Installation Data
Electrical Requirements
AC Source Site Requirements
Electrical Element
Requirement
Voltage
100 V AC to 240 V AC (nominal)
Frequency
47–63 Hz
Max. operating current
4.0 amps
Max. surge current
•
20 amps peak on a cold start (after AC has been off
for more than 200 ms)
•
100 amps peak on a warm start (after AC has been
off for less than 200 ms)
Overcurrent protection devices must be provided as part of each host equipment rack.
Circuit breakers are located between the AC source and the Sun StorEdge S1 array enclosure.
Circuit breakers must not trip when presented with inrush current of 100 amps lasting 5 ms.
The power can be disconnected for servicing in any of the following ways:
Disconnect the connector from the power module at the rear of the enclosure.
Turn off the circuit breakers in the rack where the enclosure is mounted.
Disconnect the main plug from the AC source.
DC Source Site Requirements
Electrical Element
Requirement
Voltage
–48 V DC to –60V DC
Max. operating current
4.0 amps
Max. input surge current
•
20 amps peak on a cold start (after AC has been off
for more than 200 ms)
•
100 amps peak on a warm start (after AC has been
off for less than 200 ms)
Note:
The DC power supply range is –40 V DC to –75 V DC, 5 amps max. operating current.
Electrically isolated from any AC source.
Reliably connected to the earth (the battery room positive bus is connected to ground).
Capable of providing up to 200 watts of power per feed pair.
Overcurrent protection devices must be provided as part of each equipment rack.
Circuit breakers must be located between the DC power source and the Sun StorEdge S1 array
enclosure. Two 10−amp, double−pole, fast trip, DC−rated circuit breakers must be used for each
power supply.