4 PROFIBUS-DP Option Components
16
: On /
: Flashing /
×
: Off
◆
Setting Node Address
Set drive parameter F6-30 to a unique node address (Range 0 to 125) on the network.
×
×
×
• Checking
connection with
the drive
• Waiting for data
from the master
• PROFIBUS-DP Option
is reading the node
address or parameter
configuration
• Waiting for initial input
data from master device
–
×
×
×
PROFIBUS-DP
Option Self-
diagnostics error
The PROFIBUS-DP
Option is damaged
Cycle power to the drive. If the LED
status does not change, replace the
PROFIBUS-DP Option
×
×
×
Problem connecting
to the drive
• Problem initializing the
drive and PROFIBUS-
DP Option
• Incorrect node address
• Cycle power to the drive. If the LED
status does not change, replace the
PROFIBUS-DP Option
• Check the node address setting in the
drive (parameter F6-10)
×
×
Waiting for data
from the master
device
Waiting for data from the
master device
(Set_Parm_Message or
Chk_Cfg_Message)
• Check the network settings in the
master
• Make sure the master device is
operating normally
• Check the terminal resistance settings
on the data line
• Look for any problems with the data
line, or if the connector
• Check that the data lines are properly
connected to the drive
×
×
Data is incorrect or
PROFIBUS-DP
Option timed out
waiting for data
The communication
procedure in the master is
set incorrectly
• Check the communication procedure
settings in the master
×
×
Sending or receiving
data
–
–
LED
Communication
Status
Possible Cause
Solution
RUN ERR COMM BF