Moving the Cabinet to the Installation Site
1-6
Stratus ftServer V 2404, V 4408, V 6408, and V 6512 Hardware Installation Guide
(R004S)
If the corridor and door dimensions are large enough to accommodate the
unpacked cabinet still tied to its pallet, use a pallet jack to move it from the delivery
site to the installation site, as described in
“Moving the Cabinet to the Installation
If the corridor and door dimensions are too small to accommodate the unpacked
cabinet still tied to its pallet, unpack the cabinet and unload it from the pallet before
you move it to the installation site. In this case, use the pallet jack to move the
unpacked cabinet as close to the installation site as possible. Then, unpack the
cabinet, remove it from its pallet, and roll it carefully on its casters to the installation
site.
Moving the Cabinet to the Installation Site
W A R N I N G
!
To avoid personal injury or damage to the system, two
persons are required to move, unpack, and install an
ftServer system. Because of the size and weight of
ftServer systems, have professional movers deliver
and move the packaged units to the installation site.
C A U T I O N
!
To prevent or minimize condensation on the system’s
internal and external surfaces, avoid exposing the system
to extreme temperature and/or humidity changes when
moving it to the installation site. If the system has been
exposed to extreme temperature or humidity conditions
during transit, or if condensation is present, see the
section
“Stabilizing the System” on page 1-18
stabilization guidelines.
When shipped, the system cabinet is tied to the pallet beneath it. The pallet has a
clearance for a pallet jack to move the unit. When moving a system, follow these
guidelines:
1. Verify that the unpacked system is still secured to the pallet.
2. Use a pallet jack to move the system on its pallet to the installation site.