P6
Parameter
Use UP/DOWN keys to set desired value.
This parameter is used to protect the fan
from restarting in a short period of time
and can be set between 0 to 20 minutes.
Example
: If this parameter is set at 3
minutes, once compressor will cut off at
the set temperature, it will not restart for a
minimum of 3 minutes, even if the
differential is achieved earlier. This
parameter is good to protect the life of the
compressor when there are power
fluctuations and the compressor is
switched off and on within a few seconds.
press the set key.
To change P6 parameter,
05
Function :
To set time delay between
compressor relay restart time.
1 Min
20 Min
3 Min
Range
Min
Max
Fact. Set
Parameter
P5
Example
: The temperature on the
O
display is 28.0 C, whereas the actual
O
temperature is 30.0 C. You may need to
O
set this parameter to 2.0 C, which means
that once out of the programming
parameter, the display will show the
O
O
O
temperature 30.0 C (28.0 C + 2.0 C).
Use UP/DOWN keys to set desired value.
In time it may be possible that the display
may be offset by a degree or so.
To compensate this error, you may need
to add or minus the degrees required to
achieve the correct temperature.
press the set key.
To change P5 parameter,
04
Function :
To set room probe calibration.
-10.0ºC
10.0ºC
0.0ºC
Range
Min
Max
Fact. Set
11
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
12
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
Parameter
P7
06
Function :
To set duration of defrost.
To change the P7 parameter,
press the set key.
Use UP/DOWN keys to set desired value.
0 Min
99 Min
30 Min
Range
Min
Max
Fact. Set
This is maximum amount of time allowed
for defrost. If set to 0, there will be no
defrost cycle.
Example :
If P7 is set to 15 Mins and P8
parameter is set to 1 Hr. then after every 1
Hr defrosting will take place for 15 mins.
P8
Parameter
07
Function :
To set defrost frequency.
To change the P8 parameter,
press the set key.
Use UP/DOWN keys to set desired value.
1 Hr
31 Hrs
6 Hr
Range
Min
Max
Fact. Set Example :
same as P7 parameter.
This is the amount of time between two
defrost cycles.
P9
Parameter
08
Function :
To set power on defrost delay.
To change the P9 parameter,
press the set key.
Use UP/DOWN keys to set desired value.
0 Min
99 Min
0 Min
Range
Min
Max
Fact. Set
This is the amount of time at power on
after which defrosting will take place
once.
If this parameter is set to 0, there will be no
power ON defrost.
Example :
If P9 parameter is 30 mins
then at power after 30 mins defrosting will
take place once.