System layout 1
The controller calculates the temperature difference between
collector sensor S1 and tank sensor S2. If the difference is
larger than or identical to the adjusted switch-on temperature
difference (DT O), the solar pump will be operated by relay 1,
and the tank will be loaded until the switch-off temperature
difference (DT F) or the maximum tank temperature (S MX)
is reached.
R1
Arr 1
S3
1.4 Terminal allocation in the different system layouts
Display Channels
Channel
Description
Terminal
Page
INIT
x*
ODB initialization active
-
37
FLL
x*
ODB filling time active
-
37
STAB
x*
ODB stabilization in progress
-
37
COL
x
Temperature collector
S1
37
TST
x
Temperature tank
S2
37
S3
x
Temperature sensor 3
S3
37
S4
x
Temperature sensor 4
S4
37
TR
x*
Temperature return sensor
S4
37
n %
x
Pump speed R1
R1
38
hP
x
Operating hours R1
R1
38
hP1
x*
Operating hours R1 (if OBST is activated)
R1
38
hP2
x*
Operating hours R2 (if OBST is activated)
R2
38
kWh
x*
Heat quantity kWh
-
38
MWh
x*
Heat quantity MWh
-
38
TIME
x
Time
-
34
Sensors S3 and S4 can optionally be connected for
measurement purposes.
If energy metering (OHQM) is activated, sensor S4 has to be
connected as return sensor.
If the drainback option (ODB) is activated, relay 2 can be used
to operate a booster pump by activating the booster function
(OBST).
S1
S3
S2
S4/TR
R1
R2
exemplary
Drainback system layout
(with booster pump)