Wait for the Power Status LED to turn off.
A lit green LED next to an FMod slot indicates that the FMod slot is powered on by the energy
storage module (ESM). It does
not
indicate a faulty FMod. The ESM must drain before you can
remove the FMod. Wait until the green FMod LED is off
before
removing or installing FMods.
Ensure that the ejector tabs are in the open position.
Line up the flash module with the slot.
Align the FMod notch with the key in the connector. This ensures that the FMod is oriented
correctly.
Push the flash module into the slot until the ejector tabs lock the FMod in place.
If the FMod does not easily seat into the connector, verify that the orientation of the FMod is
correct.
Prepare the server module for operation. See
“Preparing the Server for Operation”on page 34
.
Verify flash module component information.
Use the ILOM web interface or CLI. Refer to the corresponding ILOM documentation.