Chapter 4 Site Preparation 85
Site Preparation
■
Environmental Requirements
Note:
Although the SL8500 library will function over a full list of
environmental ranges as specified below,
optimal reliability
is achieved
if the environment is maintained between the recommended ranges.
Important:
Although this equipment is designed to operate in environmental
conditions of 20% to 80% humidity, industry best practices recommends
computer rooms maintain a relative humidity of 40% to 50% for best
performance.
Table 40.
Environmental Specifications
Description
Optimum
Recommended Range
Full Operating Range
Temperature
-
Operating
-
Shipping
-
Storing
22°C (72°F)
20° – 25°C (68° – 77°F)
+16° to 32°C (60° to +90°F)
-30° to +49°C (-23° to +120°F)
+4.4° to +32°C (+40° to +90°F)
Relative Humidity
-
Operating
-
Shipping
-
Storing
45%
40% – 50%
20% to 80%
5% to 90%
20% to 80%
Wet bulb
(operating)
+25.6°C (+78°F) maximum, non-condensing
Heat Output
44,380 Btu/hr (maximum loading**)
The equation for heat output is: 3.41214
x
Watts = Btu/hr
Power Consumption
13.0 kW (maximum loading**) or 13.7 kVA
kVA = kWatts
÷
Power factor (Power factor for the SL8500 is 0.95)
**Maximum loading includes 64 tape drives, 4 fully loaded racks, 8 HandBots, all the front frame
components (CAPs, service door, and elevators), plus redundant control modules.
Table 41. Environmental Definitions
British thermal unit
(Btu)
A measure of the amount of heat required to raise the temperature of one
pound of water one degree Fahrenheit. British thermal units are most
commonly associated with power over a unit of time—Btu per hour (Btu/hr).
Relative Humidity
A measure of water vapor in the air.
Temperature
The measurement of hot and cold to specific scales, such as Celsius (also
called centigrade) and Fahrenheit.
The Celsius temperature scale uses 0° for the freezing point of water and 100°
for the boiling point of water. The Fahrenheit temperature scale uses 32° for the
freezing point and 212° for the boiling point.
Watt
A watt is a unit of power or the amount of energy per unit of time. Often the term
watt is used for expressing energy consumption as kW (kilo-Watts).
Wet bulb
The difference in temperature between wet bulb (humidity) and dry bulb
(temperature) provides a measure of atmospheric humidity.
Содержание StorageTek StreamLine SL8500
Страница 4: ...Summary of Changes iv SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Страница 12: ...Contents xii SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Страница 18: ...Tables xviii SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Страница 76: ...Introduction 56 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Страница 97: ...E24254 01 Chapter 3 Site Survey Forms 77 Site Survey Forms Figure 21 Content Management Plan ...
Страница 98: ...Site Survey Forms 78 SL8500 Systems Assurance Guide July 2011 E24254 01 Figure 21 Content Management Plan ...
Страница 137: ...E24254 01 Chapter 4 Site Preparation 117 Site Preparation ...
Страница 138: ...Site Preparation 118 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Страница 163: ...E24254 01 Appendix A Content Management 141 Content Management Figure 47 Content Management Work Sheets ...
Страница 164: ...Content Management 142 SL8500 Systems Assurance Guide July 2011 E24254 01 Figure 47 Content Management Work Sheets ...
Страница 198: ...Electrical Conversions 176 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Страница 206: ...Comparisons 184 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Страница 233: ...E24254 01 Appendix H Partitioning 211 Partitioning Make copies as necessary ...
Страница 240: ...Partitioning 218 SL8500 Systems Assurance Guide July 2011 E24254 01 ...
Страница 251: ...E24254 01 Appendix J Work Sheets 229 Work Sheets Figure 73 Content Management Work Sheet ...
Страница 276: ...Index 254 SL8500 Systems Assurance Guide June 2011 E24254 01 ...
Страница 277: ......
Страница 278: ...Oracle Corporation Worldwide Headquarters 500 Oracle Parkway Redwood Shores CA 94065 U S A ...