COmmISSIONING
Controller menu
40
| STE
www.stiebel-eltron.com
Pool hysteresis
f
f
Set the temperature deviation from the set temperature, at
which heating of the swimming pool water starts.
Example
Pool hysteresis
3
°C
Set pool temperature
20
°C
Start swimming pool heating
18.5
°C
End swimming pool heating
21.5
°C
Required heating temperature
f
f
Set the flow temperature at which the pool should be heated.
Minimum compressor stage
f
f
Set the minimum stage at which the heat pump should run to
meet the swimming pool demand.
Maximum compressor stage
f
f
Set the maximum stage at which the heat pump should run
to meet the swimming pool demand.
Switching delay
f
f
Set the time after which the heat pump starts to run when
there is a swimming pool demand.
Pool runtime
f
f
Set how long the heat pump is responsible for swimming
pool heating when there is a swimming pool demand.
When this time has expired, the appliance checks if there is a heat
demand. If there is a heat demand, this demand is processed by
the heat pump.
Pool heating with booster heater
f
f
Activate or deactivate the function.
When the function is activated, the booster heater can be used to
support the heat pump for a swimming pool demand.
Activate booster heater for pool
Can only be activated when the “Pool heating with booster heater”
function is enabled.
f
f
Activate or deactivate the function.
When the function is activated, the booster heater can support the
heat pump when there is a swimming pool demand.
Mixing valves
Heating circuit 1
Activate heating circuit 1
Heating = 0, cooling = 1
Min. flow
Max. flow
Set/actual deviation
Alarm delay
Heating circuit 2 / 3 / 4 / 5
Activate heating circuit x
Selected module
Min. flow
Max. flow
Activate room sensor
Passive = 0, active = 1
Set temperature
Influence of room temperature sensor
Parameter
Unit
Temperature
°C
Current temperature in the heating system
Set temperature
°C
Required temperature in the heating system
Opening level
%
Current opening level of mixing valve
Room temperature
°C
Temperature captured by room sensor
Heating circuit 1
Activate heating circuit 1
f
f
Activate or deactivate the function.
When the function is activated, the settings made here apply for
the corresponding heating circuit. The corresponding symbol ap-
pears in the main menu. The symbol allows you quick access to
this menu.
When the function is deactivated, the higher ranking settings are
used to control the heating circuit.
Heating = 0, cooling = 1
f
f
Set whether the heating circuit is responsible for heating or
cooling operation.
Min. flow
f
f
Set the minimum temperature for the system flow.
Max. flow
f
f
Set the maximum temperature for the system flow.
Set/actual deviation
f
f
Set the maximum temperature deviation at which an error
message is displayed on the appliance.