20
S1
S2
S3
R1
R2
System layout 6
The controller calculates the temperature differences
between collector sensor S1 and tank sensors S2 and S3. If
the differences are larger than or identical to the adjusted
switch-on temperature differences (DT1O / DT2O), the solar
pumps will be operated by relay 1 and / or relay 2, and the
respective tank will be loaded until the switch-off temperature
differences (DT1F / DT2F) or the maximum tank temperatures
Arr 6
Tank 1
Tank 2
S4
Display Channels
Channel
Description
Terminal
Page
COL
x
Temperature collector
S1
37
TST1
x
Temperature tank 1 bottom
S2
37
TST2
x
Temperature tank 2 bottom
S3
37
S4
x
Temperature sensor 4
S4
37
n1 %
x
Pump speed R1
R1
38
n2 %
x
Pump speed R2
R2
38
h P1
x
Operating hours R1
R1
38
h P2
x
Operating hours R2
R2
38
TIME
x
Time
-
34
(S1MX / S2MX) are reached. The priority logic causes priority
loading of the selected tank (PRIO), if possible. Loading both
tanks simultaneously is possible as well (PRIO = 0).
Sensor S4 can optionally be connected for measurement
purposes.