cyberlab original instructions
nOtICe
A too high pre-filling can cause that liquid refrigerant gets in the compressor and the compres-
sor is damaged.
A too low pre-filling leads to the triggering of the LP alarm and shut-down of the compressor.
• Continue the filling while the compressor is running.
• Stop the filling once you see only small bubbles in the sight glass.
• Note the weight of the refrigerant bottle and determine the quantity of charged refrigerant.
This is helpful for later inspections and exchange of the refrigerant charge.
Non-return valve
(supplied loose)
Condenser
Non-return valve
(supplied loose)
external installation
Open stop
valves !
Compressor
Receiver
A/C unit
Oil separator
Evaporator
Hotgas reheat
Oil charge
nOtICe
The A/C unit is prefilled with 0.6 l oil. Further addition of oil damages the compressor.