6 PROFIBUS-DP Option Drive Parameters
27
F6-30
<3> <4>
Node Address
Select the node address of a PROFIBUS-DP Option.
Default: 0
Min: 0
Max: 125
F6-31
Clear Mode Selection
Selects the action to take when a "Clear Mode"
command is received
0: Resets back to 0
1: Maintains the previous value
Default: 0
Range: 0, 1
F6-32
PROFIBUS Map Selection
0: PPO Type
Default: 0
Range: 0
<1> To start and stop the drive through the PROFIBUS-DP network, set b1-02 to “3”. To control the frequency
reference of the drive via the PROFIBUS-DP network, set b1-01 to “3”.
<2> If F6-03 is set to 3, then the drive will continue to operate when an EF0 fault is detected. Take proper safety
measures, such as installing an emergency stop switch.
<3> All node addresses must be unique. Node addresses 0, 1, and 2 are typically reserved for control, maintenance, and
diagnostic equipment. The ERR light will illuminate when 0 or greater than 125 is entered.
<4> Power must be cycled in order for any setting changes to take affect.