Circuit Wiring Diagrams
B-4
Stratus ftServer 2510, 4410, and 6210 Systems: Site Planning Guide
(R627)
shows a single-phase 240V AC circuit connection. Note that this application
requires a single-pole circuit breaker.
Figure B-4. Single-Phase 240V AC Circuit Connection
Circuit A or B
X
Y
G (PE)
To power input A or B
Wall
Power Cord
L
N
G (PE)
0V
Single system: 20A maximum
240V
PDU: 20A maximum