install the lowe...

Страница 74: ...682 01 in the rackmounting kit The following illustration shows the additional short rear brackets Preparing the Server To prepare the server for rackmounting complete the following tasks Power off th...

Страница 75: ...take this precaution may result in personal injury and system damage In order for four persons to lift the server safely you must reduce the weight of the server before you attempt to install it into...

Страница 76: ...Removed From the Chassis The following figure identifies the parts that you must remove from the chassis before you can install the server into the cabinet The following sections provide detailed info...

Страница 77: ...From Each Side Door 1 Open one of the server s side doors Use the key provided with the server to unlock the door 2 Remove the pawl from the side door On the inside of the door remove the slot head s...

Страница 78: ...Remove the side door handle Remove the nine screws from the inside of the door From the outside of the door pull the handle straight out to remove it Note The lock remains in the handle 4 Repeat Steps...

Страница 79: ...you reconfigure the server as a deskside unit Remove the Fenders and Lower Side Panels 1 Remove the fender from the front of each of the lower side panels a Remove the screw from the top of the fende...

Страница 80: ...server Remove the screw located approximately 3 inches 8 cm from the front of the lower side panel Note On the left side of the server do not remove the screw that attaches the small bracket to the si...

Страница 81: ...erver The lower side panel should disengage as you slide the panel so that you can easily remove it 4 Repeat Steps 2 and 3 for the right lower side panel 5 Place the fenders lower side panels and scre...

Страница 82: ...he handle Using the access hole makes it easier to reach the screw hole on the inside of the handle b Position the screw on the inside of the handle in the hole that is opposite the access hole c Atta...

Страница 83: ...ack of the server provides strain relief for the cables See Managing Cables on page 89 for general cable management guidelines 1 Locate the server cable management bracket provided with the rackmounti...

Страница 84: ...net See the instructions provided with the cabinet 2 Open the front and rear doors See the instructions provided with the cabinet 3 Remove if applicable the front and rear doors and the side panels of...

Страница 85: ...tance from the inside face of the front bracket to the inside face of the rear bracket If this measurement is longer or shorter than the cabinet s depth which you measured in Step 1 you must adjust th...

Страница 86: ...ation of the short brackets in the following illustration Use the two rearmost available screw holes on the outer slides Tighten the two 10 32 screws and lock nuts on each slide to secure the short re...

Страница 87: ...cabinet A standard 72 inch 182 8 cm high cabinet can accommodate two Sun Fire V890 servers If the Sun Fire V890 server will be installed immediately above a power sequencer leave at least one free hol...

Страница 88: ...he tray assembly to the cabinet by completing the following steps 1 Attach the front brackets on the slides of the tray assembly to the front rails of the cabinet a With the help of an assistant posit...

Страница 89: ...Position of the Server in the Cabinet on page 77 Secure the front brackets using one 10 32 screw in the lower hole of each bracket Finger tighten the screws Align the upper hole of each front bracket...

Страница 90: ...e in the cabinet rail Secure the brackets to the rails using one 10 32 screw in each upper hole Finger tighten the screws Do not tighten the screws completely until all the screws are in place and the...

Страница 91: ...be sure the feet are fully extended downward to the floor Stabilize the cabinet using the stabilizing mechanisms provided with the cabinet See the instructions provided with the cabinet Caution Befor...

Страница 92: ...2 Extend the tray all the way forward Standing in front of the cabinet grasp the tray handle and pull the tray toward you until it stops Caution Do not place your fingers on the tray or under the serv...

Страница 93: ...o a 31 5 Inch Cabinet 83 4 Adjust the server on the tray until the four holes on each side of the server align with the four holes in the tray assembly Tray Align the four screw holes on the tray with...

Страница 94: ...e access hole makes it easier to reach the opposite screw hole on the inside of the handle to remove the screw See the following figure b Remove the two M4 screws that attach each handle to the server...

Страница 95: ...crews on each side of the server as shown in the following figure Do not tighten the screws until all screws are in place and you check the placement of the server 8 Check that the server is level and...

Страница 96: ...ll components 2 If you removed the server s side doors replace them Caution Avoid keeping the server s doors open for extended periods while the system is operating Server doors must be closed to prev...

Страница 97: ...net Use one or two 10 32 screws to attach the tray handle to the front rails If each of the two screw holes on each side of the handle aligns with a rail hole use two 10 32 screws to attach each side...

Страница 98: ...panels To restore the trim strips 1 Locate the two trim strips provided in the rackmounting kit 2 Attach one trim strip to the right front cabinet rail and one trim strip to the left front cabinet rai...

Страница 99: ...e the following general guidelines for more information In addition some cabinets have cable management features or optional cable management accessories The following general guidelines describe tech...

Страница 100: ...ttaches to the rear of the cabinet provides strain relief for the power cord and other server cables Releasable tie wraps provided with the rackmounting kit can be used to secure the cables See Managi...

Страница 101: ...ur cable management scheme What Next Connect the server power cords network cables and I O interface cables to the server and route the cables allowing enough slack for service access See How to Insta...

Страница 102: ...92 Sun Fire V890 Server Rackmounting Guide May 2004...

Страница 103: ...nd extendable anti tip leg You must prevent the cabinet from moving or tilting forward when one or more systems or devices are fully extended from the front of the cabinet Vertical Space Each server r...

Страница 104: ...inches 91 4 cm from the outside face of the front rail to the outside face of the rear rail Front and rear vertical rail mounting faces must be parallel to each other and to the front plane of the ca...

Страница 105: ...r that prevents the cabinet from moving or tilting forward when one or more systems or devices are fully extended from the front of the cabinet Vertical Space The Sun Rack 900 cabinet provides 38 rack...

Страница 106: ...al mounting rails one pair in front one in back that conform to the EIA RETMA standard for mounting hole spacing Front to rear rail spacing of the Sun Rack 900 cabinet is 27 inches 68 58 cm from the o...

Отзывы: