GULLY INSTALLATION & MAINTENANCE INSTRUCTIONS

APPLICATION

These instructions cover four different styles of gully - 

SWP 52

 (41453), 

SWP 90

 (41454), 

SWP SF

 (41455), 

SWP TF

 (41456)

1.  These gullies are only to be used with the Wasteflo shower waste pump and controller and must be installed by a competent  
 

plumber or specialist flooring contractor.

2.  The integrity of the Gully is dependant on achieving a watertight seal in all applications. A range of  

 

 

 

 

Silicone sealants and mastics are available for this application.

 

Only use a neutral sealant – Acetoxy based sealants 

MUST NOT

 be used as they will be detrimental to   

 

the materials used in the gully manufacture.

3.  These Gully Kits include an Installation Kit for use by the installer. Also included are a Hook and Box  

 

 

Spanner (As shown in Fig. 1) which are for routine maintenance and must be kept by the ‘end user’.

4.  All the Gullies come pre-fitted with the Sensor Switch and Cable in place.

WARNINGS:-

 

Do not pour any corrosive liquids into the Gully such as acids, solvents, oil or paint stripper as this will  

 

damage the materials used in the Gully manufacture and will invalidate the guarantee.

 

As water is heated scale deposits are released in areas of hard water and can cause the Sensor Switch  

 

Float within the Gully to stick and prevent the pump system from operating (see Routine Maintenance  

 section).

 

Acid based descalents and aggressive cleaning agents must not be used to clean the scale in the   

 Gully.

 

It is recommended that a NON ACID based descalent is used to remove limescale when required

 

If in any doubt as to the suitability of the chemical cleaning solutions, please contact our PumpAssist  

 

helpline: +44 (0) 844 98 000 97

SENSOR WIRE (CABLE CONDUIT) AND PIPE - ALL GULLIES

Wooden Floor -  Feed the Pipe and Cable Conduit under flooring as required. Retain / fully support safely both items using pipe /  
 

cable clips as appropriate.

Concrete Floor -  Chase and feed the Pipe and Cable Conduit through flooring as required. Re render 

/ seal flooring ensuring no  

 

damage to the Pipe or Cable Conduit.

Please leave this instruction booklet with the product as it contains maintenance and safety 
information.

Fig. 2

 Assemble to shower tray

Fig. 1

 Unpack & check contents

Fig. 3

 Pipework connection

Fig. 4

 Sensor cable protection

12 mm hole

Finger tighten nut 
around 22 mm 
pipe.

Appropriate cable conduit 
should butt up to gully body.

Shower tray floor

Fig. 1

ASSEMBLY

SWP 52 - 52 mm Shower tray gully

 - Part No. 41453

See note 1

Note 1:  Ensure the Sensor assembly is tight, 
this can be done by using the box spanner 
provided, gently by hand, then  push home the 
Sensor Cover with the 

12 mm hole aligned 

to outlet

.

Содержание Wasteflo

Страница 1: ...er with Tiled Floor Gully SWP TF Part No 46597 Shower Waste Pump Controller with Sheet Vinyl Floor Gully SWP SF Part No 46598 Shower Waste Pump Controller with 90 mm Shower Tray Gully SWP 90 Part No 4...

Страница 2: ...t Wiring Regulations BS7671 This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if t...

Страница 3: ...ightly from the picture above Item Description Qty Item Description Qty Controller 1 Pump 1 Controller bracket 4 Housing 1 Fixing screw 4 M4 washer 2 Mounting washer 3 M4 screw 2 Cable grommet 1 Joker...

Страница 4: ...nce instructions provided with the gully These parts are not supplied Cable to connect pump to controller HO5VV F2 2 5 mm2 IP55 cable connector suitable for 2 5 mm2 cable Screws and raw plugs to mount...

Страница 5: ...sembly must be located away from the direct line of water jets where possible 1 13 Both the controller and pump must be positioned away from heat sources such as radiators and heaters Care must be tak...

Страница 6: ...controller A using the screws C provided Fig 1 Now fix the controller to the wall using suitable fixing screws 3 18 Step 3 Pump installation First fix 3 off adhesive mounting washers D to the back of...

Страница 7: ...disconnection must be incorporated in the fixed wiring 4 17 A suitable method of connection would be via a double pole switched fused connection unit complying with BS 1363 4 protected with a fuse see...

Страница 8: ...our PumpAssist Helpline As water is heated scale deposits are released in areas of hard water It is recommended that a non acid based descalent is used to remove limescale To be carried out every thre...

Страница 9: ...Ensure the Sensor Switch Float is free to move up down on the Shaft 5 If the Sensor Switch Float is stuck not freely moving clean any detriment from the Shaft ensuring no damage to the Shaft or Float...

Страница 10: ...o C Connections Pump connections 22 mm OD compression fitting Pump Duty rating 30 mins on 30 mins off Electrical Power supply phase frequency 230 V a c 1 50 Hz Current full load 0 3 Amps Power consum...

Страница 11: ...ical specification section Check circuit breaker is set Thermal protection activated Wait approximately 20 minutes for the circuit to reset Gully float switch stuck Clean gully to ensure float operate...

Страница 12: ...ied that the product has been purchased within the guarantee term prior to the date of claim such as proof of purchase or the shower waste pump serial number This guarantee is in addition to your stat...

Страница 13: ...co uk and complete a short form which will enable visitors to find your contact details on our web site installer finder Alternatively use your smartphone to scan this QR code and go straight to the f...

Страница 14: ...14 NOTES...

Страница 15: ...15 NOTES...

Страница 16: ...PUMP AS SERIAL NUMBER BELOW COMPLIES WITH THE ESSENTIAL REQUIREMENTS OF THE ABOVE E E C DIRECTIVES RESPONSIBLE PERSON AND MANUFACTURER STUART TURNER LIMITED HENLEY ON THAMES OXFORDSHIRE RG9 2AD ENGLA...

Страница 17: ...se the Sensor Switch Float within the Gully to stick and prevent the pump system from operating see Routine Maintenance section Acid based descalents and aggressive cleaning agents must not be used to...

Страница 18: ...secured by the 4 x M6 Stainless Steel Screws and insert the Temporary Cover Plate into Gully 9 Test drainage system for air and water tightness 10 Concrete Floors make good around the Gully ensuring...

Страница 19: ...e Clamp Ring but not solvent welded at this stage 10 Concrete Floors make good around the Gully ensuring that the Gully Body is fully supported DO NOT rely solely on support under the Gully Flange 11...

Страница 20: ...ensure no damage occurs Fig 13 Flush with clean water 4 Ensure the Sensor Switch Float is free to move up down on the Shaft 5 If the Sensor Switch Float is stuck not freely moving clean any detriment...

Отзывы: