System layout 9
The controller calculates the temperature difference between
collector sensor S1 and tank sensor S2. If the difference is
larger than or identical to the adjusted switch-on temperature
difference (DT O), the solar pump will be operated by relay 1,
and the tank will be loaded until the switch-off temperature
difference (DT F) or the maximum tank temperature (S MX)
is reached.
Arr 9
Display Channels
Channel
Description
Terminal
Page
INIT
x*
ODB initialization active
-
37
FLL
x*
ODB filling time active
-
37
STAB
x*
ODB stabilization in progress
-
37
COL
x
Temperature collector
S1
37
TSTB
x
Temperature tank 1 bottom
S2
37
TSTT
x
Temperature tank 1 at the top
S3
37
TRET
x
Temperature heating circuit
S4
38
n %
x
Pump speed relay
R1
38
hP1
x
Operating hours R1
R1
38
hP2
x
Operating hours R2
R2
38
TIME
x
Time
-
34
A heating circuit return preheating will be operated by relay
2, if the temperature difference between sensors S3 and S4 is
larger than or identical to the adjusted switch-on temperature
difference (DT3O). For this purpose, relay 2 will operate the
3-way-valve.