49
min.
0,2m
min.
0,5m
cyberlab original instructions
© STULZ GmbH – all rights reserved EN/02.2018/G17F
The following installation diagram supports the instructions for the assembly.
water connection of the external humidifier
item designation
Part nr.
1
Ion exchanger SD2800
M88754
2
2x hose 3/4“-connection DN10 1.5m
M88755
3
Conductivity sensor
L80709
4
Stainless steel pipe 0.1m 6x1mm
L11200
5
Straight connector 6-6mm
M54412
6
Connector for PE tube with internal thread 1/4“
M35369
7
PE tube 5m 6x4mm
M03777
8
BNB 5000 A or BNB 8000 A
11.1 option external humidifier
The following parts are delivered with
the external humidifier:
11. options
Item 1
Ion exchanger
Water supply
BNB humidifier
illustr. similar
Item 3 Leitwertfühler
Item 7
PE tube
Sensor line
Power line
Control line
PE conductor
• Install the BNB according to the Technical manual for STULZ UltraSonic humidifier BNB, (subsequently
named briefly BNB manual) pages 36 - 38.
The BNB manual is included with the A/C unit upon delivery and is available as pdf document in the e-Stulz
area, section humidifier.
The BNB must have a minimum distance of 0.5m to the floor and 0.2m to the CyberLab unit. The length of the
electrical supply cables allow an installation in max. 0.6m height for the BNB 5000A (humidifier bottom line).
This height decreases with larger distance to the CyberLab unit.
The installation diagram on pages 23 and 35, as well as the chapter 6 of the BNB manual are not applicable.