D. VERTICAL TERMINATIONS
•
The custom fireplace must terminate with the included approved powered termination cap.
•
NO SUBSTITUTION IS ACCEPTABLE.
•
Carefully follow the instructions included with the approved powered termination cap.
•
DO NOT use an additional speed control on this powervent.
•
You must use the included Capacitor.
8 - VENTING
E. HORIZONTAL TERMINATION VENT CAP LOCATION & CLEARANCES
This gas appliance must not be connected to a chimney serving any other appliance.
•
Terminations against vinyl siding must use a vinyl siding protector. Follow instructions included.
•
DO NOT RECESS TERMINATION KIT INTO OUTSIDE BUILDING MATERIALS - i.e.: brick, stone, siding, etc. If necessary, extend framing so
that termination kit will be exposed once building materials are installed.
•
Vent termination must not be located where it will become plugged by snow or other material. The flow of combustion and ventilation air must be
not obstructed.
LOCATION CLEARANCES:
A. Above grade, veranda, porch, deck, balcony - 12" (305 mm).
B. Operable window or door - 30" (762 mm).
C. Permanently closed window* - 12" (305 mm) (recommended to prevent condensation on window).
D. Ventilated soffit* - 24" (610 mm).
E. Unventilated soffit* - 12" (305 mm).
F. Outside corner* - 12" (305 mm).
G. Inside corner* to non-combustibles - 12” (305 mm).
H. Meter / Regulator: Not to be installed above a gas meter/regulator assembly within 3 ft. (914 mm) horizontally from the center-line of the regulator.
I. Gas Service regulator vent outlet - 3 ft. (914 mm).
J. Non-mechanical air supply inlet to building or the combustion air inlet to any other appliance.
CANADA: 12" (305 mm). US: 9” (229 mm).
K. Mechanical air supply inlet.
CANADA: 6 ft. (1.83 m) US: 3 ft. (914 mm) above if within 10 ft. (3.05 m) horizontal
Massachusetts installations: 10 ft. (3.05 m).
L. Above paved side-walk or paved driveway located on public property - 7 ft. (2.13 m).
M. Under veranda, porch, deck, or balcony (must be fully opened on a minimum of 2 sides) - 18" (475 mm).
N. Between two horizontal terminations - 12" (305 mm).
O. Between two vertical terminations - 12" (305 mm). Terminations may be same height.
P. Above furnace exhaust or inlet - 12" (305 mm).
*Clearance must be in accordance with local installation codes & the requirements of the gas supplier.
VENT TERMINAL
AIR SUPPLY INLET
AREA WHERE
TERMINAL
IS NOT PERMITTED
Figure 8E.1
NOTE: A vent cannot be located directly above a side-walk or paved driveway that is located between two single family
dwellings and serves both dwellings.