Min : MINIMUM   Max : MAXIMUM
Fact. Set : FACTORY SETTING(DEFAULT)

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

To set other parameter

Press & hold SET key for 
2 seconds 

09

SP

To set the cut-out point of the controller.

Display will change to set value.
The set point value can now be changed 
by using the UP/DOWN key.

01

To change Set Point parameter, 
press the set key.

QFS+0.5

P2-0.5ºC

-20.0ºC

Range

Min 

Max 

   Fact. Set 

QFS

To set the quick freeze set point.

Use UP/DOWN keys to set desired value.

If controller is in quick freeze mode then 
compressor will cut in/ cut out as per this 
set  point  till  the  quick  freeze  duration  is 
over.

02

To change QFS parameter, 
press the set key.

P3+0.5

SP-0.5

-25.0ºC

Range

Min 

Max 

   Fact. Set 

To set other parameter

Press & hold PRG key for 
2 seconds 

PRG

EXIT

End of set mode

03

10

Sr. 

No. 

Parameter setting method

Description of parameters and functions.

Parameter 

01

P2 
Parameter

Function :

 To set allowable high 

temperature limit. 

To change P2 parameter, 
press the set key.

Use UP/DOWN key to set desired value. 
Once set at a particular value, this will not 
allow  the  set  point  to  go  above  this
value and below P3 setting.

Example  : 

Setting  this  parameter  at 

0

50.0 C   will not allow   the set point to go 

0

above  50.0 C  also  if  the    temperature 

0

reaches 50.0 C, the display will show  HT 
(High  Temperature).  The  alarm  will  be 
ON. But at power on till the ADT delay is 
over controller will not generate HT Alarm. 

SP+0.5ºC

50.0ºC

50.0ºC

Range

Min 

Max 

   Fact. Set 

(Message on Display)

(Message on Display)

02

P3
Parameter

Function :

 To set allowable low 

temperature limit.

Example 

 

Setting this parameter at 

Use UP/DOWN key to set desired value. 
Once set at a particular value, this will not 
allow the set point to go below this value 
and above P2 setting.

0

-40.0 C will not allow   the set point to go 

0

below  -40.0 C  also  if  the  temperature 

0

reaches -40.0 C, the display will show  LT 
(Low Temperature). The alarm will be ON. 

To change P3 parameter, 
press the set key.

-40.0ºC

QFS-

0.5ºC

-40.0ºC

Range

Min 

Max 

   Fact. Set 

Example(Cooling Mode) : 

 If the set point 

0

is set at 10.0 C and differential is   set at 

0

2.0 C,  then  when  the    system  reaches 

0

10.0 C, the   comp. relay will cutout. Since 

0

the  differential  is  2.0 C,  the  comp.  Relay 

0

will cutin at 12.0 C

0

0

(10.0 C + 2.0 C).     

 

Use UP/DOWN keys to set desired value.

03

P4
Parameter

Function :

 To set the differential for 

compressor restart. 

press the set key.

To change 

P4 

parameter, 

0.5ºC

20.0ºC

2.0ºC

Range

Min 

Max 

   Fact. Set 

SET MODE

PROGRAM MODE

QFS = Quick Freeze Set Point 

Display  will  show  '0000'.  Set  correct 
password to enter into program mode. The 
display  will  show  'P2'  and  scroll  the 
description of the parameter.
To go to other parameters, use UP / DOWN 
keys. After  desired  value,  press  the  SET 
key & you will see “----” which confirms that 
the  parameter  value  has  been  stored  in 
memory. 

Display will show ‘SP’ and scroll the 
description of the parameter.
To go to other parameters, use UP / 
DOWN keys. After desired value, press 
the SET key & you will see “----” which 
confirms that the parameter value has 
been stored in memory. 

SP : Set Point.

Содержание CRC-2052

Страница 1: ......

Страница 2: ...Oil Pressure Switch OPS I P Index 02 Index DESCRIPTION PARAMETER Pg No To set Evaporator Fan stop temperature To set Evaporator Restart Delay To set Evaporator Fan status at compressor off To set Evap...

