COmmISSIONING
Controller menu
www.stiebel-eltron.com
STE |
39
EN
GL
ISH
DHW alarm delay
f
f
Set a time after which an error message is displayed on the
appliance. This function delays the appearance of an error
message on the appliance when the DHW temperature at the
draw-off points reaches the limit value.
Alarm limit DHW return
f
f
Set a temperature at which an error message is displayed on
the appliance.
Alarm delay DHW return
f
f
Set a time after which an error message is displayed on the
appliance.
DHW draw-off control – booster heater
f
f
Activate or deactivate the function.
When this function is activated, the DHW between DHW cylinder
and draw-off points is further heated-up with the booster heater.
DHW booster heater start temp.
f
f
Set the DHW temperature at which the booster heater will
support the heat pump.
Booster heater start delay
f
f
Set the time after which the booster heater will support the
heat pump.
DHW booster heater stop temp.
f
f
Set the DHW temperature at which the booster heater will
stop supporting the heat pump.
Water charging system
Activate water charging system
Selected module
Set temperature
Water charging system – activate hot gas function
Alarm delay
Alarm limit
Parameter
Unit
Temperature
°C
Current return temperature from heat exchanger to
heat pump
Activate water charging system
Can only be activated when a module is selected.
f
f
Activate or deactivate the function.
Selected module
f
f
Set the module to which the necessary components are con-
nected.
Set temperature
Water charging system – activate hot gas function
f
f
Activate or deactivate the function.
Alarm delay
f
f
Set a time after which an error message is displayed on the
appliance.
Alarm limit
f
f
Set a temperature at which an error message is displayed on
the appliance.
Pool
Pool
Selected module
Set pool temperature
Pool hysteresis
Required heating temperature
Minimum compressor stage
Maximum compressor stage
Switching delay
Pool runtime
Pool heating with booster heater
Activate booster heater for pool
Parameter
Unit
Pool return temperature
°C
Current return temperature from the pool
Pool flow temperature
°C
Current flow temperature to the pool
Pool
Can only be activated when a module is selected.
f
f
Activate or deactivate the function.
When the function is activated, the heat pump can be used for
pool water heating. The corresponding symbol appears in the
main menu. The symbol allows you quick access to this menu.
Selected module
f
f
Set the module to which the necessary components are con-
nected.
Set pool temperature
f
f
Set the water temperature to which the pool should be heat-
ed.