Sample PDU Usage Calculation
Rack Configuration Planning
5-5
In the calculations in
, components were added one by one, calculating:
The total current demanded by the components
The total space used in the rack
The total number of outlets required
In this example, two PDUs can provide enough current for the LCD monitor unit, one
tape drive enclosure, one ftScalable Storage system, and three ftServer 2510, 4410, or
6210 systems. This set of components consumes 14.93 amperes; adding another
system would increase the consumption to 17.94 amperes. The configuration also
occupies 6 outlets in the A-side PDU and 19U of rack space.
To add any more components, you require another pair of PDUs.
For information about planning a rack configuration, see:
“Determining PDU Requirements” on page 5-2
“Sample PDU Usage Calculation” on page 5-4
Содержание ftServer 2510
Страница 1: ...Stratus Technologies R627 04A Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide...
Страница 8: ...Tables viii Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Страница 12: ...Preface xii Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Страница 46: ...Grounding Requirements 2 18 Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Страница 50: ...Planning for Cables 3 4 Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Страница 62: ...Modem Requirements for Brazil 4 12 Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Страница 68: ...Sample PDU Usage Calculation 5 6 Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Страница 96: ...Electrical Power Connectors B 10 Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...
Страница 104: ...Index Index 4 Stratus ftServer 2510 4410 and 6210 Systems Site Planning Guide R627...