Страница 3: ...e compressors from close starts In case of probe error or temperature alarm the instrument signals the event through acoustic signal and by closing the relay contact By pressing the mute key the buzze...

Страница 4: ...Set mode Also used as enter key if controller is in Set mode program mode Also used to save changed value Used to enter in manual defrost and to stop defrost if defrosting is ON Used to enter in fault...

Страница 5: ...ON OFF ON OFF Flashing ON OFF Flashing ON OFF ON OFF ON OFF OFF ON ON OFF ON OFF ON OFF ON OFF 07 High temperature alarm for Room temperature means room temperature is equal or above the set value of...

Страница 6: ...enerate HTAlarm SP 0 5 C 50 0 C 50 0 C Range Min Max Fact Set Message on Display Message on Display 02 P3 Parameter Function To set allowable low temperature limit Example Setting this parameter at Us...

Страница 7: ...press the set key To change P5 parameter 04 Function To set room probe calibration 10 0 C 10 0 C 0 0 C Range Min Max Fact Set 11 Sr No Parameter setting method Description of parameters and functions...

Страница 8: ...f a power failure P10 Parameter 09 Function To set type of defrost To change the P10 Parameter press the set key Use UP DOWN keys to set desired value HTR HTG HTR Range Min Max Fact Set HTR Heater def...

Страница 9: ...e the QFD Parameter press the set key Use UP DOWN keys to set desired value This is the maximum amount of time allowed for Quick Freeze If set to 0 there will be no quick freeze 1hr Example If QFS is...

Страница 10: ...10 0 C to 10 0 C may be offset by a degree or so To compensate for this error you may need to add or minus the degrees required to achieve the correct temperature Setting Use UP DOWN keys to set desi...

Страница 11: ...mpressor current is greater than 15 0 A then and exist till C2 current sensing delay then C OL fault exists and flash on display Compressor will be tripped on this fault NOTE 20 50A CT option availabl...

Страница 12: ...l Mode Use UP DOWN keys to set desired value AUTO Auto mode TON Parameter press the set key To change TON parameter 39 Range Min Max Fact Set Range Min Max Fact Set At room probe fail condition when E...

Страница 13: ...er press the SET key 0 Min 30 Min 7 Min Range Min Max Fact Set Range Min Max Fact Set Parameter LSD Use UP DOWN keys to set desired value 44 Function This parameter is used to enable disable light rel...

Страница 14: ...unction To set display at power OFF mode Use UP DOWN keys to set desired value OFF Display will show OFF TEMP Display will show Temperature LED Display Will be Blank At power OFF mode power OFF LED wi...

Страница 15: ...tion 0 1 C LSV Relay 10A 230vac Resolution 0 1Amp RS485 Connectivity Modbus RTU Protocol Mounting Wall mounting Controller CRC 2052 0 0 Operating Temp 5 C to 50 C non condensing 0 0 Storage temp 20 C...

Страница 16: ...w Connection Diagram To set fault recover delay Get to know your Controller 29 Introduction 29 Instruction Manual LVM Line Voltage Monitor Three Phase VMRC 10 3 Introduction VMRC 10 3 is three phase L...

Страница 17: ...more than TTD value then only fault is raised and this fault is applicable to Under voltage Over voltage and Unbalance fault i e In case of Phase Loss or Phase sequence fault alarm will come immediate...

Страница 18: ...s to set desired value This parameter provided to calibration voltage reading When dsP is L n then it sets calibration for r n Sr No Parameter setting method Description of parameters and functions Pa...

Страница 19: ...7 8 9 R 15 17 19 21 Y B N General Specification Under voltage and Over voltage detection Application Voltage and phase sequence monitoring and controlling Connections Screw terminals 2 5sqmm one wire...

Страница 20: ...36...

Страница 21: ...part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents remain the sole...

Страница 22: ...s Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controlle...

Отзывы: