background image

                                                                                MANUAL NCBM 01                                                             Revision 14     11/06/2021 

 

STEM S.r.l. via della Meccanica, 2 I-27010 Cura Carpignano- Pavia Italia Tel. +39 0382 583011 Fax +39 0382 583058 www.stemsrl.it [email protected]

 

  

Subject to change without notice, no responsibility will be taken for every detail. © STEM S.r.l.

 

 

 
 

If the above conditions are met the test will start by opening the output O1 (valve V1 closed in testing) and maintaining 
the output O2 closed so that the valve V2 will remain open. The duration of the test valve is set via the parameter “

test 

duration” 

in the configuration user interface, after the test of the first valve, after 5 seconds it will proceed to the tests 

of  the  second  valve  in  a  similar  manner  (activate  O1,  O2  deactivated).  In  case  a  leveling  command  is  activated  (up 
command  active  without  speed  signal  within  5  second),  the  test  is  repeated.  If    during  the  second  attempt  a  leveling 
command  is  activated  again  the  test  failed.  The  alarm  is  signaled  by  the  fault  relay  and  the  lighting  of  the  LED 
indicators. After a switch on/off  of the NCBM01 the alarm remain activated until  the reset button is pusher for at least 
5 seconds. If, during the  test  one of the following commands: 

door open

 or 

down

 or 

up

 followed by the 

speed 

within 

5s, the test is suspended. 
If  a    frequency daily  tests  is  set,  the  device  has  a  time-out  for  the  execution  of  the  test  of  one  hour. If  the  test  is  not 
performed within 1 hour  an alarm is generated. If it is set the tests frequency of one  hour, there is no time-out 
The  parameters  for  the  handling  of  activation  delay  of  the  valves,  during  normal  elevator  operation,  are  configured 
using  the  masks  "Valve  sequence",  "down  valve  closing  delay",  "down  valve  opening  delay",  as  described  in  the 
previous paragraph. 
Thirty seconds before the execution of the test and for the  whole duration of the same, the output TW (test warning) 
will remain active to signal the imminent execution of the test. This function is useful to signal to the control cabinet the 
test coming and to perform the commands necessary for the preparation of the test : door closing, lowest floor... 

2.4  Bucher I-VALVE signal control 

 

 

FIG. 2 Electrical scheme connection for hydraulic lift 

 
 
The configuration Bucher I-VALVE allows to control the timing of the SMA signal when the travel signal is changing 
the state. As indicated in the valve manual, the system detects the 

error1

 and 

error2

 
Error 1 : when travel command goes from high level to low level, the SMA signal should change the state from 0.1s to 
1s after the travel signal change, if the timing is not respected error1 has to be detected 
 
Error 2 : when travel command goes from low to high level, the SMA signal should change the state within  0.1s after 
the travel signal change, if the timing is not respected error2 has to be detected 
 
If the error is detected the Fault relay will change state according to the relay polarity selected in the SW configuration 

 

FNO, in case of alarm FNO, CF is closed 

 

FNC, in case of alarm FNC,CF is closed 
 

Led 3, Led4 and led5 continues to signal the state of the SMA and TRAVEL commands even if  NCBM is in alarm 
The alarm will be maintained until a manual reset will be performed. 
 
 

JP1

T2

D2

D1

JP3

V1

PO2

JP2

T1

A2

A1

PO1

V2

J1

FNC

J2

CF

S1

S2

J3

FNO

K2

Fault Relay

K1

PT2

PT1

A3

A4

 NCBM 01

+24VDC / L1(AC)

TRAVEL 
COMAND

SMA 
SIGNAL

CO

TW

O1

O2

Содержание NCBM 01

Страница 1: ...he safety micro switches mounted on the brake For traction lifts with uncontrolled movement device on the OSG over speed governor NCBM01 allows to monitor the proper functioning of the blocking element electromagnet installed on the OSG All the stopping element down direction valves electrical brakes and the OSG must be certified Main features activation of an output relay in case of failure of th...

Страница 2: ...oes not work under pressure and not being considered in parallel to the main valve of descent does not require monitoring The NCBM01 allows to select the activation sequence valve by setting the parameter valve sequence in the configuration window Using the parameter down valve opening delay the advance opening time of the additional valve is configured while the parameter down valve closing delay...

Страница 3: ...ng normal elevator operation are configured using the masks Valve sequence down valve closing delay down valve opening delay as described in the previous paragraph Thirty seconds before the execution of the test and for the whole duration of the same the output TW test warning will remain active to signal the imminent execution of the test This function is useful to signal to the control cabinet t...

Страница 4: ...h LED5 GREEN Lower floor On Off Lower floor On Off Time verification pending On until SMA signal change the state ALL RED Alarm Off Alarm Off Alarm Off TAB 1 Led Meaning in normal functionality monitor nomonitor I Valve configuration TEST PENDING TEST IN PROGRESS LED OPZ1 OPZ2 OPZ1 OPZ2 LED1 Green Up On Off Valve V1 O1 out On Off Off Valve V1 O1 out On Off LED2 Green Down On Off Valve V2 O2 out On...

Страница 5: ...the configuration window Opening Up Valve Timing you can configure the opening of a single or both valves during upward elevator travel The maximum opening time is configurable to 4s Checking the box always on you can configure the continuous opening of the valves during an upward travel If in the configuration menu the box V1 V2 and always on are selected together the opening and closing of the v...

Страница 6: ...losed FNC in case of alarm FNC CF is closed 3 3 Signalling traction lift LED Brakes deactivated No Alarm Brakes activated Brakes deactivated with alarm Brakes activated with alarm LED1 GREEN OFF Contact1 OFF Contact 1 ON if contact 1 faulty ON if contact 1 faulty LED2 GREEN OFF Contact 2 OFF Contact 2 ON if contact 2 faulty ON if contact 2 faulty LED3 GREEN ON POWER OK ON blink brake activated ON ...

Страница 7: ... Electromagnet driver D1 A3 D2 A4 BTAMP 12V JP3 JP1 JP2 24V Electromagnet OSG Microswitch TEST A1 A2 T1 _ V1 T2 PO1 V2 PO2 J1 K1 Fault Relay NCBM 01 K2 J3 FNO S2 CF J2 FNC PT1 PT2 S1 CO TW O1 O2 VARISTOR Down BTAMP 12V D1 D2 A4 A3 24VDC L1 AC TEST Voltage reference N AC VARISTOR PO2 V2 PO1 V1 R 1Kohm not needed with NCUM Module JP3 Voltage reference N AC 24VDC L1 AC T2 JP2 A2 T1 A1 JP1 Fault Relay...

Страница 8: ...mpulse of 300ms is sent on the O1 output 2 After a set time default 3s the status of the microswitch installed on the OSG is checked NC closed when OSG free to move LED2 OFF then ON 3 If the test fails the alarms will be activated In both cases the signaling outputs activated are TW test warning thirty seconds before the execution of the test and for the duration of the whole test to signal to the...

Страница 9: ... failure In case of power failure the NCBM01 keeps in operation only internal clock After the return of the supply voltage the control unit restores its normal operation within 1 minute The customer can select to use external 12V battery connected to the inputs A3 A4 or to use an internal battery inserted on the front side The internal battery should be type CR2032 220mAh the polarity toward the u...

Страница 10: ... runs up and down checking through the LEDs 1 to Led5 Option 1 and Option 2 that the received signals from the system are correct and the LED FAULT is not activated 3 TEST SIMULATION WITH NEGATIVE RESULT simulate a non opening and a non closing of the microswitch per each of them which is used 4 TEST SIMULATION WITH NEGATIVE RESULT AT THE POWER ON after the alarm generated at the step 3 switch on ...

Страница 11: ...e test will end with positive result 2 TEST SIMULATION WITH NEGATIVE RESULT contact failure to open a Jumper output O1 so that the electromagnet remains always powered b With the system stopped at the bottom floor and with closed doors turn on the test input T1 to GND T2 to 24VAC DC by means of an external pushbuttons After the pending time 30s the test sequence will start sensing an impulse to th...

Страница 12: ... 2014 Approvals IMQ certificate N 847 Name Type Functions Hydro Monitor nomonitor Functions Hydro I VALVE Functions Electric Functions OSG Range V AC DC Max I A Max Power W A1 A2 Power supply Power supply Power supply Power supply Power supply 15 30 0 1 T1 T2 Optoisolated input Immediate test Immediate test 15 30 0 01 D1 D2 Optoisolated input Down contactor TRAVEL Brake coil Down contactor 24 220 ...

Страница 13: ... to change without notice no responsibility will be taken for every detail STEM S r l TAB 9 General technical data 13 Order code CODICE DESCRIZIONE NCBM01 A3 monitoring unit 1SBATTCR2032 Battery CR2032 1 battery is included in the NCBM01 1PUSB2TAMB2M Cable USB 2 0 Type A Mini B length 2m Connector USB Type A Male Type Mini B Male High Full Low Speed USB compatible TAB 10 Order codes ...

Страница 14: ... every detail STEM S r l 14 User interface Configuration 14 1 Driver USB installation Copy a folder on the C disk of your computer the directory STEM_NCBM_APP Before connecting the NCBM check which communication ports are available on the PC Connect the NCBM to the PC via a USB cable and turn it on Windows will detect the new device Install the driver present in the folder C STEM_NCBM_APP inf Chec...

Страница 15: ...pe Hydraulic Options with monitoring without monitoring Date and Time date and time configuration Test Time test hour configuration Test Frequency test frequency once a day or once per hour Test Duration test time duration Valve sequence setting phase shift valves V1 open before and close after V2 or viceversa Down closing valve delay Advance opening time of the additional valve to be set 0 in cas...

Страница 16: ...temsrl it stem stemsrl it Subject to change without notice no responsibility will be taken for every detail STEM S r l 14 2 2 Hydraulic user interface Bucher i VALVE Lift type elevator type Hydraulic Date and Time date and time configuration Active Error errors active Firmware version firmware version Fault Relay Polarity set the fault relay polarity ...

Страница 17: ...responsibility will be taken for every detail STEM S r l 14 2 3 Elettric OSG1 user interface mask Lift type elevator type electric Option type and number of contact to be checked Date and Time date and time configuration Test Duration maximum time out to check the change state of the microswitch max 5s Active Error errors active Firmware version firmware version Fault Relay Polarity set the fault ...

Страница 18: ...t the point 4 3 option 2 to be used with the NCUM devices Date and Time date and time configuration Test Time test hour configuration Test Frequency test frequency once a day or once per hour Test Time Duration maximum time out to check the change state of the microswitch max 5s Active Error errors active Firmware version firmware version 14 3 Global Configuration Save save a specific configuratio...

Отзывы: