16
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
Use UP/DOWN keys to set desired value.
Parameter
L1
18
Function :
To set Evaporator Fan stop
temperature.
To change the L1 parameter,
press the set key.
-40.0ºC
50.0ºC
2.0ºC
Range
Min
Max
Fact. Set
Parameter
L2
19
Function :
To set Evaporator Restart
Delay.
To change the L2 parameter,
press the set key.
0 Min
20 Min
1 Min
Range
Min
Max
Fact. Set
Use UP/DOWN keys to set desired value.
L3
Parameter
20
Function :
To set Evaporator Fan status
at compressor off.
To change the L3 parameter,
press the set key.
OFF
ON
ON
Range
Min
Max
Fact. Set
L4
Parameter
21
Function :
To set Evaporator Fan
differential.
To change the L4 parameter,
press the set key.
0.5ºC
20.0ºC
2.0ºC
Range
Min
Max
Fact. Set
15
Sr.
No.
Parameter setting method
Description of parameters and functions.
Parameter
ON : Condenser will be ON
This function is used to decide the
condenser status when hot gas defrost is
ON. This parameter is not applicable for
Heater defrost.
At hot gas defrost,
OFF : Condenser will be OFF
Use UP/DOWN keys to set desired value.
CND7
Parameter
17
Function :
To set condenser status at
hot gas defrost.
To change the CND7
parameter, press the set key.
OFF
ON
OFF
Range
Min
Max
Fact. Set
QFD
Parameter
15
Function :
To set quick freeze duration.
To change the QFD Parameter,
press the set key.
Use UP/DOWN keys to set desired value.
This is the maximum amount of time
allowed for Quick Freeze. If set to “0”,
there will be no quick freeze.
1hr.
Example :
If QFS is set to -20.0ºC, and
quick freeze duration is set to 1 hr ,then
when it is in quick freeze mode, then the
Comp. will work on -20.0ºC set point for
0 Hr
12 Hrs
2 Hr
Range
Min
Max
Fact. Set
Parameter
CND6
16
Function :
To set condenser ON delay
timings.
To change the CND6
parameter, press the set key.
When Compressor delay over Condenser
Fan will come ON first, after cond. On
delay over Comp will come ON.
Use UP/DOWN keys to set desired value.
0 Sec
30 Sec
15 Sec
Range
Min
Max
Fact. Set
Once the fan get OFF at L1 condition, it
will not get restart until L2 duration is over.
This setting is used to limit the Max.
temperature beyond which the Evap.Fan
will cut off.
Example :
If this parameter is set to 2.0ºC,
then Evap. Fan will cut OFF at 2.0ºC.
Example :
If this is set at 1 minutes, Evap.
Fan relay will cut off at the set by Evap.
Fan Stop TC. Parameter but the Fan will
not come on for a minimum of 1 minutes
even if it’s differential is achieved earlier.
Use UP/DOWN keys to set desired value.
compressor OFF.
compressor OFF.
OFF :
Evaporator Fan will be OFF at
ON : Evaporator Fan will be ON at
Use UP/DOWN keys to set desired value.
(2.0ºC-2.0ºC = 0.0ºC) (L1 - L4)
Example :
If L1parameter is set to 2.0ºC,
and if Evaporator Fan differential
parameter is set to 2.0ºC,then Evap. Fan
will cut off at 2.0ºC and restart only at
0.0ºC.