32
EN/02.2018/G17F © STULZ GmbH – all rights reserved
cyberlab original instructions
CAutIOn
Risk of bruising limbs
Through air intake limbs can be clamped at the slamming of doors. The doors represent a pro-
tective device. During operation the doors may not be opened and the rear panels may not be
removed.
• Start the unit by pressing the Start/Stop-key on the C7000AT
controller or by typing the command “state start” on the notebook.
• Check after 20 minutes operation, whether bubbles are visible in
the sight glass of the liquid line. If this is the case, refrigerant might
have escaped by a leak.
Check the circuit on leaks, eliminate these and top up the circuit
with refrigerant in regard of the chapter „Maintenance“.
• Check the current consumption of the compressor and the fan
comparing it with the values of the e-data sheet.
Service port X15 in the e-box.